In Article " Design Calculations of Lightning Protection Systems – Part Two ", I indicated the lightning protection design process involves a number of design steps as in below Fig.1.
Fig.1: The Lightning Protection Design Process |
Step#1: Characteristics of the Structure to Be Protected
Explained in Article " Design Calculations of Lightning Protection Systems – Part Two "
|
Step#2: Risk Assessment Study
|
Also, In above Article, I indicated that the risk assessment study can be done by (4) different methods as follows:
Methods Of Calculations For Risk Assessment Study
|
Articles
|
First: Manual Method (Equations And Tables Method) as per IEC 62305-2
| |
First: Manual Method (Equations And Tables Method) as per NFPA 780
| |
Third: Excel Sheets Method For Performing The Risk Assessment Study
| |
Fourth: Online Calculators Method Used for Need for Lightning Protection calculations
|
Step#3: Selection Of External LPS Type and Material
Explained in Article " Design Calculations of Lightning Protection Systems – Part Fifteen "
|
Step#4: Sizing of Air Termination System Components
|
In Article " Design Calculations of Lightning Protection Systems – Part Sixteen ", I explained the following points:
- Types and forms of Strike Termination Subsystem,
- Sizing of Air Terminals Based on IEC 62305-3 and Based on BS EN 62305-3,
- Sizing of Natural Air Terminals,
- Positioning / Placement of Air Termination System Components.
- The Class of LPS/LPL influences on the (3) Positioning Methods.
Method for Positioning of
Air Terminals
|
Article
|
The Rolling
Sphere Method (RSM)
|
|
The Protective
Angle Method (PAM)
The Mesh Method
|
Today, I will explain Recommendations for the Best Positioning of Air Terminals.
For more information, please review the following Articles:
Step#4: Sizing and Positioning of Air Termination System
Components - Continued
|
4- Recommendations for the Best Positioning of Air Terminals
|
4.2 Recommendation for Masts and Antennas
1- Masts and Flag Poles
do not contain electrical circuits:
2- Antennas and Masts
with electrical equipment (see Fig.3):
Note:
The preferred
location for the SPD is as close as possible to the entry point of the cable
into the structure, and where possible the cable should enter into the
building near to, and be connected to an equipotential bonding bar.
3- Antennas Cables:
|
4.3 Recommendation for Protection of other items
protruding above the roof
The design of the
lightning protection system should be such that air-terminations are
positioned to provide protection against lightning flashes to the roof and
all items located upon it (vents, skylights, air-handling units, pipes, etc).
However, in some cases, protection is not required for smaller or
non-conductive items. Table#1 summarizes the requirements for
determining if air termination protection is required.
Table#1: Roof fixtures not requiring protection
Note that the bonding
requirement for these items requires separate consideration; refer to Part#4 in this Article.
Conductive
connections into the structure may be one of the following:
Items that have
conductive connections into the structure interior require air-termination
protection. Otherwise, considerable currents can be conducted into the structure
interior.
Methods to protect
Conductive connections above the roof:
1- Using a LPZ 1 or
higher:
IEC 62305-1 Section 8.3.2 requires internal
systems to be located inside a LPZ 1 or higher. LPZ 1 are zones protected
against direct flashes and only exposed to limited lightning or induced
currents. To meet this requirement:
2- Replacing
conductive connections with insulated (non conductive) connections
Special applications
A- Vents (see Fig.5):
B- Chimneys:
While most chimneys are tall enough to require
protection, in the case of non-conductive chimneys, or similar vents,
protection is still recommended, as soot deposits can effectively make these
items conductive.
C- Electronic Or
Electrical Equipment:
All items on the roof
that contain electronic or electrical equipment require protection via
air-terminations (see Fig.7). Additionally for electrical and
electronic items, protection is also required if wall mounted in a location
where a lightning flash may occur (i.e. in a location touched by rolling
sphere method). Surge protective devices must be installed on the circuits to
limit current entering into the internal environment.
|
4.4 Recommendation for Bonding of Roof Top Fixtures
Lightning Equipotential
Bonding Of Roof Top Fixtures
Separation distance
requirements between the air-terminations and all conductive roof fixtures
(including conductive flush mount fixtures) should be evaluated to determine
if bonding of the item. You can review the Separation distance requirements in Article " Conventional Lightning Protection System Components – Part Seven ".
Equipotential bonding of roof top fixtures ,generally, governed by
(3) scenarios as follows :
Scenario#1: If the roof
mounted equipment is not protected by the air termination system but can
withstand a direct lightning strike without being punctured.
In this case, Equipotential
bonding of roof top fixtures requirements will be as follows:
Scenario#2: If the roof
mounted equipment cannot withstand a direct lightning strike and there is
sufficient space on the roof for achieving a separation distance.
In this case, Equipotential
bonding of roof top fixtures requirements will be as follows:
Scenario#3: If the roof
mounted equipment cannot withstand a direct lightning strike and there isn’t
sufficient space on the roof for achieving a separation distance.
In this case, Equipotential
bonding of roof top fixtures requirements will be as follows:
These (3) scenarios are
summarized in the below flow chart:
However, to eliminate
the need to bond, it may be possible to select air-termination location and
height so the fixture is protected by the air-termination, but positioned far
enough distance away so that bonding is not required (see Fig.8B).
|
In the next Article, I will explain Step#5: the Design of Down-Conductor System. Please, keep following.
No comments:
Post a Comment