|
Evaluation Criteria for Selecting an UPS The
process for selecting an UPS consists of eight steps (see Fig.1). These steps
are: Step#1:
Determining the need for an UPS, Step#2:
Determining the purpose(s) of the UPS, Step#3:
Determining the power requirements, Step#4:
Selecting the type of UPS, Step#5:
Determining if the safety of the selected UPS is acceptable, Step#6:
Determining if the availability of the selected UPS is acceptable, Step#7:
Determining if the selected UPS is maintainable, and Step#8:
Determining if the selected UPS is affordable. Important
notes: -
The last four steps may require repeating if the UPS does not meet all of the
requirements. - This process does not and cannot provide a “cookbook solution.” Each facility has unique requirements for emergency and standby power. These requirements include:
-
The process does not give a single solution that is applicable to all cases
but it provides the framework for selecting an UPS for any facility. Fig.1: The process for selecting an
UPS |
|
Step#1:
Determine the general need for an UPS. |
|
The process for determining the need for a facility UPS is shown in fig.2. It is mainly depends on:
Fig.2: The
process for determining the need for a facility UPS The number of regulations mandating an
alternate power source to ensure safety of personnel and to prevent pollution
of the environment continues to increase. Consequently, enforcement agencies
should be consulted to determine if an UPS is mandated. They should also be
consulted during design and installation to make sure that the UPS is designed
and installed in accordance with current applicable regulations. |
|
Step#2: Determine the purpose of the UPS. |
|
An UPS may be needed for a variety of purposes. These include:
Some facilities need an UPS for more than one purpose. In any case, the purpose(s) must be known before proceeding because it determines many factors that will drive the amount of power required and the type of UPS that will be needed. These factors are:
|
|
We have two types of applications as follows: 1- Applications cannot tolerate any loss of power, no matter how short the period of time, without loss of life or revenue such as:
2- Other applications may tolerate loss of
power for several minutes (or longer) without any adverse effects like:
Important notes:
Table-1 lists General criteria for
determining the purposes of an UPS and to assist in determining the purposes
of a backup power system, diesel generator, UPS, or combination of diesel may
vary. Table-1 is from IEEE 446 Orange
Book, Emergency and Standby Power Systems for Industrial and Commercial Applications. Table-1 General
criteria for determining the purposes of an UPS |
|
Definition of the terms emergency power and
standby power used in the table-1 as follows: An emergency power system: It can be defined as an independent reserve
source of electric energy that, upon failure of the primary source,
automatically provides reliable electric power within a specified time to
critical devices and equipment which, if they fail to operate satisfactorily,
would jeopardize the health and safety of personnel, result in property
damage, or cause loss of revenue. A standby power system: It is an independent reserve source of
electric energy that, upon failure or outage of the prime source, provides electric
power of acceptable quality so that the user’s facility(ies) may continue
operation in a satisfactory manner. |
|
Step#3:
Determine the power requirements. |
|
After determining the specific purpose(s) for an UPS, the next step is to determine the facility power requirements (see fig.3). This task is essential because it sets the stage for the remainder of the selection process. Undefined power requirements, or oversight of any initial conditions, could result in the selection of a system that is:
Fig.3 the
process of determining the required power capacity. However, to determine the required power
capacity, you need to get answers for the following questions: The first question: how much power is needed? Power requirements can be divided into two categories:
Critical power is used for items such as:
Non-critical power is used for items such
as:
The Second question: how much (if any) to
oversize the unit?
UPS Oversizing rule of thumb A general rule of thumb in oversizing is to
increase the initial power requirement by 30 percent. If oversizing cannot be justified, the UPS
should be selected and the installation designed such that future expansion
can be accommodated at the least possible cost. |
|
Step#4: Select
the Type of UPS. |
|
Selecting a particular type and configuration of an UPS depends on many factors that must be considered according to a facility’s particular requirements. These factors include:
Note that the selection process (see fig.1)
is iterative. The type and configuration of the UPS initially selected is
based on the purpose and power required. If the selected UPS is not
acceptable based on one or more of the remaining factors, another type or
configuration must be selected and the evaluation repeated. The criticality, of the loads will determine the necessary availability of the UPS. Based on the criticality the UPS capacity or configuration can be selected. the following table helps in selecting the proper UPS configuration:
|
|
Step#5:
Determine if the safety of the selected UPS is acceptable. |
|
Safety is basically governed by the electrical codes and standards as adopted by government and commercial agencies, and good judgment on the part of the design and installation team. Batteries pose special safety concerns for the facility manager. Safety problems associated with lead-acid batteries include:
All of these problems can be satisfactorily
handled with the proper safety precautions like:
|
|
Step#6:
Determine if the availability of the selected UPS is acceptable. |
|
Availability definition:
Thus, if an air conditioner is required 12 hours each day, the availability would be 90 percent if it is out of commission an average of 1.2 hours each day. Normally, the required availability for UPS
is 98 percent. The inherent or designed-in availability is usually expressed
as follows: Ai = MTBF /
(MTBF + MTTR) where: Ai is inherent availability MTBF is mean time between failure (a measure
of reliability) MTTR is mean time to repair (a measure of
maintainability) For example, assume the MTBF and the MTTR of a single UPS unit are 500 hours and 20 hours, respectively. The inherent availability of a single unit configuration would be: Ai = 500 / (500+20) = 0.962 The inherent availability of a two-unit
configuration where only one unit is required would be: Ai = A1 + A2 – (A1 x A2) =0.999 The inherent availability of a two-unit
configuration where both units are required would be: Ai = A1 x A2 = 0.925 From the equation for Ai, it is obvious that availability can be increased by:
and The availability could be increased by:
The reliability could be increased by:
MTTR could be decreased by:
|
|
So, Availability is a function of :
|
|
1- UPS reliability. Reliability can be expressed in many was as follows:
Reliability is a function of: a-
The design of the UPS: Redundancy
reduces the overall failure rate of the UPS because one failure does not
cause the UPS to fail. Redundancy
definition: It
is the duplication of elements in a system or installation for the purpose of
enhancing the reliability of the system or installation. Fig.4 Redundancy improves system
reliability The example in fig.4 illustrates why this so. two units may be placed in parallel where each is capable of supplying 100 percent of the load or three units may be placed in parallel where each is capable of carrying 50 percent of the load. The earlier case where one of two units is required is the most reliable. This is shown through the following equations: The reliability where two of three units are required to supply 100 percent of the needed power, is given by the following equation. Reliability = R(t) = 3e-2lt-2e-3lt where: l
is the failure rate of each unit and the units fail exponentially t
is the time over which the system must operate The
reliability where one of two units is needed to supply 100 percent of the
power, the reliability is given by the following equation. Reliability = R(t) = 2e-lt-2e-2lt b-
The configuration selected: Another
significant factor in UPS reliability is the configuration. The different UPS
configurations were discussed in previous articles. c-
The parts used (like battery): The
reliability of the UPS is certainly affected by the battery selected. In
choosing an UPS, criteria that the buyer might use in evaluating the batteries
are shown in table-2. Table-2
Criteria for evaluating UPS battery
d-
The environment in the UPS room: Environmental
factors such as excessive heat, cold, humidity, and/or dust can all have a
significant effect on the UPS reliability. Reliability the six-nine rule
|
|
2- UPS
Maintainability. Maintainability can be expressed in many was as follows:
As already shown by the availability
equation, reducing the time to restore a system after it has failed is
another way to increase availability. Major factors determining the ease and economy with which maintenance can be performed are:
a- capability This capability can consist of built-in
test, manual troubleshooting procedures, or troubleshooting using external
test equipment. b- Accessibility Once the component(s) that caused the system
to fail are identified through the diagnostic capability available for the
system, maintenance personnel must gain access to those components. To some
extent, the accessibility is determined by the installation as well as the
system design. Access to certain areas of an UPS installed
in a very limited space may make repair very difficult even though the UPS
design is very maintainable. (c) Skills and resources Even a system that has the most reliable and
built-in diagnostics and is designed for total accessibility will not be
economical to maintain if: 1- Highly skilled personnel: When highly skilled personnel are required,
the cost of maintenance increases and Training costs also increase. Solution:
personnel will need only low to moderate skills and a minimum of
training. 2- Extensive and expensive equipment are
required: If many expensive test equipment and tools
are needed to support the UPS, this means that the UPS system is not economical. Solution: the only tools required will be
common hand tools normally found in a facility maintenance shop and the
number and cost of test equipment will be minimal. |
|
Step#7:
Determine if the selected UPS is maintainable |
|
Maintenance determines most of the operating cost of an UPS, how?
A system may be inherently maintainable
(i.e., good access, good diagnostics, etc.), but other factors can determine
whether or not the system can be maintained. These factors include: 1- Availability of trained personnel Availability of personnel is a function of:
2- Availability of spares and parts Availability of spares (to replace removed components) and parts (to repair in-place or removed components) depends on the total number initially procured. Replacement and repair then depends on:
3- Location of repair facilities for removed components. Location of repair facilities is important
as follows:
The decision should be made primarily on the
basis of: 1- Cost The cost of hiring and training personnel
should be compared to that of contracting out all or some of the maintenance.
The expected number of repairs should be considered. On the other hand, many contractors require
time (typically 24 hours) to respond to a problem. This additional time may
result in large losses of revenue. Even if internal repair is more expensive,
the added cost may be more than offset by the savings in revenue. 2- Availability A study of high
failure rate components and the stock levels needed to minimize down time is
also important. The contractor might be able to maintain the required stock
levels at a lower cost and might be able to make repairs in a shorter time. |
|
Step#8: Determine if the selected UPS is affordable |
|
Although discussed as the last step in the
selection process, affordability is often a limiting factor in the selection
of an UPS. It is placed last because the pricing of the UPS can only be done
when the type, configuration, and sizing are known. These parameters cannot
be known until the other 7 steps have been completed. When considering the cost of an UPS (or any
product, for that matter), it is best to consider the total cost, or life
cycle cost, that will be incurred. (See fig.5) that describes the process for
determining affordability. Fig.5 the
process for determining affordability For an UPS, the total cost includes:
1- The purchase price and Installation cost The acquisition and installation of the UPS typically constitute the greatest portion of the life cycle cost as follows:
2- Operating and support costs Operating and support costs of the UPS are
usually secondary to the costs of purchasing and installation. However, they can be substantial and should be included as a factor in the final selection. Operating and support costs include:
3- Disposal costs Finally, when an UPS reaches the end of its
life, disposal costs will be incurred. Disposal may simply consist of:
For UPSs containing dangerous or
environmentally unsafe chemicals or materials, disposal is much more
complicated and expensive. For example, disposal of lead acid batteries
must be performed according to all federal, state, and local regulations.
Lead-acid batteries should be reclaimed to avoid the regulatory requirements
for hazardous waste treatment and disposal facilities. Reclamation may be
included as part of a procurement contract for replacement batteries or
contracts may be placed with a permitted reclaiming facility. In disposing of
spent batteries, the facility manager must ensure that batteries meet all
radioactive contamination requirements for uncontrolled release. |
In the next Article, we will explain
the Example for UPS selection & UPS system ratings and sizing. So, please keep following.
|
Subject Of Pervious
Article |
Article |
|
Applicable Standards for UPS Systems What is a UPS? Why do we need a UPS? UPS Rating Classification of UPS: 1-Voltage range, 2-No. of phases, 3- Mobility, 4- Technological design, |
Classification and Types of
UPS – Part One |
|
5- Physical Size/capacity, 6- Form factor/ configurations: 6.1- “N” System
Configuration |
Classification and Types of UPS – Part Two |
|
6.2- “N+1” System
Configuration, which includes:
6.3- Parallel Redundant with Dual Bus Configuration (N+1 or 1+1) |
Classification and Types of
UPS – Part Three |
|
6.4- Parallel Redundant with STS Configuration
6.5- System plus System 2(N+1), 2N+2, [(N+1) + (N+1)], and 2N |
Classification and Types of UPS – Part Four |
|
7- According to UPS Topology 7.1 Off-line or Standby UPS, 7.2 Line Interactive UPS, 7.3 Standby-Ferro UPS, 7.4 Online Double Conversion UPS, 7.5 The Delta Conversion On-Line UPS. |
Classification and Types of
UPS – Part Five |
|
8- According to UPS Distribution
Architecture 8.1 Centralized UPS Configuration, 8.2 Distributed (Decentralized) UPS Configuration, 8.2.1 Distributed UPS-Zonewise Configuration 8.3 Hybrid UPS Configuration. Conventional (Monolithic) Vs Modular
UPS System:
|
Classification and Types of UPS – Part Six |
|
Three Basic Configurations Of Mains And Bypass For A UPS System:
9-According to Use of transformers with the UPS
|
Classification and Types of
UPS – Part Seven |
|
Transformer Arrangements in Practical UPS Systems: 1-Transformer options for the “single mains” configuration 2-Transformer Options for the “Dual Mains” Configuration |
Classification and Types of UPS – Part Eight |
|
3-
Transformer options for “single mains without bypass” |
Classification and Types of
UPS – Part Nine |
|
Components of Online Double Conversion UPS: 1- Rectifier, 2- Inverter, 3- Energy Storage system: 3.1 Battery |
Components of Online Double Conversion UPS– Part One
|
|
3.1.1 Battery
Configurations Serial
Strings, Parallel
Strings. 3.1.2
Battery Size and Location 3.1.3
Battery Transition Boxes 3.1.4
Battery Monitoring 3.2
Energy Storage System – Flywheel 3.3
Energy Storage system – Super Capacitors 3.4
Hydrogen Fuel Cells 4- Static
switch Earthing
Principles of UPS Systems |
Components of Online Double Conversion UPS – Part Two |








No comments:
Post a Comment