In the previous article “ Components of Online Double Conversion UPS– Part One”, We showed that an online double Conversion UPS has (4) major components As shown in the Fig.1:
- Rectifier,
- Inverter,
- Energy Storage (Battery),
- Static Switch.
Fig.1 Components
of Online Double Conversion UPS
We explained the first three components and indicated that
the energy storage system has many types as follows:
- Battery,
- Flywheels,
- Ultra capacitors,
- Hydrogen Fuel Cells.
We explained the battery and today we will continue
explaining some related topics of battery and other energy storage systems in
addition to this we will explain the earthing principles of UPS Systems.
1- Battery Configurations |
The most used battery configuration are:
Notes:
|
1.1- Serial
Strings A serial string is a single series of blocks
connected ‘end-to-end’ to form the battery. The positive terminal of the
first block is connected to the negative terminal of the second block, the
positive terminal of the second is connected to the negative of the third,
etc. (see Fig.2) Fig.2 Serial
Strings The overall voltage of the battery is the
sum of the individual block voltages and must be arranged to match the float
voltage setting of the UPS. The capacity of the battery is unchanged
with this arrangement, being the same as each individual block. For example: If 12 nos. x 12V 10Ah blocks are connected
in series, the resulting battery is 144V with a 10Ah capacity. |
1.2- Parallel Strings A
parallel string is a combination of two or more serial strings, and each
string must contain the same number of blocks. Batteries are paralleled for
two main reasons:
The positive terminal of the first battery string is connected to the positive terminal of the second battery string, the positive terminal of the second is connected to the positive of the third, etc. (see Fig.3) Fig.3 Parallel Strings The negative terminal of the first battery string is connected to the negative terminal of the second battery string, the negative terminal of the second is connected to the negative of the third, etc. The overall voltage of the battery is the same as the voltage of each string. The
capacity of the battery is the sum of the capacities of the individual
strings. For
example: If
3 strings of 12 nos. x 12V 10Ah batteries are connected in parallel, the
resulting battery is 144V with a 30 Ah capacity. Note:
|
2-
Battery Size and Location |
UPS suppliers offer a range of standard
batteries, all designed to support the full UPS load but with various
back-up/autonomy times. UPS suppliers often accommodate the batteries in different types of steel structure as follows:
Fig.4 UPS
cabinet & Additional cabinets Fig.5 Open type
racks & Cladded racks The table below gives some sample battery sizes and weights.
* Batteries located within the UPS cabinet |
3- Battery
Transition
Boxes |
Transition boxes (see fig.6) are used to
simplify the connection of a battery to a UPS. In addition to providing space
for the correct termination of battery cables. they also contain suitable fuses to protect the individual battery strings and associated cabling. Fig.6 Battery
Transition Boxes When two or more parallel battery strings
need to be connected to the same UPS, it is common to use transition boxes.
Fused transition boxes allow individual battery strings and cables to be
protected and also enable an individual battery string to be safely isolated
for maintenance or repair without completely disconnecting the UPS equipment. It is important to keep the lengths of cables within each battery string approximately the same to ensure that the impedance (and hence the current share) of each battery string is approximately the same |
4- Battery
Monitoring |
Equalization problems can be minimized using
a modern battery monitoring application, such as the patented Battery
Analysis & Care System (BACS), which can provide integrated battery
monitoring and management over an Ethernet network. Using web-management technology, the system
sequentially checks the internal resistance, temperature and voltage of each
individual battery block and corrects its charging voltage as required to
obtain a balanced charging condition across the battery string. By constantly monitoring and controlling the individual charging voltages for each battery block it ensures they are kept in their optimal voltage operating range and guarantees the availability of the battery at all times. Other benefits from using the BACS equalization system include: 1- Avoid overcharging: Through the equalization process the
unnoticed overcharging of individual batteries (gassing, dry-out, thermal
runaway) is prevented. 2- Avoid undercharging: Through the equalization process the
unnoticed undercharging of individual batteries (sulphation, loss of
capacity) is prevented. 3- Indication of battery problems: Typical battery problems such as sulphation,
corrosion, gassing, dryout, thermal runaway etc. are visible through a rise
of impedance and temperature. 4- Avoid sulphation : Sulphation is a typical problem for UPS batteries because they are consistently held at a float charge level for a long time. Its not guaranteed that ALL batteries have really been fully charged when the UPS charge switches from boost charging to float charging. The result maybe that some batteries are overcharged, while others have never been fully charged. Equalization avoids sulphation through the process of bringing the overcharged and undercharged accumulators to a balanced voltage level. 5- Show stratification: BACS warns of a possible stratification of the electrolyte through detecting increasing impedance and drifting voltages. The stratification can be removed through a discharge process and the BACS will indicate this effect through a lower impedance and improved equalizing. 6- Early warning to replace batteries: Through impedance trending you can see in the early stage that some battery blocks are damaged or simply weaker than others. The earlier accumulators are replaced the better for an increased lifetime of the complete battery system. 7- Extension of service life up to 30%: The service life of all the batteries in a string depends on the weakest member – i.e. the weakest battery. By equalizing, all batteries are kept constantly in their ideal voltage window so that all negative influences of wrong charging voltages and currents within the string are eliminated. 8- Improved maintenance: A BACS system improves the service quality
by providing remote monitoring through Internet, VPN or other network for
downloading real time data and battery history for analysis. Single,
individual battery tests are now possible without the need to disconnect
batteries from the group. Maintenance and battery testing are able to take
place at any time, under real operating. |
Second: Energy Storage System - Flywheel |
Flywheel stores electrical energy in
the form of kinetic energy during charging process and during the discharging
the kinetic energy is converted into electrical energy. A typical system consists of (see
fig.7):
Fig.7
Flywheel First generation flywheel energy storage systems use a large steel flywheel rotating on mechanical bearings. Newer systems use carbon-fiber composite rotors that have a higher tensile strength than steel and are an order of magnitude lighter. During charging process, the motor rotates at 1000rpm in clockwise direction to store the electrical energy in the form of kinetic energy. During discharge the motor acts as a generator and will convert the kinetic energy back to electrical energy Magnetic bearings are necessary; in conventional mechanical bearings, friction is directly proportional to speed, and at such speeds, too much energy would be lost to friction. The
flywheel used mainly in rotary UPS systems using rotating mass for energy
storage, rotary UPS systems have more mechanical moving pieces than a static
UPS. The spinning flywheel of a rotary system can typically only provide AC
power for 5–15 s at full load, so a backup source such as a diesel generator
may be coupled to the generator to provide longer runtimes (Fig.8). Fig.8 Diesel Generator with Rotary
UPS & Flywheel
|
Third: Energy
Storage system – Super Capacitors |
SuperCaps (also
known as ultra-capacitors or electric double-layer capacitors) (see fig.9) provide an alternative source of
DC power to traditional rechargeable batteries. Super capacitors are high
density energy storage devices with a capacitance (energy density) of up to
10,000 times that of conventional electrolytic capacitors. Fig.9 SuperCaps Super capacitors or double layer capacitor store energy much in the same way as a conventional capacitor, hence the amount of stored energy can be described by: A double layer capacitor consists of two electrodes, a separator, electrolyte, two current collectors and housing. A very high
capacitance is obtained in this way. Super capacitors are suitable for high
power applications and offer very quick response times and high efficiency. Disadvantages are comparatively low energy density, high self-discharge and high cost. Small units
exists, larger sizes are under development. Typical power
ratings are 1kW-250 kW and efficiencies in the ranges of 85-98%
|
Forth: Hydrogen Fuel Cells |
When hydrogen and oxygen combine to produce
water a chemical reaction occurs, one by-product of which is electrical
energy. Hydrogen fuel cells can therefore be said to convert hydrogen gas
into electrical energy. Fig.10 Hydrogen Fuel Cells Each hydrogen fuel cell (see fig.10) has two electrodes, an anode and a cathode, that are separated by a polymer electrolyte membrane. Oxygen is passed over the cathode and hydrogen is passed over the anode. The hydrogen molecules are converted into electrons and protons when they pass over a catalyst (typically platinum) on the anode. The electrons flow out of the fuel cell as electrical energy whilst the protons flow through a membrane to the cathode where they combine with the oxygen to produce pure water. Figure 8.2 shows a typical hydrogen fuel cell. Hydrogen fuel cells are significantly more expensive than batteries and, because hydrogen is an explosive gas, great care has to be taken with its storage. Also, because hydrogen is currently manufactured from natural gas and energy is required to make the hydrogen the “environmentally friendly” credentials of hydrogen fuel cells are currently questionable. Hydrogen fuel cells are smaller and lighter
than batteries and the research and development currently taking place into
the use of hydrogen fuel cells in automotive applications will have spin-off
benefits for “standby” fuel cell applications. |
4-
Static
switch |
Static Switch The static switch is the last major component in a traditional double-conversion UPS system. The purpose of the static switch is to provide a method to transfer the critical load from the inverter to a bypass source without interruption. If bypass power is available and acceptable, the system will transfer the load to the bypass source. It’s important to understand that bypass power is not UPS protected power. If the input source is lost, the critical load will lose power. The static switch is critical when a UPS has a failure or maintenance is required. The static switch of an on-line UPS has two operational states, ‘on UPS’ (the normal condition) and ‘on bypass’. When the UPS is operating on bypass there will be an accompanying alarm or warning condition as in this state the critical load is not protected from mains disturbance or interruption. In both cases it is the job of the static switch to provide a very fast, break-free, transfer between the inverter output and the bypass. The static switch can be considered to be an intelligent switch that decides whether to use the UPSs inverter output voltage or the raw mains to supply the load. The decision is made by the static switch’s own and/or the UPSs control logic which continually monitors the bypass (raw mains) and inverter voltages. The control logic typically controls the
phase and frequency of the UPS inverter(s) to ensure that the bypass and
inverter voltages are in phase (synchronized) with each other.
Bi-directional, break-free transfer between the two supply sources is only
possible when the bypass and the inverter are ‘synchronized’. As we
mentioned before in Article “Classification and Types of UPS – Part Five” that there are two types of bypasses (see
Fig-11):
Fig.11 UPS bypass switches |
1- Static bypass (internal
Maintenance Bypass): It gets its name from the original UPS systems using a “static switch” to bypass the rectifier and inverter when a fault occurs. This allows the load to continue to operate from unprotected power. The switch is called static because
it is an electronic switch that is solid state, not mechanical. The static switch provides a method
to bypass the rectifier and inverter when maintenance must be completed
without shutting down the load. Note: Although
the UPS power blocks can be totally isolated while the load is powered
through the maintenance bypass supply, making it safe to carry out
maintenance procedures etc., there will still be live power within the UPS at
its power isolators and input/output terminal connections. 2- Maintenance bypass (External Maintenance
Bypass): It Is external manual switch separated from the UPS, It is usually a wrap-around switch either of rotary or MCB design , this switch ensures a continuous flow of power while your UPS is undergoing maintenance or repair. Without it, your network may suffer significant downtime, leading to lost revenue and productivity. |
Bypass
Interlocking Interlocking between the maintenance bypass and UPS isolators is required to ensure that the load is transferred between the two power sources in a controlled manner. This is necessary to ensure that the load is uninterrupted during the transfer, and the UPS is not damaged by back-feeding from maintenance bypass supply into the UPS output terminals while the inverter is on load. The power isolators within the UPS are
invariably electrically interlocked to prevent such problems occurring.
However, when an external maintenance bypass circuit is employed, additional
electrical or mechanical interlocking devices are usually required. |
Static bypass Types (fig.12) 1- Single-phase static switch It’s composed by two pairs of thyristors, connected
in anti-parallel, that interrupt the phase conductors (inverter/bypass) The bypass component is protected by a fast-acting
fuse In order not to modify the grounding system the
neutral conductor is not interrupted 2- Three-phase static switch It’s composed by six pairs of thyristors, connected
in anti-parallel, that interrupt the phase conductors (inverter/bypass) Fig.12 Static bypass Types
There are 3 Static switch typologies, The three
types use different firing cards, that vary on the basis of the components
layout. TYPE 1 It’s the single-phase static switch. TYPE 2 It’s the three-phase static switch that uses compact
type thyristors. (SemiPack) TYPE 3 It’s the three-phase static switch that uses
disc-type thyristors (used only on the 500kVA and 650kVA). |
Earthing Principles of UPS Systems |
First: For
Transformer-based/Transformer-less UPS with bypass In this system Fig.13, the UPS Neutral Should not be bonded to the grounding conductor. This earthing configuration is similar for both transformer based / transformer-less UPS and This earthing configuration has the following functions:
Fig.13 Earthing System-UPS with
bypass |
Second: For Transformer-based UPS
without bypass In this system Fig.14, the UPS neutral should be bonded to the grounding conductor. This earthing configuration has the following functions:
Fig.14 Transformer Based UPS without
Bypass |
Third: For Transformer-less UPS
without bypass In this system Fig.15, the UPS neutral should not be bonded to the grounding conductor. This earthing configuration is similar for both transformer based / transformer-less UPS with bypass and This earthing configuration has the following functions:
Fig.15 Transformer-less UPS without
bypass |
Forth: For UPS with Isolated bypass In this system Fig.16, a transformer is introduced in the bypass path of the UPS. The output neutral of the UPS should be bonded to the grounding conductor. The UPS acts as a seperatively drived source. This earthing configuration has the following functions:
Fig.16 UPS with Isolated bypass |
Points to be taken care while
earthing UPS
Selecting the Earthing Conductor
Size Please
see below the Earthing conductor size requirement. This is based on the
standard IEC 60364-5-54
|
In the next Article, we will explain
the evaluation criteria for UPS selection.
So, please keep following.
Subject Of Pervious
Article |
Article |
Applicable Standards for UPS Systems What is a UPS? Why do we need a UPS? UPS Rating Classification of UPS: 1-Voltage range, 2-No. of phases, 3- Mobility, 4- Technological design, |
Classification and Types of
UPS – Part One |
5- Physical Size/capacity, 6- Form factor/ configurations: 6.1- “N” System
Configuration |
Classification and Types of UPS – Part Two |
6.2- “N+1” System
Configuration, which includes:
6.3- Parallel Redundant with Dual Bus Configuration (N+1 or 1+1) |
Classification and Types of
UPS – Part Three |
6.4- Parallel Redundant with STS Configuration
6.5- System plus System 2(N+1), 2N+2, [(N+1) + (N+1)], and 2N |
Classification and Types of UPS – Part Four |
7- According to UPS Topology 7.1 Off-line or Standby UPS, 7.2 Line Interactive UPS, 7.3 Standby-Ferro UPS, 7.4 Online Double Conversion UPS, 7.5 The Delta Conversion On-Line UPS. |
Classification and Types of
UPS – Part Five |
8- According to UPS Distribution
Architecture 8.1 Centralized UPS Configuration, 8.2 Distributed (Decentralized) UPS Configuration, 8.2.1 Distributed UPS-Zonewise Configuration 8.3 Hybrid UPS Configuration. Conventional (Monolithic) Vs Modular
UPS System:
|
Classification and Types of UPS – Part Six |
Three Basic Configurations Of Mains And Bypass For A UPS System:
9-According to Use of transformers with the UPS
|
Classification and Types of
UPS – Part Seven |
Transformer Arrangements in Practical UPS Systems: 1-Transformer options for the “single mains” configuration 2-Transformer Options for the “Dual Mains” Configuration |
Classification and Types of UPS – Part Eight |
3-
Transformer options for “single mains without bypass” |
|
Components of Online Double Conversion UPS: 1- Rectifier, 2- Inverter, 3- Energy Storage system: 3.1 Battery |
Components of Online Double Conversion UPS–
Part One
|
No comments:
Post a Comment