A double conversion UPS converts the incoming alternating current (AC) to a direct current (DC), so it can power the system’s battery, and then inverts the DC back to AC for powering equipment – hence the name “double conversion.”
We need to know how a UPS’s components work together so we
can better understand the UPS system and ensure that the critical load remains
online.
As shown in the Fig.1, an online double Conversion UPS has (4)
major components:
- Rectifier,
- Inverter,
- Energy Storage (Battery),
- Static Switch.
Fig.1 Components
of Online Double Conversion UPS
|
1- Rectifier |
|
The
rectifier acts as a load to the electrical mains. The primary objective of
the rectifier is to: A- Convert the incoming power supply (AC) to DC This
DC voltage is used to support what is commonly called a DC Bus, which is the
connection between the rectifier, the stored energy device, and the inverter. B-
Charge the battery All
UPS systems need a battery charger—a type of rectifier—to keep batteries
charged and recharge them after a power outage. Some rectifier systems use
what is called a walk-in circuit. This circuit ‘walks’ up its output, or the
DC Bus, slowly. Walking the DC Bus up gradually accomplishes several useful
things, including protecting the DC filter caps and reducing inrush current
to the system. Some
models of UPS systems will use a separate battery charger that can be turned
off when the batteries are fully charged. It will then monitor the batteries
and when they need to be charged it w ill turn back on. For a
double-conversion system with separate battery chargers, there needs to be a
rectifier to support the DC Bus during normal operation. C- It
also has a hidden objective which is to draw a sinusoidal current from the
mains and also to ensure the current drawn is in phase with the voltage
waveform so that the current harmonic distortion injected on the mains is
less and the power factor is better. Therefore,
Other names used for rectifiers are battery charger and AC to DC converter. The
rectifier in a three phase UPS is designed to operate under:
Taking
into consideration voltage fluctuations, the rectifier is typically designed
to operate with:
In general, the best rectifier topology should have:
This
will ensure good compatibility with Generators and also reduce the need to
oversize the DG set, incoming transformer and cable sizing for supporting the
UPS. The
technology of the UPS has evolved and different technologies are being used
in the rectifier of the UPS. A short comparison of different rectifier
technologies is given in Fig-2. Fig-2 Comparison of Different Rectifier
Technologies |
|
2- Inverter |
|
The
primary objective of the inverter is to convert DC power to AC power and to
support the loads. The DC
power can be either from the rectifier or from the battery connected to the
DC bus of the UPS System. The
inverter is a critical component as this acts as a source to the critical
loads connected to it. As a source, the inverter has to support the loads
with sinusoidal voltage waveform under below conditions:
There
are two main Inverter topologies namely with:
We already explained these topologies in article “Classification and Types of UPS – Part Seven” Inverter typologies As already seen for the rectifiers, also the
inverters can be separated in different typologies, according to the
constructive solution chosen (TYPE 1, TYPE 2 & TYPE 3) TYPE 1 It’s the single-phase inverter, with the following
manufacturing features:
TYPE 2 It’s the three-phase inverter, with the following manufacturing features:
TYPE 3
|
|
3- Energy Storage |
|
When
electrical service is disrupted (i.e., mains failure), the UPS continues to
support the load connected to it through its energy storage system. A stored
energy source provides DC power to the inverter when the normal AC power is
not available. This normal AC source could be utility or generator power. The
UPS may provide power for durations ranging from 10 to 20 seconds to several
hours. Shorter duration UPSs are designed to carry the load during the
start-up of back-up electrical generators, typically diesel engine driven
generators, and to enable a smooth transition to the generator as the power
source. In
many cases, the UPS is designed to provide power for 5 to 30 minutes. The
purpose is to enable an orderly shutdown of operations thereby avoiding an
abrupt shutdown, which would otherwise cause equipment damage, product/work
losses or a security/safety hazard. The under-desk UPS for PCs is an example.
UPS
with enough energy to provide power for several hours are somewhat rare. A
key reason is that, in most situations, it is less expensive to store energy
in the form of diesel fuel (for generators) if backup power is needed for
several hours. There are different technologies of energy storage solution available in the market like:
The selection of right energy storage system depends on:
|
|
3.1 Energy Storage system - battery |
|
Battery
is the most critical component in the UPS and is also considered as heart of
the UPS System. Without, battery the UPS is just a power conditioner. The
purpose of the battery is to provide the energy necessary to supply the load
when the mains supply in not available. Cost
of battery is a major component on the final price of the UPS solution
proposed to the customer. A
battery is an electrochemical device that stores energy at one time for use
at another. The battery uses electrical energy to store energy in chemical
form which is converted to electrical energy during the discharge of the
battery (see Fig.3) Fig.3 battery is an electrochemical device The
UPS battery may furnish power to the inverter for a few seconds, many
minutes, or hours. The battery capacity is determined by the amount and
duration of power the inverter has to deliver to the load from the battery. |
|
Types of Battery Three common
varieties of battery chemistries popularly used in UPS applications (Fig.4)
are:
Fig.4 Types of Battery |
|
3.1.1 Lead Acid Battery It is
very commonly used as the storage battery or secondary battery where
electrical energy can be stored as chemical energy and this chemical energy
is then converted to electrical energy as and when required.
Whereas
conversion of chemical energy into electrical energy for supplying the
external load is known as discharging of secondary battery. During
charging of battery, current is passed through it which causes some chemical
changes inside the battery. This chemical changes absorb energy during their
formation. When
the battery is connected to the load, the chemical changes take place in
reverse direction, during which the absorbed energy is released as electrical
energy and supplied to the load. The
principle working of lead acid battery The main active materials required to construct a lead acid battery are:
The
positive plate is made of lead peroxide. This is dark brown, hard and brittle
substance. The
negative plate is made of pure lead in soft sponge conditions. Dilute
sulfuric acid used for lead acid battery has ratio of water to acid = 3:1. During
discharging:
During
charging:
|
||||||
|
The
lead acid battery is further classified as:
|
|
3.1.1.A SMF (Sealed Maintenance Free) battery It is a battery that doesn't require topping up due to negligible water loss. It is designed in such a way that it cannot be opened or refilled. These batteries are safe, maintenance free and are suitable for most UPS applications. The SMF battery will have an additional safety valve which release the excessive formation of hydrogen, as a result of overcharging, in to the atmosphere. SMF
battery works on a recombination technology where the hydrogen gas evolved
during the charging process, is converted to water with the help of oxygen
present inside the battery container. The typical cyclic performance of the battery is less and is limited by the operating temperature and the charging profile. The
SMF battery delivers higher power at higher temperatures but the life of
battery comes down significantly The SMF battery needs to be installed in a
controlled environment to maintain the temperature at 25-27 deg C and an
additional hydrogen sensor in the battery room is recommended for
installation. |
|
3.1.1.B Tubular/Flooded Battery Tubular Batteries have openings at top to add distilled water for maintenance and safe running. These batteries are very rugged and used in Cyclic application. These batteries last longer due to robust design and are suitable for harsh environment applications. The tubular battery can be installed in any environment (other than closed air conditioner room) with proper ventilation and air exchanges as hydrogen evolution from the battery is higher when compared with SMF buttery. |
|
3.1.1.C Tubular Gel VRLA Tubular
Gel batteries require no topping of water and is a sealed, valve regulated
lead-acid deep cycle battery that uses a gel electrolyte. These type of batteries are rugged and suitable for cyclic applications but are maintenance free compared to flooded tubular batteries. |
|
3.1.2 Nickel cadmium cell (Ni-Cd) The active components of a rechargeable Ni-Cd battery in the charged state consist of:
Due to their low internal resistance and the very good current conducting properties, Ni-Cd cells can supply extremely high currents and can be recharged rapidly. These
cells can operate over a large temperature range, from +60°C down to -20°C. The selection of the separator (nylon or polypropylene) and the electrolyte (KOH, LiOH, NaOH) is also of great importance. These elements influence the voltage conditions in the case of a high current discharge, the service life and the overcharging capability of the cell. In the case of misuse, a very high-pressure may arise quickly. For this reason, these cells are equipped with a reversible safety valve, which can act several times. NiCad
cells offer a long service life (depending on the type of application and
charging unit up to 2000 cycles).
|
||||||
|
3.1.3 Lithium Ion battery Lithium-ion batteries offer several advantages over traditional valve-regulated, lead acid batteries as follows:
Therefore,
lithium-ion batteries become an appealing energy storage technology option
for energy storage. Similar to the lead- and nickel-based architecture, lithium-ion uses a cathode (positive electrode), an anode (negative electrode) and electrolyte as conductor, it consist of:
During
discharge:
During
Charging:
When the cell charges and discharges, ions shuttle between cathode (positive electrode) and anode (negative electrode). On discharge, the anode undergoes oxidation, or loss of electrons, and the cathode sees a reduction, or a gain of electrons. Charge reverses the movement. All
materials in a battery possess a theoretical specific energy, and the key to
high capacity and superior power delivery lies primarily in the cathode. For
the last 10 years or so, the cathode has characterized the Li-ion battery. Common cathode material include:
Different
Technologies of Lithium Ion Battery (see Fig.6) Fig-6 Different Technologies of Lithium Ion
Battery |
||||||
|
Batteries can be classified either
as:
The deep cycle means that the
battery is fully discharged and then recharged. From the outside, both
batteries look alike; however, there are fundamental differences in design as
per the following comparison table:
|
In the next Article, we will continue
explaining other Components of Online Double Conversion UPS. So, please keep following.
|
Subject Of Pervious
Article |
Article |
|
Applicable Standards for UPS Systems What is a UPS? Why do we need a UPS? UPS Rating Classification of UPS: 1-Voltage range, 2-No. of phases, 3- Mobility, 4- Technological design, |
Classification and Types of
UPS – Part One |
|
5- Physical Size/capacity, 6- Form factor/ configurations: 6.1- “N” System Configuration |
Classification and Types of UPS – Part Two |
|
6.2- “N+1” System
Configuration, which includes:
6.3- Parallel Redundant
with Dual Bus Configuration (N+1 or 1+1) |
Classification and Types of
UPS – Part Three |
|
6.4- Parallel Redundant with STS Configuration
6.5- System plus System
2(N+1), 2N+2, [(N+1) + (N+1)], and 2N |
Classification and Types of UPS – Part Four |
|
7- According to UPS Topology 7.1 Off-line or Standby UPS, 7.2 Line Interactive UPS, 7.3 Standby-Ferro UPS, 7.4 Online Double Conversion UPS, 7.5 The Delta Conversion On-Line UPS. |
Classification and Types of
UPS – Part Five |
|
8- According to UPS Distribution
Architecture 8.1 Centralized UPS Configuration, 8.2 Distributed (Decentralized) UPS Configuration, 8.2.1 Distributed UPS-Zonewise Configuration 8.3 Hybrid UPS Configuration. Conventional (Monolithic) Vs Modular
UPS System:
|
Classification and Types of UPS – Part Six |
|
Three Basic Configurations Of Mains And Bypass For A UPS System:
9-According to Use of transformers with the UPS
|
Classification and Types of
UPS – Part Seven |
|
Transformer Arrangements in Practical UPS Systems: 1-Transformer options for the “single mains” configuration 2-Transformer Options for the “Dual Mains” Configuration |
Classification and Types of UPS – Part Eight |
|
3-
Transformer options for “single mains without bypass” |
Classification and Types of
UPS – Part Nine |







No comments:
Post a Comment