As we explained before in article “Power Factor Correction Capacitors Sizing Calculations – Part Eleven”, how
to calculate the capacitor KVAR rating for compensation at:
- Transformers,
- Individual motors.
Today, we will explain
how to calculate the capacitor KVAR rating for buildings and power plants
(group compensation).
| 
Calculation Of The Capacitor KVAR
  Rating For Buildings And Power Plants | 
| 
To calculate the capacitor
  KVAR rating for buildings and power plants (group compensation), we have (2)
  methods: 
 | 
| 
Method#1: By Using Measuring Devices 
This method is used when the old P.F is unknown and there
  different methods to measure/calculate this old PF and then calculate the
  Capacitor KVAR Rating. These measuring methods are: 
 
 | 
| 
Direct
  Method: Measurement Of Current And Power Factor 
 
 
 
P = √3*V*I*cos
  Ø*10-3  [kW] 
After
  this, we have (3) options: 
1-
  Calculation by using equation 
If
  the desired power factor cos Ø was specified, the capacitor power rating can be
  calculated from the following formula.  
QC = P · (tan Ø1 - tan Ø2) in KVAR 
2- Calculation
  by using Tables published by leading power factor capacitor manufacturers 
 
QC = k.P 
For more information about measuring the power
  factor, please review our article “Power Factor Correction Capacitors Sizing Calculations –  Part Six”. 
Table-1 
Note: 
 
Example#1:  
Measured readings in one project are as follows: 
Apparent
  current: 248 A 
Power
  factor cos Ø1: 0.86 
Desired
  cos Ø2: 0.92 
Voltage
: 397 V  
Calculate
  the KVAR rating for the power factor correction capacitors. 
Solution: 
P = √3*V*I*cos Ø*10-3  [kW]  
P = √3 * 397 * 248 * 0.86 · 10-3 = 146.6 kW 
By using equation: 
QC = P* (tan Ø1 -
  tan Ø2) =
  146.6 x (0.59 – 0.43) = 23.456 KVAR 
By using Table-1 we obtain: 
Factor k = 0.17 
Required capacitor rating: 
QC = 146.6 * 0.17 = 24.9 KVAR 
3- Calculation
  By Using Nomographs 
The Nomograph
  shown
  in figure-1 is used to calculate the capacitor KVAR rating as follows: 
Fig.1 
 
Example#2: 
An
  80 KW load with power factor 0.64, calculate the required KVAR capacitor
  rating to get a 0.9 PF by using the nomograph method. 
Solution: 
First,
  trace a line segment from the value of the load 80 KW to the initial cosØ = 0.64 then to the
  KVAR line will give Initial KVAR value = 96 KVAR. 
Then trace
  a line segment from the value of the load 80 KW to the desired cosØ= 0.9 then to the
  KVAR line will give final KVAR value = 38.4 KVAR. 
Finally,
  subtract (Initial KVAR value – final KVAR value) = (96 - 38.4) = 57.6 KVAR
  this will be the desired Capacitor KVAR Rating. 
If you apply
  the given data to table it will give the same value 57.6 KVAR | 
| 
Indirect Methods: Measurements With Recording Of Active And
  Reactive Power 
More
  reliable results are obtained with recording instruments. The parameters can
  be recorded over a longer period of time, peak values also being included.
  Required capacitor power rating is then calculated as follows: 
QC = QL – (P · tan Ø2) 
Where: 
QC = required capacitor rating 
QL = measured reactive power 
P = measured active power 
tan Ø2 =
  the corresponding value of tan Ø at the desired cos Ø (can
  be obtained from Table-1, (e.g. when cos Ø= 0.92 the
  corresponding tan Ø= 0.43) | 
| 
Indirect Methods: Measurement By Reading Meters 
The
  active and reactive current meters are read at the start of a shift. Eight
  hours later both meters are read again. If there has been a break in
  operation during this time, the eight hours must be extended by the duration
  of this break. Tan Ø can be calculated from the following equation: 
tan Ø =
  (RM2 – RM1) / (AM2 – AM1) 
Where: 
RM1 = reactive current meter reading at start 
RM2 = reactive current meter reading at finish 
AM1 = active current meter reading at start 
AM2 = active current meter reading at finish 
Using
  this calculated value of tan Ø and the desired cos Ø we
  can then obtain the factor k from
  Table-1. 
Then,
  The required capacitor power rating can thus be derived: 
QC = k* f* (AM2 – AM1 ) /8 
Where: 
The
  parameter f is
  the ratio of the meter current transformers.  
Example#3:
   
The
  following meter readings have been noted: 
active
  current meter 
(AM1)...115.3 KWH 
(AM2 )...124.6 KWH 
reactive
  current meter  
(RM1)...311.2 KVAR 
(RM2)...321.2 KVAR 
The
  meters work with 150/5 A current transformers. Calculate the KVAR rating for
  the power factor correction capacitors. 
Solution: 
tan Ø = (RM2 – RM1) / (AM2 – AM1) 
tan Ø = (3 2 1 . 2 – 3 1 1 . 2) /(124.6
  – 115.3)  = 1.08 
For a desired cos Ø of 0 .92 a factor k of 0.65 is obtained from Table-1. 
150/5
  A current transformers are used, so here the factor f = 150/5 = 30 
The capacitor power rating is thus 
QC = k* f* (AM2 – AM1 ) /8 
QC =0.65*30*(124.6 – 115.3 )/8 = 22.67 KVAR | 
| 
Method#2: By Using The Utility Company’s Invoice 
 
 
 
 
First:
  In case of using Kilowatt-hour tariff  
the
  following procedure can be used to calculate the KVAR rating for the power factor
  correction capacitors: 
Step#1:
  Calculate Tan Ø from the following equation: 
tan Ø = reactive energy (regular) /
  active energy (regular ) Step#3: Multiply KW by the K multiplier to get the proper Capacitor KVAR Rating. 
QC = k.P 
Example#4: 
The
  data derived from the utility company´s invoice are as follows: 
Active
  power 99 kW 
Active
  energy (regular tariff) 17820 kWh 
Reactive
  tariff (off-peak) 19840 kVArh 
Calculate
  the KVAR rating for the power factor correction capacitors. 
Solution: 
Step#1:
  Calculate Tan Ø from the following equation: 
tan Ø= reactive energy (regular) /
  active energy (regular )= 19840 KVARH / 17820 kWh =
  1.11 
Step#2:
  The actual value of cos Ø can now be obtained from Table 2, since the
  calculated tan Ø of 1.11 corresponds to a cos Ø1
  of 0.67. 
A
  factor k of 0.68 is
  then obtained from Table 2 to produce a desired cos Ø2 =
  0.92. 
Step#3: The
  required capacitor power rating is calculated from:  
QC = k.P = 0.68 x 99 kW = 67.32 KVAR 
In
  this case a standard capacitor rating of 75 kVAr must be selected. If a
  possible future expansion of the facility is also to be taken into account,
  then a somewhat larger capacitor, (e.g. 100 kVAr) could also be selected. 
Second:
  In case of using Demand tariff 
the
  following procedure can be used to calculate the KVAR rating for the power
  factor correction capacitors: 
Step#1:
  Use table-1 to find the multiplier factor k  
Step#2: Multiply KW by the K multiplier to get the proper Capacitor KVAR
  Rating. 
QC = k.P 
Note: In this case the utility company bases its invoice on the maximum amount of power drawn by the user during the given month. It is advisable to select a capacitor power rating that will achieve a cos Ø2 of 1. 
Example#5: 
The
  data derived from the utility company´s invoice are as follows: 
Maximum
  active power = 104 kW 
cos
  Ø1 =
  0.62 
Calculate
  the KVAR rating for the power factor correction capacitors. 
Solution: 
Step#1: From
  Table-1, with an uncorrected cos Ø1 = 0.62 and a
  desired cos Ø2 = 1, a factor k of 1.27 is read off. 
Step#2: Multiply KW by the K multiplier to get the proper Capacitor KVAR
  Rating. 
QC = k.P = 1.27 x 104= 132.08 KVAR 
For
  this duty a reactive power control relay with a capacitor power rating of 150
  to 175 KVAR is arranged as a switched variable bank. | 
| 
Important notes for
  sizing Capacitor KVAR Rating For Buildings And Power Plants 
 
 
 
QcY
  = QcΔ 
CY = 3 ・ CΔ 
 | 
In the
next article, we will explain the Effects of
Harmonics on Power Factor Capacitors. Please, keep following.
The
previous and related articles are listed in below table:
| 
Subject Of
  Previous Article | 
Article | 
| 
 | |
| 
 |  | 
| 
 |  | 
| 
 |  | 
| 
 |  | 
| 
 |  | 
| 
 | |
| 
 |  | 
| 
 |  | 
| 
 |  | 
| 
 |  | 
| Back To | 
 



 
 
 
No comments:
Post a Comment