In Article " Conductor Ampacity Calculation – Part Six ", I indicated Some special cases for the application of adjustment factor of table 310.15(B)(3)(a) where is More Than Three Current-Carrying Conductors in a Raceway or Cable, which were:
- Bare or Covered Conductors,
- Neutral Conductor,
- Grounding or Bonding Conductor,
- Main feeders to Dwelling units,
- Conductors contained in sheet metal auxiliary gutter,
- Conductors contained in Nonmetallic Auxiliary Gutters,
- Conductors in Metal Wireways,
- Conductors for Remote Remote-Control, Signaling, And Power-limited Circuits,
- Conductors for Fire Alarm Systems,
- Conductors and Cables in Cable Trays.
Today, I will explain Last Special Case for Conductor Ampacity Calculations: Conductors and Cables in Cable Trays as follows.
For more information and good following, please review the following articles:
Conductors and Cables Ampacity Calculations in Cable Trays
Rule#1: Ampacity of
Multiconductor Cables, Rated 2000 Volts or Less, installed in Cable Trays
As per
392.80(A)(1), the Ampacity of Multiconductor Cables, Rated 2000 Volts or
Less, installed in Cable Trays using the allowable fill areas
as per Section 392.22(A), shall be as given in Table 310.15(B)(16) and Table 310.15(B)(18)
subject to the three below provisions.
|
Provision#1
If
there are more than 3 current carrying conductors in a multiconductor cable,
derate cable ampacity per section 310.15(B)(3)(A).
|
Note to Provision#1
Adjustment factors shall be
limited to the number of current-carrying conductors in the cable and not to
the number of conductors in the cable tray.
|
Provision#2
Where cable trays are continuously covered for more than 1.8 m
(6 ft) with solid unventilated covers, use 95% of the ampacity
values shown in Table 310.15(B)(16) and Table 310.15(B)(18) for multiconductor
cables.
|
Note to Provision#2
Where cable tray
covers are to be used, it is best to use raised or ventilated covers so that
the cables can operate in a lower ambient temperature.
|
Provision#3
If multiconductor cables
are placed in a single layer in uncovered trays, with a maintained spacing of
not less than (1) cable diameter between cables, the ampacity of the cables
shall not exceed the allowable ambient temperature-corrected ampacities of
multiconductor cables with not more than (3) insulated conductors in free air
in accordance with Section 310.15(C) and Table B.310.15(B)(2)(3). (see
below image)
|
Note to Provision#3
By spacing the
cables one diameter apart, the engineer may increase the allowable ampacities
of the cables to the free air rating as per Section 310.15(C) and Table B.310.15(B)(2)(3)in Appendix B.
Notice that the allowable fill of the cable tray has been decreased in this
design due to the cable spacing.
|
Notes to Rule#1
|
Rule#2: Selection
Of Ampicity For Multi-Ampacity Conductors
As per 310.15(A)(2), Where more than one ampacity applies for a
given circuit length, the lowest value shall be used. (see below image)
|
Exception Rule#2
A higher ampacity is
permitted, if the length of the reduced ampacity doesn’t exceed 10 ft and is not
longer than 10% of the total length of the circuit.
|
Example#1:
Five nos., 4 conductor multi cables, 1/0 AWG, THHN are stacked together in a solid-bottom cable tray with two nos., 4 conductor multi cables, 350 Kcmil, THHN installed as a single layer. What are the ampacity of these multiconductor cables noting that all conductors in cables are current carrying conductors?
Solution:
Step#1: From table 310.15(B)(16), find the allowable ampacity for these multiconductor cables
Allowable ampacity For 350 Kcmil THHN = 350 A Allowable ampacity For 1/0 AWG THHN = 170 A
Step#2: Applying Adjustment Factors from table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors in a Raceway or Cable
Since, Adjustment factors shall be limited to the number of current-carrying conductors in the cable and not to the number of conductors in the cable tray.
Nos. of current carrying conductors in cable = 4
So, the Adjustment Factors from table 310.15(B)(3)(a) = 80%
Derated allowable ampacity For 350 Kcmil THHN = 350 A x 80% = 280 A
Derated allowable ampacity For 1/0 AWG THHN = 170 A x 80% = 135 A
Example#2:
Same cables as in example#1, but the cable tray has a solid cover, What are the ampacity of these multiconductor cables noting that all conductors in cables are current carrying conductors?
Solution:
Step#1: From table 310.15(B)(16), find the allowable ampacity for these multiconductor cables
Allowable ampacity For 350 Kcmil THHN = 350 A Allowable ampacity For 1/0 AWG THHN = 170 A
Step#2: Applying Adjustment Factors from table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors in a Raceway or Cable
Since, Adjustment factors shall be limited to the number of current-carrying conductors in the cable and not to the number of conductors in the cable tray.
Nos. of current carrying conductors in cable = 4
So, the Adjustment Factors from table 310.15(B)(3)(a) = 80%
Derated allowable ampacity For 350 Kcmil THHN = 350 A x 80% = 280 A
Derated allowable ampacity For 1/0 AWG THHN = 170 A x 80% = 135 A
Step#3: Applying 392.80(A)(2), Derate ampacity by 95%
Derated allowable ampacity For 350 Kcmil THHN = 280 A x 95% = 266 A
Derated allowable ampacity For 1/0 AWG THHN = 135 A x 95% = 128.25 A = 129 A
Rule#3: Ampacity of Single-Conductor
Cables Cables, Rated 2000 Volts or Less, installed in Cable Trays
As per
392.80(A)(2), for Single-Conductor Cables or single conductors cabled
together (triplexed, quadruplexed, etc.), Rated 2000 Volts or Less, installed
in Cable Trays according to the requirements of 392.22(B), The adjustment
factors of 310.15(B)(3)(a) shall not apply , and the ampacity shall comply
with the below Table.
|
Ampacity of Cables Rated 2000 Volts or Less in Cable Tray
(single conductor cables)
|
||||
cable size
|
solid unventilated cable tray cover (for more than 1.8 m (6 ft)
)
|
applicable ampacity tables
|
multiply Ampacity Table values by
|
special conditions
|
600 K cmil and larger
|
no cover allowed (**)
|
310.15(b)(17) and 310.15(B)(19)
|
0.75
|
|
600 K cmil and larger
|
yes
|
310.15(b)(17) and 310.15(B)(19)
|
0.7
|
|
1/0 AWG through 500 Kcmil
|
no cover allowed (**)
|
310.15(b)(17) and 310.15(B)(19)
|
0.65
|
|
1/0 AWG through 500 Kcmil
|
yes
|
310.15(b)(17) and 310.15(B)(19)
|
0.6
|
|
1/0 AWG & Larger in single layer
|
no cover allowed (**)
|
310.15(b)(17) and 310.15(B)(19)
|
1
|
maintained spacing of one cable diameter
|
Single conductors in triangle configuration 1/0 AWG and Larger (see
below image)
|
no cover allowed (**)
|
310.15(B)(20) (see NEC section 310.15(B))
|
1
|
Spacing of 2.15 x one conductor O.D. between cables (***)
|
(*) The ambient ampacity
correction factors must be used.
|
||||
(**) At a specific
position, where it is determined that the tray cables require mechanical
protection, a single cable tray cover of six feet or less in length can be installed.
|
||||
(***) O.D. of the largest conductor contained within the
configuration and adjacent conductor
configurations or cables, the spacing of 2.15 times one conductor diameter is to be maintained between circuits. Two interpretations of this statement are possible as follows:
The use of the
word “circuit” is unfortunate as its presence promotes Interpretation #1. An
installation based on Interpretation #1 is not desirable as a free air space
equal to 2.15 times one conductor diameter between the cable bundles should be
maintained to promote cable heat dissipation.
|
||||
Example#3:
Four single Copper conductors 700 Kcmil THHN installed in uncovered cable tray as a single layer, what is the allowable ampacity for these conductors?
Solution:
Step#1: From table 310.15(B)(17), find the allowable ampacity for these single conductors
Step#2: Applying 392.80(A)(2)(a), Derate ampacity by 75%
Derated allowable ampacity For 700 Kcmil THHN = 855 A x 75% = 641 A
Example#4:
Same as example#3, but the cable tray is covered, what is the allowable ampacity for these conductors?
Solution:
Step#1: From table 310.15(B)(17), find the allowable ampacity for these single conductors
Allowable ampacity For 700 Kcmil THHN = 855 A
Step#2: Applying 392.80(A)(2)(a), Derate ampacity by 70%
Derated allowable ampacity For 700 Kcmil THHN = 855 A x 75% = 598.5 A = 599 A
Rule#4: Ampacity for
Combinations of Multiconductor and Single-Conductor Cables in the same cable
tray
As per NEC
392.80(A)(3), Combination of multiconductor and single- conductor cable in
the same cable tray must not exceed the fill requirements for each type of
cable as if it were installed in its own tray and all installation
requirements and ampacity limits for each cable type apply, provided that the
following conditions apply:
The sum of the
multiconductor cable fill area as a percentage of the allowable fill area for
the tray calculated in accordance with 392.22(A), and the single-conductor
cable fill area as a percentage of the allowable fill area for the tray
calculated in accordance with 392.22(B), totals not more than 100 percent.
Multiconductor
cables are installed according to 392.22(A) and single-conductor cables are
installed according to 392.22(B) and 392.22(C) and (D).
|
In the next Article, I will explain the second method: Under engineering supervision, as provided in 310.15(C). Please, keep following.
Thanks for this thorough explanation and citing the reference code rule and tables that has to be read in conjunction. Well done and keep up the great work.
ReplyDelete