In Article " Conductor Ampacity Calculation – Part Four ", I explained the rule that controlling and refining the Conductor Ampacity selection from NEC Tables.
Also, in Article " Conductor Ampacity Calculation – Part Three ", I explained the following points:
- The need for ampacity calculation,
- When do we need ampacity calculation?,
- Methods for Conductors Ampacity Calculations as per NEC code,
- Methods for Ampacity Calculations of Conductors Rated 0–2000 Volts,
- First Method: Conductor Ampacity Calculations from Tables as provided in 310.15(B),
- General Overview of Allowable Ampacity Tables for conductors rated 0 to 2000 volts.
Today, I will continue explaining the correction Factors affecting conductor ampacity Tables as follows.
For more information and good following, please review the following articles:
First Method: Conductor Ampacity Calculations from Tables as provided in 310.15(B)
3- Correction Factors Affecting Conductor Ampacity Tables:
- Table 310.15(B)(16)
- Table 310.15(B)(17)
- Table 310.15(B)(18)
- Table 310.15(B)(19)
- Table 310.15(B)(20)
- Table 310.15(B)(21)
This selection process of the correct allowable ampacity table depends on knowing the following variables:
- Voltage,
- Cable configuration,
- Electrical duct configuration,
- Ambient Temperature.
After selecting the correct allowable ampacity table, the ampacity value of a certain application/ wiring method will be determined based on the following variables:
- Conductor material,
- Insulation type,
- Terminal temperature.
For example:
To select Table 310.15(B)(16), the variables must be as follows:
- Voltage: Rated Up to and Including 2000 Volts
- Cable configuration: Not More Than Three Current-Carrying Conductors in a Raceway or Cable.
- Electrical duct configuration: one Raceway, Cable, or Earth (Directly Buried)
- Ambient Temperature: 30°C (86°F)
And to determine the exact value for the ampacity, the following variables must be known:
1- Conductor material: Copper Or Aluminum Or Copper-Clad Aluminum
2- Insulation type:
- Types TW, UF
- Types RHW, THHW, THW, THWN, XHHW, USE, ZW
- Types TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW- 2, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW-2
3- Temperature Rating of Conductor: 60°C (140°F), 75°C (167°F), 90°C (194°F)
4- The Terminal temperature as discussed in Article " Conductor Ampacity Calculation – Part Four ".
But if we have an application/ wiring method with different variables than that specified in the allowable ampacity tables, for example:
- An application/ wiring method with Ambient Temperature: 37°C.
- An application/ wiring method with Cable configuration: More Than Three Current-Carrying Conductors in a Raceway or Cable.
- An application/ wiring method with Electrical duct configuration: More Than One Conduit, Tube, or Raceway
In this case, depending upon your application / wiring method, you might need to apply the following correction / adjustment factors:
- Ambient Temperature Correction Factors as in Table 310.15(B)(2)(A) and Table 310.15(B)(2)(b),
- More Than Three Current-Carrying Conductors in a Raceway or Cable as in Table 310.15(B)(3)(a),
- Ambient Temperature adjustment for Circular Raceways Exposed to Sunlight on Rooftops as in Table 310.15(B)(3)(c)
To download a PDF file that includes the Correction / Adjustment Factors Tables, click on the link.
Now, we will discuss these Correction / Adjustment Factors one by one as follows:
1- Ambient Temperature Correction Factors
Rule#1: Ambient Temperature
Correction Factors
Ampacities for
ambient temperatures other than those shown in the ampacity tables shall be
corrected in accordance with Table 310.15(B)(2)(a) or Table 310.15(B)(2)(b),
or shall be permitted to be calculated using the following equation:
Where:
I’ = ampacity
corrected for ambient temperature
I = ampacity shown
in the tables
Tc = temperature
rating of conductor (°C)
T’a = new ambient
temperature (°C)
Ta = ambient
temperature used in the table (°C)
|
2- Adjustment Factors
2.A More Than Three Current-Carrying Conductors in a Raceway or Cable
Rule#2: More Than Three
Current-Carrying Conductors in a Raceway or Cable
The allowable
ampacity of each conductor shall be reduced as shown in Table 310.15(B)(3)(a)
Where:
|
Important!!!
Each current-carrying
conductor of a paralleled set of conductors shall be
counted as a current-carrying conductor.
|
Important!!!
Where conductors of different
systems (power, lighting, control, etc.) are installed in a common
raceway or cable, the adjustment factors shown in Table 310.15(B)(3)(a)
shall apply only to the number of power and lighting
conductors Neglecting any control and
signal
conductors in the same raceway or cable.
|
Rule#3: Cases where Adjustment
factors shall not apply
Adjustment factors
shall not apply for the following cases:
Case#1: Conductors
in raceways having a length not exceeding 600 mm (24 in.),
Case#2: underground
conductors entering or leaving an outdoor trench if those conductors have
physical protection in the form of rigid metal conduit, intermediate metal
conduit, rigid polyvinyl chloride conduit (PVC), or reinforced thermosetting
resin conduit (RTRC) having a length not exceeding 3.05 m (10 ft), and if the
number of conductors does not exceed four.( see below image)
Case#3: Type AC
cable or to Type MC cable under the following conditions:
The cables do not
have an overall outer jacket.
Each cable has not
more than three current-carrying conductors.
The conductors are
12 AWG copper.
Not more than 20
current-carrying conductors are installed without maintaining spacing, are
stacked, or are supported on“bridle rings.”
|
Important!!!
on the contrary to case#3 in
Rule#3 above, An adjustment factor of 60 percent shall be applied to
Type
AC cable or Type MC cable under the following conditions:
|
Important!!!
Where conductors are
installed in cable trays, the provisions of 392.80 shall apply (This will be
explained later).
|
2.B More Than One Conduit, Tube, or Raceway
Spacing shall be maintained between individual conduits in groups of conduit runs from junction box to junction box because of the need to separate the conduits where they enter the junction box, to allow room for locknuts and bushings. (No adjustment factor will be applied)
2.C Ambient Temperature adjustment for Circular Raceways Exposed to Sunlight on Rooftops
Rule#4: Ambient Temperature
adjustment for Circular Raceways Exposed to Sunlight on Rooftops
the adjustments
shown in Table 310.15(B)(3)(c) shall be added to the outdoor temperature to
determine the applicable ambient temperature for application of the
correction factors in Table 310.15(B)(2)(a) or Table 310.15(B)(2)(b) Where
conductors or cables are installed in circular raceways exposed to direct
sunlight on or above rooftops.(see below image)
|
Important!!!
In Rule#4 above,
the closer the conduit is to the roof, the greater the ambient temperature
adjustment.
|
Example#1:
What is the Allowable ampacity for a wiring method where conduit with three 6 THWN-2 conductors with direct sunlight exposure that is ¾ inch above the roof?
Solution:
Step#1: As per TABLE 310.15(B)(3)(c) for Distance Above Roof to Bottom of Conduit = ¾ inch
So, 40 °F to be added to the correction factors at table 310.15(B)(2)(A).
Step#2: Assuming an ambient temperature of 90°F , the temperature to use for conductor correction = 90°F + 40°F = 130°F ,
Step#3: As per table 310.15(B)(16), THWN-2 conductor has temperature rating 90°C and have allowable ampacity = 75A
Step#4: As per table 310.15(B)(2)(A), the adjustement factor for Ambient Temperature130°F and Temperature Rating of Conductor 90°C = 0.76
Step#5: So in this wiring method, the 6 THWN-2 conductor ampacity = 75 A X 0.76 = 57 A
Example#2:
Determine the ampacity of each of 10 current carrying no. 10 THW conductors installed in the same IMC, with an ambient temp of 105°f, connecting to terminals rated at 60°C.
Solution:
Step#1: Find the no. 10 THW on table 310.15(B)(16), we find it in the 75°C column, however the terminals are rated at 60°C, so we will use the ampacity from the 60°C column; which will be 30 amps.
Step#2: As per table 310.15(B)(2)(A), the adjustement factor for Ambient Temperature105°F and Temperature Rating of Conductor 75°C = 0.82
Step#3: The problem mentioned that we have 10 current carrying conductors installed in the same IMC, for this we will use table TABLE 310.15(B)(3)(a)
No. of current carrying conductors = 10, so the adjustment factor = 50%.
Step#4: Multiply the current rating of no. 10 THW Conductor from step#1 by the two correction/adjustment factors from steps# 2 & 3
Rating of each no. 10 THW Conductor = 30 x 0.82 x 50% = 12.3 A
As a summary, many
corrections may be made for any conductor ampacity as follows:
|
In the next Article, I will explain some Special Cases for Conductor Ampacity Calculations. Please, keep following.
No comments:
Post a Comment