In Article " Electrical Rules and Calculations for Air-Conditioning Systems – Part One ", which was the first Article in our new Course HVAC-2: Electrical Rules and Calculations for Air-Conditioning Systems, I explained the following points:
- Introduction for Air-Conditioning Systems Types
- Introduction for Types of Motors/Compressors used in Air-Conditioning Systems
And in Article " Electrical Wiring Diagrams for Air Conditioning Systems – Part One ", I explained the following points:
- Importance of Electrical Wiring for Air Conditioning Systems,
- How to get the Electrical Wiring for Air Conditioning systems?,
- Types of Electrical Wiring Diagrams For Air Conditioning Systems,
- How to read Electrical Wiring Diagrams?
Also, I explained the electrical wiring diagrams for Typical Air conditioning equipments in the following Articles:
Today, I will explain in detail identification and Marking of Disconnecting Means used for Air Conditioning Systems.
1- Classification of Electrical Distribution Systems
according to Interrupting
Ratings of their OCPD Combinations
|
All the disconnecting means
(or generally all the overcurrent protective devices OCPD) in a building’s
electrical distribution system are arranged, with respect to their short
circuit ratings /interrupting ratings, in two combinations as follows:
Each system from the above can consist of
all fuses, all circuit breakers, or a combination of fuses and circuit
breakers.
|
1.1 Differences between Fully Rated And Series Rated Systems
|
1.3 Difference between Series Rated System and Selective
Coordinated System
|
2- Identification and Marking of Disconnecting Means
|
Based on the
above discussion, any disconnect means will be used either in a fully Rated
Combination System or in a Series Rated Combination System as described in
above.
First: Identification of Disconnecting Means used in a fully
Rated Combination System
For Identification of
Disconnecting Means used in a fully Rated Combination System, the rules NEC
240.60 and 240.83 are applied as shown in below.
As we stated above that a
fully rated system consist of all fuses, all circuit breakers, or a combination
of fuses and circuit breakers. For this reason, we will explain the
identification/Marking of Fuses and Molded Case Circuit breakers that widely
used as disconnecting means for Air conditioning systems.
|
1- Marking for Fuses
Fuses shall be plainly
marked, either by printing on the fuse barrel or by a label attached to the
barrel showing the following: (see Fig.5)
|
2- Marking for Molded Case Circuit breakers
Circuit breakers shall have
marking showing the following:
Examples for important
markings of Molded Case Circuit breakers:
Example#1: As shown in Fig.6,
the numbered marking will be as follows:
1. ON and OFF:
The ON and OFF
(closed and open) positions of the handle must be marked (NEC 240.81). These
positions may also be marked with the internationally recognized “I” and “O”
symbols, although this is not a UL requirement. If these markings are not
visible when a motor operator is installed over the circuit breaker markings,
then they must appear on the motor operator. Motor operators may be found in
applications where remote or automatic operation of a circuit breaker is
required.
2. Ampere
Rating (if 100 A or less):
The ampere rating
may be located on the handle escutcheon or on the handle itself (NEC
240.83(B)). Circuit breakers that are rated more than 100 A may have their
ampere rating marked in a position that is not visible with trims or covers
in place.
3. HACR type:This marking indicates the circuit breaker is suitable for use with the group motor installations typically found in heating, air conditioning and refrigeration equipment. The NEC 2005 no longer has this marking requirement. The electrical industry determined that circuit breakers are considered suitable for use with such equipment without any further testing, therefore, the HACR marking is no longer required on air conditioning and refrigeration equipment or on circuit breakers for use in these applications. The requirement for this marking has also been removed from the UL 1995 product standard for HVAC equipment.
Example#2: As shown in Fig.7,
the numbered marking will be as follows:
1. Manufacturer’s
Name:
This marking may
be the manufacturer’s name, trademark or other recognized means to
identifying the company that made the circuit breaker.
2. Type
Designation:
All circuit
breakers are marked with a type designation, which may be a catalog number
prefix or a separate designation. Equipment labels, such as on panelboards,
will list the circuit breaker types suitable for use. Note that the word
“type” may or may not be used on the circuit breaker or equipment labels. It
is important to review the markings on the equipment, such as a panelboard,
to make sure the circuit breaker designations on the equipment match the
marking on the circuit breaker.
3. Voltage Rating:
All circuit
breakers must be marked with a voltage rating. If the rating is not marked
“ac” or “dc,” then it is suitable for both. 120/240 V rated circuit breakers
are suitable for use on single and three-phase 4-wire systems where the
line-to-ground voltage does not exceed 120 V. Wye rated circuit breakers such
as those rated 480Y/277 V, are suitable for use on three-phase 4-wire
systems where the voltage to ground does not exceed 277 V. Special attention
needs to be given to high leg or corner-grounded delta systems to insure that
the circuit breaker has the appropriate rating. A review to see that the
circuit breakers installed have a voltage rating suitable for the application
is paramount for a code-compliant installation (NEC 240.83(E)).
4. SWD:
15- or 20-A
circuit breakers rated 347 V or less may be marked “SWD,” meaning that they
are suitable for switching fluorescent lighting loads on a regular basis (NEC
240.83(D)). These circuit breakers are evaluated for high endurance use,
since they will be used similar to a light switch.
5. HID:
50 A or less
circuit breakers rated 480 V or less may be marked “HID,” meaning they are
suitable for switching high intensity discharge or fluorescent lighting loads
on a regular basis. These circuit breakers may employ a different
construction than a standard SWD circuit breaker in order to address the high
inrush current resulting from the lower power factor created by the HID
lighting (NEC 240.83(D)). These circuit breakers also undergo additional
endurance evaluation to demonstrate their ability to perform the switching
duty.
6. Trip and Reset:
Circuit breaker
handles typically assume an intermediate position when tripped. This position
must either be marked on the circuit breaker or on the equipment into which
it is to be installed. If these markings are not visible when a motor
operator is installed, then a “tripped” marking may appear on the motor
operator.
Example#3: As shown in Fig.8,
the numbered marking will be as follows:
1. Line and Load
Designation:
Circuit breakers
marked with “line” and “load” designations are not suitable for reverse
connection. Circuit breakers with interchangeable trip units must be marked
“line” and “load” unless there is no risk of shock when changing the trip
unit.
2. Interrupting
Ratings:
All circuit breakers with an interrupting
rating more than 5000 A must be marked with an interrupting rating
(NEC 240.83(C)). Interrupting ratings are stated in RMS symmetrical amperes.
If the short-circuit current rating of the equipment in which the circuit
breaker is installed is less than the interrupting rating of the circuit
breaker, then the lesser rating applies. Circuit breakers should be reviewed
after installation to ensure they have an interrupting rating suitable for
the application. This marking may be found in any location except the back of
circuit breakers that are 1-½ inches wide per pole or less due to the size
constraint.
3. Ampere rating
(if more than 100 A):
The ampere rating of a circuit breaker
larger than 100 A may be found in a location that is visible after the cover
or trim is removed. This marking requirement also applies to interchangeable
trip units (NEC 240.83(A)).
5. Terminations
(Cu-Al wire):
Circuit breakers
must be marked with the type material (Cu-Al) and size of wire for which
their terminals are suitable for use. If suitable for use with only copper or
only aluminum, then the word “only” must be used. The abbreviations “CU” and
“AL” are generally found on circuit breakers as permitted by the product
standard. If only solid 10–14 AWG wire can be used, then that information
must be noted. The number of wires per terminal will also be noted if more
than one wire per terminal is permitted (NEC 110.14(A)).
6. Tightening
Torque:
The nominal torque
for all field-wiring terminals must be marked. If the width of the circuit
breaker is 1-½ inches per pole or less, then this marking may be found in any
location except on the back.
7. Wire
Temperature Ratings:
Circuit breakers
rated 125 A or less may be marked as suitable for use with 60°C,
60/75°C or 75°C only wire. Circuit breakers rated more than 125 A are rated
for use with 75°C wire; the marking is optional. It is always permissible to
use wire with a higher temperature rating, but it must be sized in accordance
with the temperature marking on the circuit breaker and NEC Table 310.16. If
the width of the circuit breaker is 1-½ inches per pole or less, then this
marking may be in any location except on the back (NEC 110.14(C)1).
Example#4: As shown in Fig.9,
the numbered marking will be as follows:
1. “1 – 3”
Marking:
A 2-pole circuit breaker used to protect a
3-phase load on a corner-grounded delta system must be rated and marked for
such an installation. Circuit breakers marked “1-phase – 3-phase” or “1 – 3
“are suitable for use on 3-phase corner-grounded delta or single-phase
circuits (NEC 240.85).
100% Rated
Marking:
100 percent
continuous rated – Circuit breakers are typically intended for use at not
more than 80% of rated current where the load is considered continuous, or
will continue for 3 hours or more (NEC 210.20). However, some circuit
breakers are rated for continuous use at 100% of their current rating. These
circuit breakers must be so marked in any location except on the back.
Enclosure information such as a specific type or specific volume must also be
marked. A requirement for the use of 90°C insulated wire sized to the 75°C column in NEC Table 310.16 and specific ventilation requirements may also be
marked on the circuit breaker or equipment (NEC 210.20(A) and 215.3).
|
Notes for Marking of Fuses
and Circuit breakers
|
Second: Identification Disconnecting Means used in a Series Rated
Combination System
For Identification of
Disconnecting Means used in a Series Rated Combination System, the rules NEC
240.86 and 110.22 are applied as shown in below.
The arrangement of protective
components in a series rated system is determined by two methods as follows:
The marking of a series rated
system will differ according to the two above method used for arrangement of
protective components as follows:
1- Marking for Engineered
Series Combination Systems:
Equipment enclosures for
circuit breakers or fuses shall be legibly marked in the field as directed by
the engineer and the marking shall be readily visible.
2- Marking for Tested Series
Combination Systems: (see Fig.10)
Example for series rated
system marking:
A- In case of Engineered
Series Combination Systems, The marking can be as follows:
CAUTION — ENGINEERED SERIES
COMBINATION SYSTEM RATED ………. AMPERES. IDENTIFIED REPLACEMENT COMPONENTS
REQUIRED.
B- In case of Tested
Series Combination Systems, the field marking can be as follows:
CAUTION — SERIES COMBINATION
SYSTEM RATED ………. AMPERES. IDENTIFIED REPLACEMENT COMPONENTS REQUIRED.
|
General Notes For Disconnecting Means Markings
|
In the next Article, I will explain in detail How to Locate and Size of Disconnecting Means used for Air Conditioning Systems. So, please keep following.

No comments:
Post a Comment