In the previous article “Classification and Types of UPS – Part One”, we stated that UPS is classified according to:
- Voltage range,
- No. of phases,
- Mobility,
- Technological design,
- Physical Size/capacity,
- Form factor/ configurations,
- Topology,
- Distribution Architecture,
- Use of transformers.
We already
explained all classifications in the Previous articles (see table in the end of
Article) and today we will explain Transformer arrangements in practical UPS systems
related to the last classification “Use of transformers” using the papers from Schneider Electric – Data
Center Science Center.
|
Transformer
Arrangements in Practical UPS Systems |
|
As stated in previous article “Classification and Types of UPS – Part Seven”, 92 different arrangements of transformers are possible with a single UPS, even before redundancy configurations are considered. Instead of attempting to describe and compare
each of these arrangements, we will describe the functions and benefits of
the transformers in the three basic configurations:
From this, the preferred arrangements of transformers will be deduced and described. |
|
1- Transformer
options for the “single mains” configuration |
|
The single
mains system is the most common UPS configuration, used in over 50% of all
UPS installations. In smaller systems (below 100kW), it is even more
dominant, making up approximately 90% of all installations. The advantage
of this system is that it is relatively simple to design and install, yet it
provides a bypass that gives a variety of redundancy and maintenance
benefits. Small UPS
systems below 10 kW typically only have a single input and must be used in
the single mains configuration. UPS systems
over 10 kW usually provide for dual mains input but are converted to single
mains by simply connecting the two mains inputs together. The majority of UPS
systems shipped with dual mains input connections actually end up configured
for single mains input. In the single mains configuration,
transformers can be located in three positions as shown in Fig-1. Any
combination of these transformers, including none or all three, might exist
in a UPS installation. Fig-1 Possible
transformer locations in the “single mains” UPS configuration The inverter transformer, if present, is
always integral to the UPS, but the mains and output transformers can be
either located at the UPS or remotely located. Table-1 describes the
function of each transformer, when it is needed, and the issues related to
its physical location (local vs. remote). Table-1
Characteristics of the three SINGLE MAINS transformer locations
Notes to Table-1: The following observations can be made from a study of the functions of the transformers in the single mains UPS configuration:
There
is no advantage to using a transformer-based UPS in the single mains
configuration. |
|
There are 8 possible transformer
arrangements in a single mains UPS configuration. Tables -2a to 2c
below summarize the preferred transformer options for the single mains UPS
configuration, with guidance as to where each approach is used.
|
||||||||||||||||||||||||||||||||||||
|
Transformer Options
for the “Dual Mains” Configuration |
|
The dual mains configuration is
used in many, but not all, larger installations. Fig-2 shows four
options for transformer location in a dual mains system Fig-2 Possible
transformer locations for the DUAL MAINS configuration There are two core reasons that the dual
mains system is used: The first reason: The dual mains approach must be used when
the system architecture prescribes that the rectifier and the bypass supplies
come from different sources – for example, separate utility substations or in
highly specialized redundancy architectures. This requirement is actually
quite uncommon and is restricted to architectures designed for extreme
redundancy. Note that in most systems with alternate supplies, such as diesel
generators or secondary utility mains supplies, an automated transfer switch
is provided upstream of the UPS because there are other loads in addition to
the UPS – such as cooling plants – that must be backed up. The second reason: The dual mains design is used is to allow
for concurrent maintenance of the distribution wiring and breakers feeding
the UPS. If the breakers and wiring supplying the two mains inputs are
separate, either can be shut down without shutting down the critical load,
which will be powered from the remaining path during the maintenance. While
this is a common reason for specifying this arrangement, there are
alternative ways to allow for concurrent maintenance without using this
approach, such as a dual power path architecture or concurrently maintainable
parallel breakers. Inverter transformer, if present, is always integral to the UPS, but the rectifier, bypass, and output transformers can be either located at the UPS or remotely located. Table-3 describes the function of each transformer, when it is needed, and issues related to its physical location (local vs. remote). Table-3 Characteristics of the four DUAL
MAINS transformer locations
Notes to
table-3:
In
many cases, there is no advantage to using a transformer-based UPS in the
dual mains configuration. |
|
There are 16 possible combinations of
transformer arrangements in this system. When remote vs. local location
options for the mains and output transformers are considered, the number of
options grows to 56. Tables-4a to 4d
below summarize the preferred transformer options for the dual mains UPS
system, with guidance as to where each approach is used.
|
||||||||||||||||||||||||||||||||||||||||||||||||
In the next Article, I will
explain Transformer options for “single mains without
bypass”. So, please keep following.
|
Subject Of Pervious
Article |
Article |
|
Applicable Standards for UPS Systems What is a UPS? Why do we need a UPS? UPS Rating Classification of UPS: 1-Voltage range, 2-No. of phases, 3- Mobility, 4- Technological design, |
Classification and Types of
UPS – Part One |
|
5- Physical Size/capacity, 6- Form factor/ configurations: 6.1- “N” System
Configuration |
Classification and Types of UPS – Part Two |
|
6.2- “N+1” System
Configuration, which includes:
6.3- Parallel Redundant
with Dual Bus Configuration (N+1 or 1+1) |
Classification and Types of
UPS – Part Three |
|
6.4- Parallel Redundant with STS Configuration
6.5- System plus System
2(N+1), 2N+2, [(N+1) + (N+1)], and 2N |
Classification and Types of UPS – Part Four |
|
7- According to UPS Topology 7.1 Off-line or Standby UPS, 7.2 Line Interactive UPS, 7.3 Standby-Ferro UPS, 7.4 Online Double Conversion UPS, 7.5 The Delta Conversion On-Line UPS. |
Classification and Types of
UPS – Part Five |
|
8- According to UPS Distribution
Architecture 8.1 Centralized UPS Configuration, 8.2 Distributed (Decentralized) UPS Configuration, 8.2.1 Distributed UPS-Zonewise Configuration 8.3 Hybrid UPS Configuration. Conventional (Monolithic) Vs Modular
UPS System:
|
Classification and Types of UPS – Part Six |
|
Three Basic Configurations Of Mains And Bypass For A UPS System:
9-According to Use of transformers with the UPS
|
Classification and Types of
UPS – Part Seven |









No comments:
Post a Comment