Stationary UPS Sizing Calculations – Part Six


in Article “Stationary UPS Sizing Calculations -Part Four”, we explained Selection and sizing of UPS protective devices (CBs or Fuses).

Also, in Article “Stationary UPS Sizing Calculations – Part Five, we explained the following:

  1. Selection and sizing of UPS Cables,
  2. Sizing a generator set for UPS system

 

Today, we will explain the Battery Room Ventilation Calculations.

 

 

 

Battery Room Design Criteria

 

 

 

There are many critical design issues that must be taken into consideration when planning, designing and constructing a safe and reliable battery room. Many of the model building codes and recognized standards such as IEEE, OSHA, NEC, and NFPA Life Safety Codes outline the requirements for the design and installation of battery rooms. 



They provide guidance on the performance criteria for the various systems as well as requirements for related equipment. These requirements are as follows:

 

  1. General Requirements,
  2. Mechanical Requirements,
  3. Electrical Requirements,
  4. Fire protection Requirements.

 

  

 

1-      General Requirements


  • Comply with NFPA 70E Article 320.6 (2004 Edition) for battery room design and NFPA 70E Article 480 for battery room ventilation requirements.
  • Occupational Safety and Health Standards (OSHA) require battery installations to have environment control and ventilation. Other mandatory regulation standards may include Title 29 Code of Federal Regulations (CFR) Parts 1910 &1926 and Title 40 Code of Federal Regulations Protection of Environment.
  • Provide a battery enclosure that is commercially manufactured, designed and UL listed for battery containment. It should have an integral electrolyte spill containment.

 

 

 

 

2-      Mechanical Requirements


A- Temperature Control

 

  • For optimal battery performance, the battery room temperature should be maintained at a constant 77°F. Temperatures below 77°F increase the battery’s life but decrease its performance during heavy discharge. In room temperatures above 77°F, battery performance increases but its life decreases.
  • Comply with the following IEEE documents for temperature control criteria, as appropriate for the selected battery type:

  1. IEEE Std. 484-2002, IEEE Recommended Practice for Installation Design and Installation of Vented Lead-acid Batteries for Stationary Applications.
  2. IEEE Std. 1106-2005, IEEE Recommended Practice for Installation, Maintenance, Testing, and Replacement of Vented Nickel-Cadmium Batteries for Stationary Applications.
  3. IEEE Std. 1187-2002, IEEE Recommended Practice for Installation Design and Installation of Valve-Regulated Lead-acid Storage Batteries for Stationary Applications.

 

B- Ventilation

 

  • Battery rooms shall be designed with an adequate exhaust system which provides for continuous ventilation of the battery room to prohibit the build-up of potentially explosive hydrogen gas. During normal operations, off gassing of the batteries is relatively small. However, the concern is elevated during times of heavy recharge of the batteries, which occurs immediately following their rapid and deep discharge.
  • The dual explosion proof fan shall be installed with a remote alarming capability to report a hydrogen gas build up and abnormal operating conditions. Refer to Section 2 for details.

 

 

 

 

3-      Electrical Requirements 


A- General

  • All electrical equipment or fittings installed in a battery room must be intrinsically safe to reduce the risk of arcing, flashing or ignition.
  • The ventilation fans shall be provided with the single-phase squirrel-cage induction type motors suitable for direct-on-line starting. These shall be Class I Division II ‘non-sparking’ motors.
  • Battery rooms shall be equipped with a centralized Emergency Power-Off (EPO) system than can disconnect power to the load centers (UPS common battery bus or individual UPS modules). This EPO system enables the facility management team to quickly isolate a battery system experiencing problems and thereby mitigating a potentially dangerous situation. An EPO device should be located at all egress points from the room and be tied into the central alarm system and monitored.
  • Article 480-9 of the National Electric Code requires a disconnecting means which shall be provided for all ungrounded conductors derived from stationary battery systems over 50 volts.
  • All battery racks and cabinets associated with UPS systems should have NEC code green wire grounds linking all battery racks.
  • Type AC, NM, NMC, NMS and UF cables shall not be used in battery rooms. No flexible metal conduit or flexible metallic tubing shall be used. Connections to battery terminal posts, including inter-cell connections, shall minimize strain on the battery posts.

 

B- Lighting

 

  • Illuminance levels in the battery room shall be designed to meet IESNA Lighting Handbook recommendations with a minimum illumination level of 300lux (30 fc). The lighting design shall consider the type of battery rack and the physical battery configuration to ensure that all points of connection, maintenance and testing are adequately illuminated.
  • The entire lighting installation within the battery room shall consist of explosion proof luminaires which shall be designed in such a way that all possible sources of ignition, such as arcs, sparks and excessive surface temperatures, can be closely controlled and the probability of an explosion occurring is reduced to an acceptably low level.
  • The luminaires shall not be mounted directly over the battery stands and shall be positioned in parallel with the battery stands. This precaution will facilitate maintenance on the fittings, and will also minimize the obvious dangers of working over the cells.
  • Battery room lighting fixtures shall be pendant or wall mounted and shall not provide a collection point for explosive gases. Fixtures shall offer lamp protection by shatterproof lenses or wire guards. Fixtures in battery rooms for vented cells shall be constructed to resist the corrosive effects of acid vapors. Luminaires and lamps shall provide minimal heat output in general and shall provide minimal radiant heating of the batteries. Fixture mounting shall not interfere with the operation of lifting devices used for battery maintenance.
  • Lighting track shall not be installed in battery rooms.
  • Receptacles and lighting switches should be located outside of the battery area.

 

C- Monitoring and Instrumentation

 

  • Provide alarms and instrumentation to measure battery voltage, battery current, ground detection for ungrounded systems and ventilation fan failure/run status.
  • The ventilation system shall include sensors (differential pressure switch) for initiating alarm signals to the central control room in the event of ventilation system failure.
  • Consider the hydrogen gas detection and alarm system interlocked to the exhaust fans. Local codes usually do not require hydrogen and other gas detectors to be installed in dedicated battery rooms. If used, hydrogen detectors should be set to alarm at a maximum of 2% concentration. The detectors should be installed at the highest, draft-free location in the battery compartment or room where hydrogen gas would accumulate.
  • Article 480-9 of the National Electric Code requires each vented battery cell to be equipped with a flame arrester designed to prevent destruction of the cell attributable to an ignition of gases outside the cell.

 

D- Cable Entry Facilities

 



  • Where the cable entry is through the floor, the following shall be adhered to:
  1. The cable opening shall be adjacent to the wall and stands where applicable.
  2. PVC or cement cable pipes curved to the bending radius of the cable shall be cast into the floor in such a way that the entry of the cables into the battery room is perpendicular to the floor.
  3. To prevent fluids or foreign matter from entering the pipe, its upper end shall project at least 50mm above the finished floor surface.
  • For any other form of cable entry, the following shall be adhered to:
  1. These cable entries shall be either vertically from the floor above, if applicable, or horizontally (at a satisfactory height) through one of the battery room walls.
  2. A separate entry, as near as possible to the battery terminals, shall be provided for each battery bank.
  3. These entries shall be kept sealed with vermiculite or equivalent material, to prevent hydrogen transfer before and after installation of the cables.

 

 

 

4-      Fire protection Requirements

 

  • Suitable and adequate number of fire extinguishers and other firefighting equipment should be made available in the workplace. This equipment should also be kept in readily accessible locations.
  • It should be noted that a water type fire extinguisher may not be suitable, as it may short-circuit the batteries. A 10-pound class C fire extinguisher should be located just inside the battery room door.
  • The locations of the fire extinguishers and other firefighting equipment should be made known to the workers.
  • The workers should be trained on the proper use of fire extinguishers and other firefighting equipment.
  • The workers should only try to control the fire when small and manageable. Otherwise, they should evacuate from the workplace immediately and contact the local fire department and other emergency services.

 

 


 

Ventilation Design Criteria

 



The battery room ventilation design criteria include:

  • Design mechanical systems to maintain ventilation rates in accordance with NFPA 70E.
  • Battery room shall be ventilated at high points for removal of accumulated hydrogen. Ideally the battery room exhaust ventilation shall have both high-level exhaust for hydrogen and low-level exhaust for electrolyte spills (acid fumes and odors). Distribute one-third of the total exhaust flow rate to the high-level exhaust to ventilate all roof pockets. Locate low-level exhaust at a maximum of 1-ft above the floor.
  • Hydrogen gas from battery rooms shall be extracted to a safe area, i.e. outdoors, or to an area where the gas will always dissipate into the atmosphere without possible danger of the gas accumulating in any part of that area.
  • The ventilation system for the battery room shall be separate from ventilation systems for other spaces. Air recirculation in the battery room is prohibited.
  • Exhaust air through a dedicated exhaust duct system if the battery room is not located on an outside wall. Ductwork shall be fabricated from fiberglass reinforced plastic (FRP) or polyvinyl chloride (PVC).
  • Design ventilation systems to maintain concentrations of hydrogen gas in the battery room below 1 percent concentration.
  • Design the makeup (replacement) air volumetric flow rate equal to approximately 95 percent of the exhaust flow rate to maintain the battery room under negative pressure and prevent the migration of fumes and gases into adjacent areas.
  • Makeup air can be transferred from a Class 1 or Class 2 area in the facility as defined in ASHRAE 62.1 or supplied directly. If supplied directly, it shall be filtered.
  • The air inlets shall be no higher than the tops of the battery cells of the lower tier if more than one tier is present.
  • Provide means for balancing air flow to ensure a negative pressure relationship. Exhaust all air directly to the outdoors.

 

Fans and Motors

  • The battery room shall be ventilated by means of two exhaust fans (one working + one standby). The standby fan should start automatically in case the other fails, each fan shall have an independent failure alarm. 
  •  The fan shall be mounted as high as possible in the wall, but not below the level of the light fittings. 
  • Fans will have non-sparking wheel construction and motor shall be explosion proof type. Use AMCA 201, Type B spark resistant construction. 
  • Fans shall preferably be roof-mounted with an upwardly directed discharge. Where a roof-mounted ventilator cannot be used, a wall mounted axial type extract fan with back draught dampers shall be used.

 

Note:

  • The ventilation calculation discussed is for flooded cell batteries. VRLA batteries do have relief vents but these do not function unless they are forced into a failure mode. The requirements of a ventilation system must be coordinated with the supplier’s recommendations as well the requirements of a fire prevention and suppression system.

 

  

 

 

Battery Room Ventilation Calculations

 

 

 

Hydrogen is produced during battery charging. If hydrogen gas is allowed to accumulate in an enclosed area, it is readily ignitable and may result in an explosion.

 

How much hydrogen does a battery emit?

As a rule of thumb, when the battery is about fully charged, each charging ampere supplied to the cell produces about 0.0158 cubic feet of hydrogen per hour from each cell. This rate of production applies at sea level, when the ambient temperature is about 77ºF, and when the electrolyte is "gassing or bubbling."

 

The National Fire Protection Association lists the lower explosive level (LEL) of hydrogen as 4% by volume.

 

What does this mean?

LEL is the point at which hydrogen can combust. For example the air in a box with a volume of 100 cubic feet containing 4 cubic feet of hydrogen gas would be expected to ignite when exposed to a spark or open flame. This can be disastrous. Below is a picture depicting the extent of damage due to a ventilation failure.

To ensure safety, most regulations such as the Uniform Fire Code and the International Fire Code stipulate a maximum hydrogen concentration below the level of 1% or 25% of the lower explosion limit LEL in a battery room.

 

 

 

 

Ventilation calculation methods:

  1. NFPA method,
  2. British (metric) units method.

 

 

 

 

First Method: NFPA Method

 

NFPA 1 (2006) Section 52.3.6 — Ventilation:

Ventilation shall be provided for rooms and cabinets in accordance with the mechanical code adopted by the jurisdiction and one of the following:

  • The ventilation system shall be designed to limit the maximum concentration of hydrogen to 1.0 % of the total volume of the room during the worst-case event of simultaneous boost charging of all the batteries, in accordance with nationally recognized standards.
  • Continuous ventilation shall be provided at a rate of no less than 1 ft3/min/ft2 (5.1 L/sec/m2) of floor area of the room or cabinet.

 

The following steps shall be followed:

 

Step 1: Calculate Hydrogen Release

Amount of hydrogen release during normal float condition for a flooded battery is given as:

H = N * I * k

Where:

  • H = Hydrogen generated, in cubic feet per hour (ft3/hr).
  • k = 0.0158 ---- [A typical lead-acid power battery will generate approximately0.0158 cubic feet of hydrogen per cell per hour at sea level, when the ambient temperature is about 77ºF, and when the electrolyte is "gassing”.]
  • N = Number of cells per battery ---- [Note: A single cell is normally 2 volts DC. Therefore, a 6-volt battery normally has 3 cells, and a 12-volt battery normally has 6 cells.]
  • I = Charge current, amperes

 

Step 2: Calculate Room Volume

A room with a flat roof has a volume of:

RV = w x l x h

Where,

  • RV = Room volume
  • w = Room width
  • l = Room length
  • h = Room height

 

Step 3: Determine Critical Volume

The critical volume is the maximum permissible hydrogen concentration to limit the value to below 1% and is given by:

CV = RV * PC

Where,

  • CV = Critical volume in ft3
  • RV = Room volume in ft3
  • PC = Maximum permissible hydrogen concentration to limit the value to below1%.

 

Step 4: Time to reach Critical Level of Hydrogen Concentration

 

t= CV/H

Where,

  • t = time to produce critical level of hydrogen, hrs
  • CV = critical volume, ft3
  • H = hydrogen generated in ft3/hr

 

Step 5: Determining the Ventilation Rate

Q = H/(60*PC%)

Where,

  • Q = Minimum required ventilation airflow rate, in cubic feet per minute (cfm).
  • H = Hydrogen generated, in cubic feet per hour (ft3/hr).
  • PC = Percent concentration of hydrogen allowed in a room is limited to one percent.

 

Step 6: Fan Sizing

Add a 25% safety margin in Step 5. This safety factor is to allow for hydrogen production variations with changes in temperature, charge controller failure, and reduction in net volume of battery room due to battery equipment and fixtures. It also allows for deterioration in ventilation systems. As such:

QA = Q x FS

Where,

  • QA = the actual volumetric ventilation rate, in cubic feet per minute (cfm)
  • FS = Factor of safety, usually 25%.

 

Step 7: Determine Air changes per hour

ACH = QA * 60/RV

Where,

  • QA = Actual ventilation rate in CFM
  • ACH = Air changes per hour
  • RV = Room Volume in cu.-ft

 

Step 8: calculate time required for one air change

 

Time required for one air change = 60 minute/ ACH

 

Step 9: compare results from step 4 and step 8

If step 8 result = step 4 result, then the ventilation is identical to the required and ventilation system is ok.

If step 8 result < step 4 result, then the ventilation is quicker than the required and ventilation system is ok.

If step 8 result > step 4 result, then ventilation system is not adequate.

 

Note:

  • Lower ventilation rates than necessary is a safety issue while over ventilation is a waste of energy, especially where the battery rooms are provided with mechanical air-conditioning to reduce temperature extremes.

 

 

 

 

Example # 1

A 60-cell lead-acid battery, located in a room having a volume of 2000 cubic feet, is being charged at 50 amperes. The ventilation system is designed to provide three air-changes each hour. Determine the rate of hydrogen production and the adequacy of the air exchanges required for ventilation.

Solution:

Step 1: Calculate Hydrogen Release

Hydrogen (H2) production in cubic meters per hour is: H = N * I * k

50 amps * 60 cells * 0.0158 ft3 /cell/hour = 47.4 ft3 /hour

Step 2: Calculate Room Volume

Room having a volume of 2000 cubic feet

 

Step 3: Determine Critical Volume

Critical volume, based on 1 percent by volume is:

2000 ft3 * 0.01 = 20 ft3

 

Step 4: Time to reach Critical Level of Hydrogen Concentration 1%

t= CV/H = 20 ÷ 47.4 = 0.42 hour (25.2 minutes)

The ventilation system must clear the 2000 ft3 room within 0.42 hour (25.2 minutes) before the batteries can produce 20 cubic feet of hydrogen.

 

Step 5: Determining the Ventilation Rate

Q = H/(60*PC%) = 47.4 / (60*0.01) = 79 ft3

 

Step 6: Fan Sizing

QA = Q x FS

QA = 79 x 1.25 QA = 98.75 ft3

 

Step 7: Determine Air changes per hour

Room Volume = 2000 sq.-ft.

ACH = QA * 60/RV

ACH = 98.75 * 60 / 2000 = 2.96 say 3 air changes per hour.

 

Step 8: calculate time required for one air change

Time required for one air change = 60 minute/ ACH = 60/3 =20 minutes

 

Step 9: compare results from step 4 and step 8

Step 4 time = 25.2 minutes

Step 8 time = 20 minutes

 

So, step 8 result < step 4 result,

Then the ventilation is quicker than the required and ventilation system is ok.

Critical hydrogen concentration will not be reached with continuous operation of the ventilation system.

 

 

Example# 2

Same condition as previously mentioned in Example 1, except that the battery is located in a smaller room size of 1000 ft3.

Solution:

Step 1: Calculate Hydrogen Release

Hydrogen (H2) production in cubic meters per hour is:

H = N * I * k = 50 amps * 60 cells * 0.0158 ft3 /cell/hour = 47.4 ft3 /hour

 

Step 2: Calculate Room Volume

Room having a volume of 1000 cubic feet

 

Step 3: Determine Critical Volume

Critical volume, based on 1 percent by volume = 1000 ft3 * 0.01 = 10 ft3

 

Step 4: Time to reach Critical Level of Hydrogen Concentration 1%

Time to produce critical level of 1 percent hydrogen (10 cubic feet) in the 1000 cubic-feet battery room is:

t= CV/H = 10 ÷ 47.4 = 0.21 hour (12.6 minutes)

The ventilation system must move 1000 cubic feet (the room volume), with the 10 cubic feet of hydrogen contained within, before the 0.21 hour (12.6 minutes) elapses.

 

Step 5: Determining the Ventilation Rate

Q = H/(60*PC%) = 47.4 / (60*0.01) = 79 ft3

 

Step 6: Fan Sizing

QA = Q x FS

QA = 79 x 1.25 QA = 98.75 ft3

 

Step 7: Determine Air changes per hour

Room Volume = 1000 sq.-ft.

ACH = QA * 60/RV

ACH = 99.38 * 60 / 1000 = 5.96 say 6 air-changes per hour.

 

Step 8: calculate time required for one air change

Time required for one air change = 60 minute/ ACH = 60/6 =10 minutes

 

Step 9: compare results from step 4 and step 8

Step 4 time = 12.6 minutes

Step 8 time = 10 minutes

So, step 8 result < step 4 result,

Then the ventilation is quicker than the required and ventilation system is ok.

Critical hydrogen concentration will not be reached with continuous operation of the ventilation system.

 

 

Example #3

Per manufacturer specification, one fully charged lead-acid battery cell at 77°F will pass 0.24 amperes of floating current for every 100 ampere-hour cell capacity when subject to an equalizing potential of 2.33 volts. Each cell has a nominal 1,360-amphere hour’s capacity at the 8-hour rate. Calculate the ventilation rate for a battery room consisting of 182-cell battery and 3 battery banks. Assume the battery room has dimensions of 20’ (l) x 15’ (w) x 10’ (h).

Solution:

First, we need to calculate the Charging current

I = FC*AH/100

Where,

I = Charging current, amperes

FC = Float current per 100 ampere-hour. FC varies with battery types, battery condition, and electrolyte temperature.

Ah = Rated capacity of the battery in Ampere hours.

 

I = FC*AH/100 = 0.24*1360/100= 3.264 amps

 

Step 1: Calculate Hydrogen Release

N = 182 cells /battery * 3 battery banks = 546 cells

k = 0.0158 ft3/amp hr cell

H = 3.264 * 0.0158 * 546

H = 28.16 ft3/hr

 

Step 2: Calculate Room Volume

Room Volume = 20 x 15 x 10 = 3,000 cubic feet

 

Step 3: Determine Critical Volume

Critical volume, based on 1 percent by volume = 3000 ft3 * 0.01 = 30 ft3

 

Step 4: Time to reach Critical Level of Hydrogen Concentration 1%

t= CV/H = 30 ÷ 28.16 = 1.07 hour (64.2 minutes)

 

Step 5: Determining the Ventilation Rate

Q = H/(60*PC%) = 28.16 / (60*0.01) = 46.93 ft3

 

Step 6: Fan Sizing

QA = Q x FS

QA = 46.93 * 1.25 = 58.66 ft3/min

The ventilation system should be capable of extracting 58.66 cubic feet per minute.

 

Step 7: Determine Air changes per hour

ACH = QA * 60/RV = 58.66*60/3000 = 1.17 say 2 air-changes per hour


Step 8: calculate time required for one air change

Time required for one air change = 60 minute/ ACH = 60/2 =30 minutes

 

Step 9: compare results from step 4 and step 8

Step 4 time = 64.2 minutes

Step 8 time = 30 minutes

So, step 8 result < step 4 result,

Then the ventilation is quicker than the required and ventilation system is ok.

Critical hydrogen concentration will not be reached with continuous operation of the ventilation system.

 

Notes for example#3:

 

  • There will be 28.16 cubic feet of hydrogen gas produced per hour in a room with a volume of 3000 cubic feet. As an industry standard, the maximum percentage of hydrogen gas allowed within a room should not exceed 1%. This can be estimated by comparing the volume of the room to the amount of hydrogen that could potentially be produced within an hour.
  • If the level in your battery room exceeds 1% after one hour of charging, normally forced ventilation would be recommended. Based on the numbers provided, the room would be at 28.16/3000 = .0094% after 1 hour, which is less than 1%. Therefore, theoretically the forced ventilation may be avoided but is highly recommended due to uncertainties of building geometries, high points, and inadequate or blocked openings for natural ventilation.
  • Exhaust Fan Requirements: Two exhaust fans (one working + one standby) are recommended, each rated for 58.66 cubic feet per minute. The air in the room will need to be completely exchanged every 1.07 hour (64.2 minutes) to maintain a safe level of hydrogen gas.

 

 

Example# 4

In example#3, how much time it will take to build 1% concentration of gas with no ventilation? Assume 1000 cu-ft of room volume is covered by battery equipment.

Solution:

Volume of the room = 3000 cu ft

Volume taken by the batteries infrastructure = 1000 cu ft

Net volume = 2000 cu ft

 

Step 3: Determine Critical Volume

Critical volume, based on 1 percent by volume = 2000 ft3 * 0.01 = 20 ft3


Step 4: Time to reach Critical Level of Hydrogen Concentration 1%

t= CV/H = 20 ÷ 28.16 = 0.71 hour (42 minutes)

 

 

 

 

 

Second method: Metric Units per British Standard BS 6133

 

The following is an extract from BS 6133:1985 – Safe operation of lead-acid stationary cells and batteries:

  • In order to be certain that the ventilation of the battery room is adequate to keep the average concentration of hydrogen gas in the room within safe limits, it is necessary to be able to calculate the rate of evolution of hydrogen. Hydrogen is evolved during a recharge or freshening charge of the battery when the voltage rises above 2.30V per cell. 
  • During this period when the cells are gassing freely, it is recommended that the concentration of hydrogen gas within the battery room is limited to an average of 1%, except in the immediate vicinity of the cell tops. This is only one quarter (25%) of the normally accepted safe limit of 4% hydrogen, but in view of the potential hazard with stationary batteries, this additional safety margin is fully justified.

 

The following method may be used to calculate the ventilation requirements of a battery room. 26.8Ah input to a fully charged cell will liberate 8 g of oxygen and 1 g of hydrogen. One (1) g of hydrogen occupies a volume of 12 liters at 20°C and at a pressure of one standard atmosphere. Therefore 26.8Ah input will evolve 12 liters of hydrogen. Therefore the volume of hydrogen evolved from a battery per hour:

 

H = no. of cells * charge current *12 liter /26.8

H = no. of cells * charge current *0.45 liter

Since 1 liter = 0.001 m3

H = no. of cells * charge current *0.45 * 0.001


H = no. of cells * charge current *0.00045

 

Where:

  • H: the volume of hydrogen evolved from a battery (m3 per hour)

 

The volume of hydrogen found by the above calculation can be expressed as a percentage of the total volume of the battery room, and from this, the number of changes of air per hour to keep the concentration of hydrogen below 1% can be calculated.

 

Example# 5

Consider a battery of 120 cells with charge current of 17 amperes. The battery is installed in a double tier, double row terraced arrangement in a room of 4m x 2m x 3m. Determine the ventilation rate to limit hydrogen concentration to less than 1%.

 

Solution:

Rate of hydrogen produced, H

H = no. of cells * charge current *0.00045

H = 120 x 17 x 0.00045 = 0.92 m3/hr

Maximum permissible concentration of hydrogen, PC = 1% Ventilation required, Q

Q = H/(60*PC%) m3/min

Q = H/PC m3/h

Q = 0.92/0.01 = 92 m3/hr

 

Fan Capacity

QA = Q x 1.25

QA = 92 x 1.25 = 115 m3/hr

  

Room Volume,

RV = 4 x 2 x 3 = 24 m3.

 

Air changes per hour

ACH = QA/RV

ACH = 115/24 = 4.79

Therefore to keep the concentration of hydrogen gas at a maximum of 1%, the air in the room will need to be changed 4.79 times per hour, or about five times per hour.

 

 

 

 

Requirement of Air Conditioner for UPS

 

  

 

UPS system produces heat, which must be removed to prevent the UPS temperature from rising to an unacceptable level. Selection of air conditioner for UPS room requires an understanding of the amount of heat produced by the UPS. Heat is energy and is commonly expressed in Joules, BTU, tons, or calories.

common measures of heat output rate for equipment are BTU per hour, Tons per day, and Joules per second (Joules per second is equal to Watts)

 

Power (KW)

Constant Value

Remarks

1KW

3412.14 BTU/Hr

To convert the heat loss in KW to BTU/Hr,we need to multiply KW with BTU/Hr Constant Value

1KW

3.567 Tonnage

To convert the heat loss in KW to tonnage of AC, we need to divide the KW by constant Value

12000 BTU/Hr

1 RT

RT - Refrigeration tonnage

 

 

The selection of UPS for air conditioner has to be calculated based on:

  • Area of the room,
  • Number of persons who may utilize the room,
  • Sources of heat generation,
  • Insulation of the room.

 

 

 

 

Sizing of Air Conditioner

 

Step 1: Calculate the basic capacity in BTU/Hr required for the UPS room

Multiply the length of UPS room by its width, which will gives us the total area of the room. Based on the below table, the basic capacity in BTU/Hr required for the UPS room can be calculated

 

Total Floor Area in sq m

Basic Cooling Capacity in BTU/Hr

9 -15

5000

15 - 23

6000

23 - 28

6500

28 - 33

7250

33 - 38

8000

38 - 41

8750

41 - 46

9650

46 - 51

10500

51 - 65

12500

65 - 93

15000

93-111

17700

111 - 149

19000 - 24000

149 - 167

24000 – 27000

167 - 260

27000 - 33000

 

Step 2: Arrive at the no of person who will work in the UPS room

Generally the UPS room is unmanned apart from the time when the technician visits to service the UPS or during the visit of maintenance engineer. It is ideal to consider 600 BTU/Hr per person to arrive at the air conditioner capacity of the UPS room.

 

Step 3: Heat Loss of UPS

To arrive at the capacity of the air conditioner required for UPS, we need to calculate the heat loss of UPS in KW using the formula:

Heat Loss of UPS (in KW) = Input Power in KW – Output Power in KW

Heat Loss of UPS (in KW) = Output Power in KW / Efficiency of UPS - Output Power in KW

 

Heat Loss of UPS = heat loss of UPS in KW x 3412.14 BTU/Hr (in BTU/Hr)

 

As a thumb rule, 7% of the UPS capacity can be considered as heat loss which gives the thumb rule formula of

Heat Loss in BTU/Hr = 7% x Capacity of UPS in KW X 3412.14 BTU/hr

 

Step 4: Insulation Loss

As a thumb rule, a 10% of insulation loss can be considered in the calculation

 

Step 5: calculate required tons of Air Conditioner

Sum total heat losses, then

Required tons of Air Conditioner = total heat losses / 12000 

Round the result to the nearest standard value.

 

Step 6: calculate the required air flow

Required air flow = RT (from step 5) * 400 CFM

 

Example#6:

UPS capacity 200KVA

Area of UPS Room 9 sq m (3X3X3,WXDXH in m)

Heat loss of UPS 7%

Heat Loss of Other Loads 1%

No of Person in UPS Room 1

Insulation Loss 10%

 

Solution:

From Step 1:

Area of UPS Room = 9 sq m (3X3X3,WXDXH in m)Capacity in

From Table- , Basic Cooling Capacity in BTU/Hr  = 5,000 BTU/Hr

 

From Step 2:

No of Person in UPS Room = 1 Person

Consider 600 BTU/Hr per person

 

From Step 3:

Heat loss of UPS = 7% * 200 KVA * 3412.14 BTU/hr = 47,770 BTU/Hr

Heat Loss of Other Loads

Assumption of 1% of UPS capacity = 1%*200 KVA*3412.14 BTU/hr = 6,824 BTU/Hr

 

From Step 4:

Insulation Loss

Consider 10% of UPS, Other loads and person heat = 10%* (600+47,770+6,824) = 5,500 BTU/Hr

 

From Step 5:

Total Losses = 600 + 47,770 + 6,824 + 5,500 = 65,694 BTU/ Hr

Required tons of Air Conditioner = total heat losses / 12000 = 65,694 / 12000 = 5.47 RT

Round the result to the nearest standard value = 6 RT

 

From Step 6:

Required air flow = RT (from step 5) * 400 CFM = 6 * 400 = 2400 CFM

 

 

In the next Article, we will explain the Installation and testing of UPS. So, please keep following.

 

Subject Of Pervious Article

Article

Applicable Standards for UPS Systems

What is a UPS?

Why do we need a UPS?

UPS Rating

Classification of UPS:

1-Voltage range,

2-No. of phases,

3- Mobility,

4- Technological design,

 

Classification and Types of UPS – Part One

5- Physical Size/capacity,

6- Form factor/ configurations:

6.1- “N” System Configuration

Classification and Types of UPS – Part Two

6.2- “N+1” System Configuration, which includes:

  • Isolated Redundant Configuration (N +1)
  • Parallel Redundant Configuration (1+1)
  • Parallel Redundant Configuration (N +1)
  • Parallel Redundant Configuration (N +2) and so on

6.3- Parallel Redundant with Dual Bus Configuration (N+1 or 1+1)

Classification and Types of UPS – Part Three

 

 

6.4- Parallel Redundant with STS Configuration

  • Parallel Redundant Configuration (1+1) + STS
  • Parallel Redundant Configuration (N+1) + STS

6.5- System plus System 2(N+1), 2N+2, [(N+1) + (N+1)], and 2N

Classification and Types of UPS – Part Four

 

 

 

7- According to UPS Topology

7.1 Off-line or Standby UPS,

7.2 Line Interactive UPS,

7.3 Standby-Ferro UPS,

7.4 Online Double Conversion UPS,

7.5 The Delta Conversion On-Line UPS.

Classification and Types of UPS – Part Five

 

 

 

8- According to UPS Distribution Architecture

8.1 Centralized UPS Configuration,

8.2 Distributed (Decentralized) UPS Configuration,

8.2.1 Distributed UPS-Zonewise Configuration

8.3 Hybrid UPS Configuration.

Conventional (Monolithic) Vs Modular UPS System:

  • Deploy UPSs in parallel,
  • Deploy UPSs in Series,
  • Use modular UPS products.

Classification and Types of UPS – Part Six

 

 

Three Basic Configurations Of Mains And Bypass For A UPS System:

  • Single mains,
  • Single mains without bypass,
  • Dual mains.

9-According to Use of transformers with the UPS:

  • Transformer based,
  • Transformer less UPS,
  • Transformer less UPS with external input/ output transformer.

Classification and Types of UPS – Part Seven

 

 

 

Transformer Arrangements in Practical UPS Systems:

1-Transformer options for the “single mains” configuration

2-Transformer Options for the “Dual Mains” Configuration

Classification and Types of UPS – Part Eight

 

 

3- Transformer options for “single mains without bypass”

Classification and Types of UPS – Part Nine

Components of Online Double Conversion UPS:

1- Rectifier,

2- Inverter,

3- Energy Storage system:

3.1 Battery

Components of Online Double Conversion UPS– Part One

 

 

 

3.1.1 Battery Configurations

Serial Strings,

Parallel Strings.

3.1.2 Battery Size and Location

3.1.3 Battery Transition Boxes

3.1.4 Battery Monitoring

3.2 Energy Storage System – Flywheel

3.3 Energy Storage system – Super Capacitors

3.4 Hydrogen Fuel Cells

4- Static switch

Earthing Principles of UPS Systems

Components of Online Double Conversion UPS – Part Two

 

 

Evaluation Criteria for Selecting an UPS

 

Evaluation Criteria for Selecting an UPS-Part One

Example: Selecting an Uninterruptible Power Supply (UPS)

UPS System Ratings and Service Conditions

First: from IEC 60146-4

Second: according to American standards

Evaluation Criteria for Selecting an UPS-Part Two

 

 

The UPS sizing calculations steps

Stationary UPS Sizing Calculations – Part One

 

2- Rectifier/Charger Sizing Calculations

3- Inverter sizing calculations & Static Switch Sizing

4- The Battery sizing calculations

First: The Manufacturers’ methods, which include:

  • Method#1:Watts per cell method
  • Method#2:Watts per bank method
  • Method#3:Ampere per cell method

Stationary UPS Sizing Calculations – Part Two

 

 

 

 

Second: The IEEE methods of Battery Sizing Calculations which includes:

  • Method#1: The IEEE 485 method,
  • Method#2: The IEEE 1184 method.

Stationary UPS Sizing Calculations -Part Three

 

 

- UPS Backup time calculation

- Selection and sizing of UPS protective devices (CBs or Fuses)

Stationary UPS Sizing Calculations – Part Four


-Selection of UPS Cables

-Sizing of UPS Cables:

  • UPS Input Cables,
  • UPS Output Cables,
  • Neutral Conductors,
  • UPS to Battery Cables.

-Sizing a generator set for UPS system

Stationary UPS Sizing Calculations – Part Five


 

 

No comments:

Post a Comment