In Article " Conductor Ampacity Calculation – Part Six ", I indicated Some special cases for the application of adjustment factor of table 310.15(B)(3)(a) where is More Than Three Current-Carrying Conductors in a Raceway or Cable, which were: 
- Bare or Covered Conductors,
- Neutral Conductor,
- Grounding or Bonding Conductor,
- Main feeders to Dwelling units,
- Conductors contained in sheet metal auxiliary gutter,
- Conductors contained in Nonmetallic Auxiliary Gutters,
- Conductors in Metal Wireways,
- Conductors for Remote Remote-Control, Signaling, And Power-limited Circuits,
- Conductors for Fire Alarm Systems,
- Conductors and Cables in Cable Trays.
Today, I will explain Last Special Case for Conductor Ampacity Calculations: Conductors and Cables in Cable Trays as follows.
For more information and good following, please review the following articles:
Conductors and Cables Ampacity Calculations in Cable Trays
| 
Rule#1: Ampacity of
  Multiconductor Cables, Rated 2000 Volts or Less, installed in Cable Trays 
As per
  392.80(A)(1), the Ampacity of Multiconductor Cables, Rated 2000 Volts or
  Less, installed in Cable Trays using the allowable fill areas
  as per Section 392.22(A), shall be as given in Table 310.15(B)(16) and Table 310.15(B)(18)
  subject to the three below provisions. | 
| 
Provision#1 
If
  there are more than 3 current carrying conductors in a multiconductor cable,
  derate cable ampacity per section 310.15(B)(3)(A). | 
| 
Note to Provision#1 
Adjustment factors shall be
  limited to the number of current-carrying conductors in the cable and not to
  the number of conductors in the cable tray. | 
| 
Provision#2 
Where cable trays are continuously covered for more than 1.8 m
  (6 ft) with solid unventilated covers, use 95% of the ampacity
  values shown in Table 310.15(B)(16) and Table 310.15(B)(18) for multiconductor
  cables. | 
| 
Note to Provision#2 
Where cable tray
  covers are to be used, it is best to use raised or ventilated covers so that
  the cables can operate in a lower ambient temperature. | 
| 
Provision#3 
If multiconductor cables
  are placed in a single layer in uncovered trays, with a maintained spacing of
  not less than (1) cable diameter between cables, the ampacity of the cables
  shall not exceed the allowable ambient temperature-corrected ampacities of
  multiconductor cables with not more than (3) insulated conductors in free air
  in accordance with Section 310.15(C) and Table B.310.15(B)(2)(3). (see
  below image) | 
| 
Note to Provision#3 
By spacing the
  cables one diameter apart, the engineer may increase the allowable ampacities
  of the cables to the free air rating as per Section 310.15(C) and Table B.310.15(B)(2)(3)in Appendix B.
  Notice that the allowable fill of the cable tray has been decreased in this
  design due to the cable spacing. | 
| 
Notes to Rule#1 
 
 
 | 
| 
Rule#2: Selection
  Of Ampicity For Multi-Ampacity Conductors 
As per 310.15(A)(2), Where more than one ampacity applies for a
  given circuit length, the lowest value shall be used. (see below image) | 
| 
Exception Rule#2 
A higher ampacity is
  permitted, if the length of the reduced ampacity doesn’t exceed 10 ft and is not
  longer than 10% of the total length of the circuit. | 
Example#1:
Five nos., 4 conductor multi cables, 1/0 AWG, THHN are stacked together in a solid-bottom cable tray with two nos., 4 conductor multi cables, 350 Kcmil, THHN installed as a single layer. What are the ampacity of these multiconductor cables noting that all conductors in cables are current carrying conductors?
Solution:
Step#1: From table 310.15(B)(16), find the allowable ampacity for these multiconductor cables
Allowable ampacity For 350 Kcmil THHN = 350 A Allowable ampacity For 1/0 AWG THHN = 170 A
Step#2: Applying Adjustment Factors from table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors in a Raceway or Cable
Since, Adjustment factors shall be limited to the number of current-carrying conductors in the cable and not to the number of conductors in the cable tray.
Nos. of current carrying conductors in cable = 4
So, the Adjustment Factors from table 310.15(B)(3)(a) = 80%
Derated allowable ampacity For 350 Kcmil THHN = 350 A x 80% = 280 A
Derated allowable ampacity For 1/0 AWG THHN = 170 A x 80% = 135 A
Example#2:
Same cables as in example#1, but the cable tray has a solid cover, What are the ampacity of these multiconductor cables noting that all conductors in cables are current carrying conductors?
Solution:
Step#1: From table 310.15(B)(16), find the allowable ampacity for these multiconductor cables
Allowable ampacity For 350 Kcmil THHN = 350 A Allowable ampacity For 1/0 AWG THHN = 170 A
Step#2: Applying Adjustment Factors from table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors in a Raceway or Cable
Since, Adjustment factors shall be limited to the number of current-carrying conductors in the cable and not to the number of conductors in the cable tray.
Nos. of current carrying conductors in cable = 4
So, the Adjustment Factors from table 310.15(B)(3)(a) = 80%
Derated allowable ampacity For 350 Kcmil THHN = 350 A x 80% = 280 A
Derated allowable ampacity For 1/0 AWG THHN = 170 A x 80% = 135 A
Step#3: Applying 392.80(A)(2), Derate ampacity by 95%
Derated allowable ampacity For 350 Kcmil THHN = 280 A x 95% = 266 A
Derated allowable ampacity For 1/0 AWG THHN = 135 A x 95% = 128.25 A = 129 A
| 
Rule#3: Ampacity of Single-Conductor
  Cables Cables, Rated 2000 Volts or Less, installed in Cable Trays 
As per
  392.80(A)(2), for Single-Conductor Cables or single conductors cabled
  together (triplexed, quadruplexed, etc.), Rated 2000 Volts or Less, installed
  in Cable Trays according to the requirements of 392.22(B), The adjustment
  factors of 310.15(B)(3)(a) shall not apply , and the ampacity shall comply
  with the below Table. | 
| 
Ampacity of Cables Rated 2000 Volts or Less in Cable Tray
  (single conductor cables) | ||||
| 
cable size | 
solid unventilated cable tray cover (for more than 1.8 m (6 ft)
  ) | 
applicable ampacity tables | 
multiply Ampacity Table values by | 
special conditions | 
| 
600 K cmil and larger | 
no cover allowed (**) | 
310.15(b)(17) and 310.15(B)(19) | 
0.75 | |
| 
600 K cmil and larger | 
yes | 
310.15(b)(17) and 310.15(B)(19) | 
0.7 | |
| 
1/0 AWG through 500 Kcmil | 
no cover allowed (**) | 
310.15(b)(17) and 310.15(B)(19) | 
0.65 | |
| 
1/0 AWG through 500 Kcmil | 
yes | 
310.15(b)(17) and 310.15(B)(19) | 
0.6 | |
| 
1/0 AWG & Larger in single layer | 
no cover allowed (**) | 
310.15(b)(17) and 310.15(B)(19) | 
1 | 
maintained spacing of one cable diameter | 
| 
Single conductors in triangle configuration 1/0 AWG and Larger (see
  below image) | 
no cover allowed (**) | 
310.15(B)(20) (see NEC section 310.15(B)) | 
1 | 
Spacing of 2.15 x one conductor O.D. between cables (***) | 
| 
(*) The ambient ampacity
  correction factors must be used. | ||||
| 
(**) At a specific
  position, where it is determined that the tray cables require mechanical
  protection, a single cable tray cover of six feet or less in length can be installed. | ||||
| 
(***) O.D. of the largest conductor contained within the
  configuration and adjacent conductor configurations or cables, the spacing of 2.15 times one conductor diameter is to be maintained between circuits. Two interpretations of this statement are possible as follows: 
 
The use of the
  word “circuit” is unfortunate as its presence promotes Interpretation #1. An
  installation based on Interpretation #1 is not desirable as a free air space
  equal to 2.15 times one conductor diameter between the cable bundles should be
  maintained to promote cable heat dissipation. | ||||
Example#3:
Four single Copper conductors 700 Kcmil THHN installed in uncovered cable tray as a single layer, what is the allowable ampacity for these conductors?
Solution:
Step#1: From table 310.15(B)(17), find the allowable ampacity for these single conductors
Step#2: Applying 392.80(A)(2)(a), Derate ampacity by 75%
Derated allowable ampacity For 700 Kcmil THHN = 855 A x 75% = 641 A
Example#4:
Same as example#3, but the cable tray is covered, what is the allowable ampacity for these conductors?
Solution:
Step#1: From table 310.15(B)(17), find the allowable ampacity for these single conductors
Allowable ampacity For 700 Kcmil THHN = 855 A
Step#2: Applying 392.80(A)(2)(a), Derate ampacity by 70%
Derated allowable ampacity For 700 Kcmil THHN = 855 A x 75% = 598.5 A = 599 A
| 
Rule#4: Ampacity for
  Combinations of Multiconductor and Single-Conductor Cables in the same cable
  tray 
As per NEC
  392.80(A)(3), Combination of multiconductor and single- conductor cable in
  the same cable tray must not exceed the fill requirements for each type of
  cable as if it were installed in its own tray and all installation
  requirements and ampacity limits for each cable type apply, provided that the
  following conditions apply: 
The sum of the
  multiconductor cable fill area as a percentage of the allowable fill area for
  the tray calculated in accordance with 392.22(A), and the single-conductor
  cable fill area as a percentage of the allowable fill area for the tray
  calculated in accordance with 392.22(B), totals not more than 100 percent. 
Multiconductor
  cables are installed according to 392.22(A) and single-conductor cables are
  installed according to 392.22(B) and 392.22(C) and (D). | 
In the next Article, I will explain the second method: Under engineering supervision, as provided in 310.15(C). Please, keep following.
 
 
 
 
Thanks for this thorough explanation and citing the reference code rule and tables that has to be read in conjunction. Well done and keep up the great work.
ReplyDelete