In Article " Design Process for Lightning Protection Systems ", I indicated the (3) phases of the Design Process for Lightning Protection Systems as follows:
Design Process For Lightning Protection Systems
The design process of lightning protection systems is commonly broken into discrete phases, allowing the lightning protection designer to present an integrated design package. These phases can be listed as follows:
A Quality assurance is required in each phase in above.
|
Introduction To Design Calculations Of Lightning Protection Systems
It is very important before explaining the design calculations of lightning protection systems to highlight some important topics or expressions that will be used in these calculations. These topics can be listed as follows:
|
Design Calculations of Lightning Protection Systems – Continued
Third: Detailed Design Phase
|
The lightning protection design process involves a number of design steps as in Fig.1.
Fig.1: The Lightning Protection Design Process |
Step#1: Characteristics of the Structure to Be Protected
|
Step#2: Risk Assessment Study
|
Methods Of Calculations
For Risk Assessment Study
The risk assessment study can be done by (4) different
methods as follows:
1- Manual Method (equations and tables method),which will be
explained as per:
2-Software Method,
3- Excel Sheets Method,
4-Online Calculators Method.
|
First: Manual Method (Equations
And Tables Method) as per IEC 62305-2
|
Procedure For Performing The Risk Assessment Study By Manual Method
Procedure for performing the risk assessment
study includes three parts as follows:
|
And In Article " Design Calculations of Lightning Protection Systems – Part Three ", I explained the following:
- Step#2-1: Identify the structure to be protected,
- Step#2-2: Identify the types of loss relevant to the structure to be protected Rn,
- Step#2-3: For each loss to be considered, identify the tolerable level of risk RT,
- Step#2-4 First Part: Identification of the Risk Components Rx.
Also, in Article " Design Calculations of Lightning Protection Systems – Part Four ", I explained Step#2-4 Second Part: Calculations of the Risk Components Rx - Calculation of the first Parameter Nx = Number of dangerous events per year and I indicated that:
Each of the risk
components Rx is obtained using further calculations, sub-calculations and
reference tables based on the general equation:
RX = NX x PX x LX
Where
NX = number of dangerous
events per year,
PX = probability of
damage to structure,
LX = amount of consequent loss.
X = A, B, ...
So, The task
of the risk assessment therefore involves the determination of the three
parameters NX, PX and LX.
|
Today, I will explain how to calculate the second Parameter: PX = probability of damage to structure.
Step#2-4 Second Part: Calculations of the Risk Components Rx
|
Calculations of second
Parameter: PX = probability of damage to
structure
|
Probability of damage
to structure PX
The damage probability
parameter gives the probability that a supposed lightning strike will cause a
quite specific type of damage. It is therefore assumed that there is a
lightning strike on the relevant area; the value of the damage probability
can then have a maximum value of (1). We differentiate between the following
eight damage probabilities in Table-1:
Table-1: The Eight Damage Probabilities
|
1- Probability PA that a flash to a structure
will cause injury to living beings by electric shock
The values of probability PA of shock to living beings due to
touch and step voltage by a lightning flash to the structure, depend on the
adopted LPS and on additional protection measures provided:
PA = PTA x PB
Where:
Table-2: Values of probability PTA that a flash to a structure
will cause shock to living beings due to dangerous touch and step voltages
Notes:
|
2- Probability PB that a flash to a structure
will cause physical damage
The values of probability PB of physical damage by a flash to
a structure, as a function of lightning protection level (LPL) are given in Table-3.
Table-3: Values of probability PB depending on the protection
measures to reduce physical damage
Notes:
|
3- Probability PC that a flash to a structure
will cause failure of internal systems
The probability PC that a flash to a structure will
cause a failure of internal systems is given by:
PC = PSPD x CLD
Where:
Table-4: Value of the probability PSPD as a function of LPL for
which SPDs are designed
Notes:
Table-5: Values of factors CLD and CLI depending on shielding,
grounding and isolation conditions
Notes:
|
4- Probability PM that a flash near a
structure will cause failure of internal systems
PM = PSPD x PMS
Notes:
The values of PMS are obtained from the product:
PMS = (KS1 x KS2 x KS3 x KS4)2
Where:
Note:
Inside an LPZ, at a safety
distance from the boundary screen at least equal to the mesh width wm, factors KS1 and KS2 for LPS or spatial grid-like
shields may be evaluated as:
KS1 = 0,12 x wm1
KS2 = 0,12 x wm2
Where:
wm1 (m) and wm2 (m) are the mesh widths of
grid-like spatial shields, or of mesh type LPS down-conductors or the spacing
between the structure metal columns, or the spacing between a reinforced
concrete framework acting as a natural LPS.
Notes:
Table-6: Value of factor KS3 depending on internal
wiring
The factor KS4 is evaluated as:
KS4 = 1/UW
Where:
Uw is the rated impulse withstand
voltage of system to be protected, in kV.
Notes:
|
5- Probability PU that a flash to a line will
cause injury to living beings by electric shock
The values of probability PU of injury to living beings
inside the structure due to touch voltage by a flash to a line entering the
structure depends on the characteristics of the line shield, the impulse
withstand voltage of internal systems connected to the line, the protection
measures like physical restrictions or warning notices and the isolating
interfaces or SPD(s) provided for equipotential bonding at the entrance of
the line according to IEC 62305-3.
Note:
A coordinated SPD system
according to IEC 62305-4 is not necessary to reduce PU; in this case SPD(s) according
to IEC 62305-3 are sufficient.
The value of PU is given by:
PU = PTU x PEB x PLD x CLD
Where:
Note:
When SPD(s) according to IEC
62305-3 are provided for equipotential bonding at the entrance of the line,
earthing and bonding according to IEC 62305-4 may improve protection.
Table-7: Values of probability PTU that a flash to an entering
line will cause shock to living beings due to dangerous touch voltages
Note:
If more than one provision has
been taken, the value of PTU is the product of the corresponding values.
Table-8: Value of the probability PEB as a function of LPL for
which SPDs are designed
Note:
The values of PEB may be reduced for SPDs having
better protection characteristics (higher nominal current IN, lower protective level UP, etc.) compared with the
requirements defined for LPL I at the relevant installation locations.
Table-9: Values of the probability PLD depending on the resistance
RS of the cable screen and the
impulse withstand voltage UW of the equipment
Note:
In suburban/urban areas, an LV
power line uses typically unshielded buried cable whereas a telecommunication
line uses a buried shielded cable (with a minimum of 20 conductors, a shield
resistance of 5 Ω/km, a copper wire diameter of 0,6 mm). In rural areas an LV
power line uses an unshielded aerial cable whereas a telecommunication line
uses an aerial unshielded cable (copper wire diameter: 1 mm). An HV buried
power line uses typically a shielded cable with a shield resistance in the
order of 1Ω/km to 5 Ω/km. National committees may improve this information in
order to better meet national conditions of power and telecommunication
lines.
|
6- Probability PV that a flash to a line will
cause physical damage
The values of probability PV of physical damage by a flash to
a line entering the structure depend on the characteristics of the line
shield, the impulse withstand voltage of internal systems connected to the
line and the isolating interfaces or the SPDs provided for equipotential bonding
at the entrance of the line according to IEC 62305-3.
Note:
A coordinated SPD system
according to IEC 62305-4 is not necessary to reduce PV; in this case, SPDs according to
IEC 62305-3 are sufficient.
The value of PV is given by:
PV = PEB x PLD x CLD
Where:
|
7- Probability PW that a flash to a line will
cause failure of internal systems
The values of probability PW that a flash to a line entering
the structure will cause a failure of internal systems depend on the
characteristics of line shielding, the impulse withstand voltage of internal
systems connected to the line and the isolating interfaces or the coordinated
SPD system installed.
The value of PW is given by:
PW = PSPD x PLD x CLD
Where:
|
8- Probability PZ that a lightning flash near
an incoming line will cause failure of internal systems
The values of probability PZ that a lightning flash near a
line entering the structure will cause a failure of internal systems depend
on the characteristics of the line shield, the impulse withstand voltage of
the system connected to the line and the isolating interfaces or the
coordinated SPD system provided.
The value of PZ is given by:
PZ = PSPD x PLI x CLI
Where:
Table-10: Values of the probability PLI depending on the line type
and the impulse withstand voltage UW of the equipment
|
The Probability P of damage in a structure with zones
ZS
For the evaluation of risk
components and the selection of the relevant parameters involved, the
following rules apply for the probability P of damage:
PC = 1 – (1 – PC1) x (1 – PC2) x (1 – PC3)
PM = 1 – (1 – PM1) x (1 – PM2) x (1 – PM3)
Where:
PCi, and PMi are parameters relevant to
internal system i =1, 2, 3,…
With the exception made for PC and PM, if more than one value of any
other parameter exists in a zone, the value of the parameter leading to the
highest value of risk is to be assumed.
|
No comments:
Post a Comment