In the previous article “Classification and Types of UPS – Part One”, we stated that UPS is classified according to:
- Voltage range,
- No. of phases,
- Mobility,
- Technological design,
- Physical Size/capacity,
- Form factor/ configurations,
- Topology,
- Distribution Architecture,
- Use of transformers.
We already explained the first seven
classifications in the Previous articles (see table in the end of Article).
Today, we will continue explaining
other Classification and Types of
UPS.
|
Eighth:
According to UPS Distribution Architecture |
|
Understanding
the UPS architecture is important as it has a direct influence on the
available power to the protected devices. Many UPS Distribution Architectures divided according to the following Architecture forms:
|
|
First:
Centralized Vs Decentralized UPS Systems |
|
UPS
backup power strategies are deployed in three main Architecture forms: 1-
Centralized UPS Configuration, 2-
Distributed (Decentralized) UPS Configuration, 2.1
Distributed UPS-Zonewise Configuration 3-
Hybrid UPS Configuration. From a technical standpoint they serve the
same purpose, namely, to keep power flowing, particularly during adverse
conditions (i.e., surges, brownouts, fluctuations, total power outages,
frequency differences and other power issues). |
|
1- Centralized
UPS Configuration It is
a system where the UPS is installed in a centralized location like electrical
panel room (see Fig.1), and then the power is distributed across the facility
to support the critical loads generally of larger capacity. The capacity is
decided based on the load level, future expansion plan and the redundancy
levels required. Fig.1: Centralized UPS
Configuration |
|
2- Distributed
(Decentralized) UPS Configuration It Is
a system where a dedicated UPS is installed near to the loads like a rack
mount UPS mounted on the server rack for server’s applications or 600 VA /1KVA
UPS for desktop computers (see Fig.2) Fig.2: Distributed (Decentralized) UPS
Configuration |
|
2.1 Distributed
UPS-Zonewise Configuration The
distributed system can also be zonewise like floorwise or applicationwise (
see Fig.3) which can be based on medium range of UPS System (between 10 -
120KVA), if a UPS fails during a power outage, the impact is limited to the
zone that device supports. Fig.3: Distributed
UPS-Zonewise Configuration |
|
Comparison of Centralized
Vs Decentralized UPS Systems The following table
shows comparison of Centralized Vs Decentralized UPS Systems
|
|
3- Hybrid UPS
Configuration Sometimes a combination of
decentralized and centralized UPS will be more beneficial for the
organization. The two strategies can be
used in combination to provide redundancy to
mission critical applications. For
example, an entire facility may be protected by a large, centralized UPS, but a specific department such as a 24x7 call center may have decentralized UPSs as well to provide redundant protection and possibly extend runtime for call center equipment. |
|
Conclusion: The
decision on which system best fits a particular situation often depends on
three factors:
In
addition, each option has its own advantages and disadvantages, but by giving
full consideration to each UPS solution and the needs of the load and the
requirement of organization, the designers can better determine which of
these strategies is best suited. |
|
Second:
Conventional (Monolithic) Vs Modular UPS System |
|
Data centers with fluctuating needs or future requirements that are difficult to forecast can employ Three strategies to increase the scalability of their UPS deployment:
|
|
1- Deploy UPSs in parallel Parallel UPS architectures boost scalability as well as
redundancy. As their power needs increase, organizations can simply add more
modules to existing UPS systems, rather than replace current devices with new
ones (see Fig.4) If any UPS fails completely, the other systems can keep
protected information technology equipment (ITE) loads operational. Parallel
UPS systems all feed the output bus, so any single UPS module can be isolated
for maintenance or in case of a failure. Parallel systems must be synchronized
together to share the loads. Fig.4: Parallel UPS systems |
|
2- Deploy UPSs in Series In a serial architecture, multiple UPSs are connected end to end
such that if any one UPS in the string fails, the others can compensate
automatically. Fig.5: Serial UPS systems
|
|
3- Use modular UPS products Modualrity refers to:
Some newer UPSs feature modular designs that allow you to add
capacity incrementally as requirements increase. For mid-sized power requirements, building blocks of 50kW may be the best financial solution, allowing scaling from 50 or 100 kW up to 300 to 400kW very easily. Even the latest generation large UPS systems are available in modular 200 to 300 kW increments. That is a scalable and efficient approach to keeping up with escalating power needs that also lowers upfront capital spending and conserves equipment room floor space. |
|
Important note: Keep in mind that, for either of the above options, the premises
wiring should be sized for the maximum possible UPS size, so that future
re-wiring will not be necessary as the UPS system grows. |
|
From the above three strategies we have two types of UPSs (see Fig.6):
Fig.6: Conventional VS Modular UPS
Systems |
|
1-
Conventional (Monolithic) UPS Conventional UPS system is built
mostly based on monolithic concept i.e. a UPS system will have a rectifier
and inverter bridge of its rated capacity to support the loads. The conventional UPS can also be
based on modular construction concept i.e. a UPS system will have 2 or 3
subassemblies of rectifier and inverter bridge which works together to form
the full capacity of the UPS. The conventional UPS systems can
work in standalone configuration or can be paralleled to improve the capacity
or to improve the redundancy levels. The Monolithic UPS will have:
Where:
|
|
2-
Modular UPS System The modular UPS will be built up
with multiple smaller UPS modules and number of UPS modules is paralleled to
achieve the desired level of redundancy. Modular construction concept will
have the same characteristic like monolithic UPS but will have higher
availability. The modular UPS will exhibit a:
The key advantages of Modular construction when compared with monolithic construction are:
|
|
Example#1: Availability Comparison of Monolithic vs Modular UPS
Example#2: Comparison of Foot Print Monolithic vs Modular UPS
|
|
Comparison Of
Conventional Ups Vs Modular UPS
|
|
Conclusion:
|
In the next Article, I will continue explaining other Classifications of
UPS Systems like:
9- Use of transformers.
So, please
keep following.
|
Subject Of Pervious Article |
Article |
|
Applicable Standards for UPS Systems What is a UPS? Why do we need a UPS? UPS Rating Classification of UPS: 1-Voltage range, 2-No. of phases, 3- Mobility, 4- Technological design, |
Classification and Types of
UPS – Part One |
|
5- Physical Size/capacity, 6- Form factor/ configurations: 6.1- “N” System
Configuration |
Classification and Types of UPS – Part Two |
|
6.2- “N+1” System
Configuration, which includes: Isolated Redundant
Configuration (N +1) Parallel Redundant
Configuration (1+1) Parallel Redundant
Configuration (N +1) Parallel Redundant
Configuration (N +2) and so on 6.3- Parallel Redundant
with Dual Bus Configuration (N+1 or 1+1) |
Classification and Types of
UPS – Part Three |
|
6.4- Parallel Redundant with STS Configuration Parallel Redundant
Configuration (1+1) + STS Parallel Redundant
Configuration (N+1) + STS 6.5- System plus System
2(N+1), 2N+2, [(N+1) + (N+1)], and 2N |
Classification and Types of UPS – Part Four |
|
7- According to UPS Topology 7.1 Off-line or Standby UPS, 7.2 Line Interactive UPS, 7.3 Standby-Ferro UPS, 7.4 Online Double Conversion UPS, 7.5 The Delta Conversion On-Line UPS. |
Classification and Types of
UPS – Part Five |






No comments:
Post a Comment