In Article " Electrical Rules and Calculations for Air-Conditioning Systems – Part One ", which was the first Article in our new Course HVAC-2: Electrical Rules and Calculations for Air-Conditioning Systems, I explained the following points:
- Introduction for Air-Conditioning Systems Types
- Introduction for Types of Motors/Compressors used in Air-Conditioning Systems
And in Article " Electrical Wiring Diagrams for Air Conditioning Systems – Part One ", I explained the following points:
- Importance of Electrical Wiring for Air Conditioning Systems,
- How to get the Electrical Wiring for Air Conditioning systems?,
- Types of Electrical Wiring Diagrams For Air Conditioning Systems,
- How to read Electrical Wiring Diagrams?
Also, I explained the electrical wiring diagrams for Typical Air conditioning equipments in the following Articles:
And in Article " Electrical Rules and Calculations for Air-Conditioning Systems – Part Two ", I explained Types of Disconnecting Means for Air-Conditioning Systems.
Also, in Article " Electrical Rules and Calculations for Air-Conditioning Systems – Part Three ", I explained identification and Marking of Disconnecting Means for Air-Conditioning Systems.
Today, I will explain in where to locate Disconnecting Means used for Air Conditioning Systems.
Location of Disconnecting
Means with respect to Controller, Motor and Driven Machinery Location
|
As we stated in Article " Electrical Rules and Calculations for Air-Conditioning Systems – Part Two " that
the definition of the term In Sight From (Within Sight From, Within Sight)
was as follows:
Where one equipment is
specified to be “in sight from,” “within sight from,” or “within sight of,”
and so forth, another equipment, the specified equipment is to be visible and
not more than 15 m (50 ft) distant from the other. (see Fig.1 & Fig.2)
|
First: for Motors and Motor-operated Equipments
|
1- NEC Code “In Sight From” Rules
There are several Rules in
the NEC Code for a disconnecting means to
be in sight from the equipment that it controls.
|
Rule#2
NEC 430.102(B) requires that Disconnect
must be in sight of motor location and driven machinery. If the disconnect as
required in 430.102(A) is in sight of the controller, the motor location, and
driven machinery, then that disconnect meets the requirements of both
430.102(A) and 430.102(B). (see Fig.4)
If, because of the nature of the
installation, the disconnect is in sight of the controller, but not in sight
of the motor location and the driven machinery, then, generally, another
disconnect must be installed. (see Fig.5)
Note:
When providing more than one
disconnecting means, At least one of them shall be readily accessible as per
NEC 430.107.
|
Rule#3
NEC 430.102(A) Exception No. 2 requires
that A
single disconnecting means may be located adjacent to (or in sight from) a group of coordinated
controllers, where the controllers are mounted on a multi-motor continuous
process machine.
(see Fig.6)
Note:
NEC
Code uses the terms motor location and controller location instead of motor
and controller because in many instances, the motor or controller is inside
an enclosure and is out of sight until an access panel is removed. If the
terms motor and controller were to be used, then it would be mandatory to
install the disconnect inside of the enclosure. This is not always practical.
The Commercial Building's roof-top air-conditioning units are examples.
|
Rule#4
Exceptions to Rule#4:
Exception No. 1: Where a motor receives
electric energy from more than one source, the disconnecting means for the
main power supply to the motor shall not be required to be immediately
adjacent to the motor, provided the controller disconnecting means is capable
of being locked in the open position.
Exception No. 2: A separate disconnecting
means shall not be required for a Class 2 remote-control circuit conforming
with Article 725, rated not more than 30 volts, and isolated and ungrounded.
|
2- Exceptions NEC Code “In Sight From” Rules
Three exceptions permit
disconnecting means to be located elsewhereand not in sight of a motor.
|
430.102(A) Exception No. 1
For motors over 600 volts,
the controller disconnecting means may be out of sight of the controller,
provided the controller has a warning label indicating the location and
identification of the disconnecting means, which must be capable of being
locked in the open position.
|
430.102(A) Exception No. 3
The disconnecting means
shall not be required to be in sight from valve actuator motor (VAM)
assemblies containing the controller (see Fig.8) where such a location
introduces additional or increased hazards to persons or property and the
following conditions are met:
|
430.102(B) exception
the disconnecting means may
only be out of sight of the motor, if the disconnecting means complying with 430.102(A) is individually capable
of being locked in the open position and meets the following cases:
Case#1:
Case#2:
Notes:
|
Second: for Air Conditioning Equipment
|
1- NEC Code “In Sight From” Rule
|
NEC 440.14
Note:
The main
purpose of above rule is providing protection for service personnel working
on equipment located in attics, on roofs, or outside in a remote location
where it is difficult to gain access to a remote lockable disconnect
|
2- Exceptions NEC Code “In Sight From” Rule
|
440.14
Exception
1
There is no need to place a
disconnecting means within sight from the equipment, if all of the following
conditions are verified:
Note:
440.14 Ex 1 is for special conditions such
as very large process refrigeration equipment and is rarely applicable for
the following reasons:
|
3- Exceptions NEC Code “Readily
Accessible” Rule
|
440.14 Exception 2
Fig.11: an attachment plug and receptacle as a disconnecting means for Room air conditioners
|
In the next Article, I will explain How to Size the Disconnecting Means used for Air Conditioning Systems. So, please keep following.
No comments:
Post a Comment