As we explained before in article “Power Factor Correction Capacitors Sizing Calculations – Part Eleven”, how
to calculate the capacitor KVAR rating for compensation at:
- Transformers,
- Individual motors.
Today, we will explain
how to calculate the capacitor KVAR rating for buildings and power plants
(group compensation).
|
Calculation Of The Capacitor KVAR
Rating For Buildings And Power Plants
|
|
To calculate the capacitor
KVAR rating for buildings and power plants (group compensation), we have (2)
methods:
|
|
Method#1: By Using Measuring Devices
This method is used when the old P.F is unknown and there
different methods to measure/calculate this old PF and then calculate the
Capacitor KVAR Rating. These measuring methods are:
|
|
Direct
Method: Measurement Of Current And Power Factor
P = √3*V*I*cos
Ø*10-3 [kW]
After
this, we have (3) options:
1-
Calculation by using equation
If
the desired power factor cos Ø was specified, the capacitor power rating can be
calculated from the following formula.
QC = P · (tan Ø1 - tan Ø2) in KVAR
2- Calculation
by using Tables published by leading power factor capacitor manufacturers
QC = k.P
For more information about measuring the power
factor, please review our article “Power Factor Correction Capacitors Sizing Calculations – Part Six”.
Table-1
Note:
Example#1:
Measured readings in one project are as follows:
Apparent
current: 248 A
Power
factor cos Ø1: 0.86
Desired
cos Ø2: 0.92
Voltage
: 397 V
Calculate
the KVAR rating for the power factor correction capacitors.
Solution:
P = √3*V*I*cos Ø*10-3 [kW]
P = √3 * 397 * 248 * 0.86 · 10-3 = 146.6 kW
By using equation:
QC = P* (tan Ø1 -
tan Ø2) =
146.6 x (0.59 – 0.43) = 23.456 KVAR
By using Table-1 we obtain:
Factor k = 0.17
Required capacitor rating:
QC = 146.6 * 0.17 = 24.9 KVAR
3- Calculation
By Using Nomographs
The Nomograph
shown
in figure-1 is used to calculate the capacitor KVAR rating as follows:
Fig.1
Example#2:
An
80 KW load with power factor 0.64, calculate the required KVAR capacitor
rating to get a 0.9 PF by using the nomograph method.
Solution:
First,
trace a line segment from the value of the load 80 KW to the initial cosØ = 0.64 then to the
KVAR line will give Initial KVAR value = 96 KVAR.
Then trace
a line segment from the value of the load 80 KW to the desired cosØ= 0.9 then to the
KVAR line will give final KVAR value = 38.4 KVAR.
Finally,
subtract (Initial KVAR value – final KVAR value) = (96 - 38.4) = 57.6 KVAR
this will be the desired Capacitor KVAR Rating.
If you apply
the given data to table it will give the same value 57.6 KVAR
|
|
Indirect Methods: Measurements With Recording Of Active And
Reactive Power
More
reliable results are obtained with recording instruments. The parameters can
be recorded over a longer period of time, peak values also being included.
Required capacitor power rating is then calculated as follows:
QC = QL – (P · tan Ø2)
Where:
QC = required capacitor rating
QL = measured reactive power
P = measured active power
tan Ø2 =
the corresponding value of tan Ø at the desired cos Ø (can
be obtained from Table-1, (e.g. when cos Ø= 0.92 the
corresponding tan Ø= 0.43)
|
|
Indirect Methods: Measurement By Reading Meters
The
active and reactive current meters are read at the start of a shift. Eight
hours later both meters are read again. If there has been a break in
operation during this time, the eight hours must be extended by the duration
of this break. Tan Ø can be calculated from the following equation:
tan Ø =
(RM2 – RM1) / (AM2 – AM1)
Where:
RM1 = reactive current meter reading at start
RM2 = reactive current meter reading at finish
AM1 = active current meter reading at start
AM2 = active current meter reading at finish
Using
this calculated value of tan Ø and the desired cos Ø we
can then obtain the factor k from
Table-1.
Then,
The required capacitor power rating can thus be derived:
QC = k* f* (AM2 – AM1 ) /8
Where:
The
parameter f is
the ratio of the meter current transformers.
Example#3:
The
following meter readings have been noted:
active
current meter
(AM1)...115.3 KWH
(AM2 )...124.6 KWH
reactive
current meter
(RM1)...311.2 KVAR
(RM2)...321.2 KVAR
The
meters work with 150/5 A current transformers. Calculate the KVAR rating for
the power factor correction capacitors.
Solution:
tan Ø = (RM2 – RM1) / (AM2 – AM1)
tan Ø = (3 2 1 . 2 – 3 1 1 . 2) /(124.6
– 115.3) = 1.08
For a desired cos Ø of 0 .92 a factor k of 0.65 is obtained from Table-1.
150/5
A current transformers are used, so here the factor f = 150/5 = 30
The capacitor power rating is thus
QC = k* f* (AM2 – AM1 ) /8
QC =0.65*30*(124.6 – 115.3 )/8 = 22.67 KVAR
|
|
Method#2: By Using The Utility Company’s Invoice
First:
In case of using Kilowatt-hour tariff
the
following procedure can be used to calculate the KVAR rating for the power factor
correction capacitors:
Step#1:
Calculate Tan Ø from the following equation:
tan Ø = reactive energy (regular) /
active energy (regular )
Step#3: Multiply KW by the K multiplier to get the proper Capacitor KVAR Rating.
QC = k.P
Example#4:
The
data derived from the utility company´s invoice are as follows:
Active
power 99 kW
Active
energy (regular tariff) 17820 kWh
Reactive
tariff (off-peak) 19840 kVArh
Calculate
the KVAR rating for the power factor correction capacitors.
Solution:
Step#1:
Calculate Tan Ø from the following equation:
tan Ø= reactive energy (regular) /
active energy (regular )= 19840 KVARH / 17820 kWh =
1.11
Step#2:
The actual value of cos Ø can now be obtained from Table 2, since the
calculated tan Ø of 1.11 corresponds to a cos Ø1
of 0.67.
A
factor k of 0.68 is
then obtained from Table 2 to produce a desired cos Ø2 =
0.92.
Step#3: The
required capacitor power rating is calculated from:
QC = k.P = 0.68 x 99 kW = 67.32 KVAR
In
this case a standard capacitor rating of 75 kVAr must be selected. If a
possible future expansion of the facility is also to be taken into account,
then a somewhat larger capacitor, (e.g. 100 kVAr) could also be selected.
Second:
In case of using Demand tariff
the
following procedure can be used to calculate the KVAR rating for the power
factor correction capacitors:
Step#1:
Use table-1 to find the multiplier factor k
Step#2: Multiply KW by the K multiplier to get the proper Capacitor KVAR
Rating.
QC = k.P
Note: In this case the utility company bases its invoice on the maximum amount of power drawn by the user during the given month. It is advisable to select a capacitor power rating that will achieve a cos Ø2 of 1.
Example#5:
The
data derived from the utility company´s invoice are as follows:
Maximum
active power = 104 kW
cos
Ø1 =
0.62
Calculate
the KVAR rating for the power factor correction capacitors.
Solution:
Step#1: From
Table-1, with an uncorrected cos Ø1 = 0.62 and a
desired cos Ø2 = 1, a factor k of 1.27 is read off.
Step#2: Multiply KW by the K multiplier to get the proper Capacitor KVAR
Rating.
QC = k.P = 1.27 x 104= 132.08 KVAR
For
this duty a reactive power control relay with a capacitor power rating of 150
to 175 KVAR is arranged as a switched variable bank.
|
|
Important notes for
sizing Capacitor KVAR Rating For Buildings And Power Plants
QcY
= QcΔ
CY = 3 ・ CΔ
|
In the
next article, we will explain the Effects of
Harmonics on Power Factor Capacitors. Please, keep following.
The
previous and related articles are listed in below table:
|
Subject Of
Previous Article
|
Article
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Back To |



No comments:
Post a Comment