Today we will explain the following points:
- How to size the power and control cables used in PFC panels,
- Effects of Power Factor Correction Capacitors on Generators,
- Should capacitors be included in fault studies?
|
How
to size Cables for PFC Panels?
|
|
Cables are used inside PFC panels for:
The selection of a proper and adequate cable for PFC panels depends
on the following Points:
|
|
First:
Sizing Power Cables for Power Circuit
|
|
Power cables are used for interconnection between bus bar, step
protection, switches, reactors and capacitors. The power cables for power
circuit inside PFC panels must have the following characteristics:
Power cables are sized based on the following methods:
|
|
First Method: General Rule
NEC code article 460 stated that “The ampacity of capacitor circuit
conductors shall not be less than 135 percent of the rated current of the
capacitor” this means that:
I cable
= 1.35 x In
Where:
I cable: designed power cable
current capacity
In: the rated capacitor current
Some manufacturers recommend that the Power conductors must be oversize
to carry continuous current of at least 1.5 times the rated capacitor current
at a temperature of 50˚C
I cable
= 1.5 x In
Reason to oversize the
wire serving a capacitor bank:
Example#1:
For 50 KVAR, 3 phase, 400V, 50Hz capacitor. Calculate the rated
current? And the designed power cable current capacity?
Solution:
IN = KVAR x 103 / (√3 x UN)
IN = (50 × 1000) / (1.732 × 400)
IN = 72.16 A
I cable = 1.5
x In = 1.5 x 72.16 = 108.24 A
|
|
Second Method: Manufacturers’ Tables
Various manufacturers of cables distinguish cables based on cable
diameter, current carrying capacity and type. Hence it is necessary to select
cables suitably to meet the needs in APFC panels.
Note:
Selection of suitable lugs is very much important in order to
achieve a proper joint. Proper crimping of these lugs to the cables should
also be ensured. Only 2 lugs are permitted in one hole for termination (i.e.
at either sides of the hole and not one above the other).
Below are the
most used manufacturer’s tables for getting the size of
cable, Fuse, Safety Switch And Circuit Breaker according to the used KVAR of
the PFC Panel.
1- Tables as per
NEC code (60 Hz):
Notes on above Tables:
2- Tables as per
VDE code (50 Hz):
|
|
Third Method: Rule of Thumbs
Rule of thumbs is used for sizing power cables for power circuit in
PFC panels are as follows:
|
|
Second:
Sizing Control Cable for Control Circuit
|
|
Control cable for control circuit inside PFC panels must have the
following characteristics:
Note: For Current Transformer connection the lug used should be ring type.
The following cable cross sections are recommended for control
wiring:
|
|
Power
Factor Correction Capacitors and Generators
|
|
|
Power
Factor & Generator Set KVA
Example#2:
Alternator output (kVA): 100kVA
So, Engine power output
(kW):
100kVA x
0.8 = 80Kw
Any changes in the rated PF
0.8 value lagging of the generator will affect the generator operation as
follows:
In case of
Lagging power factor <0.8:
lagging power factor
below 0.8 results in:
In case of
Lagging power factor >0.8 :
In case of
Leading power factor:
|
|
Should
Capacitors Be Included In Fault Studies?
|
|
|
End of the Course |
The
previous and related articles are listed in below table:
|
Subject Of
Previous Article
|
Article
|
|
Glossary of Power Factor Correction Capacitors
|
|
|
Types of Loads,
The Power
Triangle,
What is a power
factor?
Types of power
factor
Why utilities
charge a power factor penalty?
Billing Structure.
|
|
|
What causes
low power factor?
Bad impacts
of low power factor,
Benefits of
Power Factor correction.
|
|
|
How to make
Power Factor Correction?
Types of
Power Factor Correction Capacitors
Individual compensation
|
|
|
Group compensation,
Central compensation,
Hybrid compensation.
Summary for Power Factor Correction
Capacitors Sizing Calculations Steps
|
|
|
Step#1: Collect Monthly Billing Data
Step#2: Make Some Preliminary Measurements
For Current And Voltage
|
|
|
Step#3: Fill the Economic Screening Worksheet
|
|
|
Step#4: Make Preliminary Measurements
For Harmonics
Step#5: Repeat the Economic Screening
Worksheet
Step#6: Compare the Savings with the
Probable Cost of Capacitors' Installation
Second: Design Phase
Step#1: Performing a Detailed Plant
Survey
Step#1.A:
Review the one line diagram
Step#1.B:
Take into consideration the loads that produce harmonics
Step#1.C:
collect sufficient data Inventory by using measuring instruments
|
|
|
Step#2: Select Economical Capacitor Scheme
Step#3: Checking the "No Load" Voltage Rise
Step#4: Select Capacitor Switching Options
Step#5: Check the Harmonic Distortion and make Harmonic
Mitigation Options
Step#6: Use the Economic Screening Worksheet again
|
|
|
Power Factor Correction Capacitors
Sizing Calculations Steps For New Designs
|
|
|
Factors Affecting The Rated KVAR For a Capacitor
Calculation of the Capacitor KVAR Rating for Compensation at:
1-Transformer
2-Individual Motors
|
|
|
3- Calculation Of The Capacitor KVAR Rating For Buildings
And Power Plants(Group Compensation)
|
|
|
Harmonics Effects On Power Factor Capacitors
Harmonic Limits in Electric Power Systems (IEEE 519-2014)
Options to Reduce Harmonics for PFCC
Power Factor Compensation In Case Of Harmonics
|
|
|
Power
Factor Correction Capacitors Calculators:
1- Arteche Reactive Power and Harmonic Resonance Point
Calculator,
2- Eaton Power Factor Correction Calculator,
3- AccuSine Sizing
Spreadsheet,
4- Square-D (Schneider Electric) Calculator.
|
|
|
The Main Components of PFC Panel
How to select Circuit Breakers for PFC Panel
How to select Fuses for PFC Panel
How to select Contactors for PFC Panel
|
|
|
How to select a capacitor for PFC Panel and Capacitors’
rules
Capacitor compensation with a detuned reactor
How to Select a Detuned Reactor
|
|
|
How to Select a Discharge Resistor
How to Calculate the Value of Discharge Resistor How to Select Power Factor Controller How to Calculate the Number of Physical Steps, Electrical Steps and Electrical Control. |
|



No comments:
Post a Comment