In Article " Earthing System Components – Part One ", I indicated that:
Earthing System Components 
Earthing system in an installation is normally
  comprised of the following components: 
  | 
 
1- Earth Wells and Accessories 
the prime components and accessories of an earth
  well will be: 
  | 
 
Also in this Article, I explained the first six items; Earth Rod, Earth Plate, Earthing Clamp, Earthing Rod Coupling, Earthing Rod Tip and Earthing Rod Driving Head with driving sleeve.
Today I will explain continue explaining other Components of Earthing Well and Earthing Systems as follows.
You can preview the following Articles for more info:
- Introduction to Grounding System Design – Part Two
 - Types of Earthing System – Part One
 - Types of Earthing System – Part Two
 - How to Select the Best Earthing System
 
Earthing System Components – Part Two
1.7 Earth Access Pit 
 
 
1- Earth Pit Sizes: 
Inspection pits are
  available in various sizes and materials.  
2- Earth Pits Main
  Types: 
A- According to
  location: 
a- Light Weight Duty 
Light-duty
  units are generally used. For example Plastic Light weight duty earth pits are schedule 40 PVC. 
b- Heavy Duty 
For areas of high
  vehicular traffic, you should use heavy-duty inspection wells. For example
  Plastic Heavy duty
  earth pits are schedule 80 PVC. 
B- According to Material 
Earth pit’s side walls are constructed of
  insulating material to appropriately isolate the earth rod’s top connection
  from the surrounding soil and protect it for furture reference test and
  maintenance practices.  
The materials used for fabrication of Earth Pits
  are: 
 
Note: 
  | 
 
1.8 Earth Pit Cover 
To protect the earth pits against ingression of
  foreign material, an appropriate concrete cover is provided to be placed atop
  the earth pit. 
The cover is equipped with a rigid handle for
  convenient removing and replacement practices. 
1- Earth Pit Cover Sizes: 
Inspection pits
  covers are available in various sizes to accommodate the size of their
  earthing pits. 
2- Earth Pit Cover Materials: 
The materials used for fabrication of Earth Pits
  Covers are: 
 
the ASTM specifications for Earth Pit Covers are as in the below image. 
 | 
 
1.9 Earth/ Ground Enhancement Materials (GEM) 
 
 
1- Where and when Earth Enhancement Materials should
  be used? 
Earth Enhancement Materials
  improves grounding effectiveness regardless of soil conditions and provides
  excellent permanent conductivity: 
 
2- Types of Earth Enhancement
  Materials 
Many types of Earth Enhancement
  Materials are used improves grounding effectiveness
  regardless of soil conditions and provides excellent permanent conductivity,
  Like: 
A- Carbon
  and Salt Bedding  
Depending on the technical design specification
  of the earthing system and primarily for soil conductivity reasons of the
  area where the earth wells are to be installed, the earth rods are embedded
  in carbon bedding. To install the carbon bedded earth wells, pre-excavation
  of the ground, to sufficient size and dimension, would be carried out to
  provide room for the carbon bedding and the earthing components (rods,
  plates, etc.). To achieve the maximum conductivity for the earth well, an
  appropriate amount of salt is added to the carbon and mixed before charging
  into the earth well. 
B- Marconite Compound 
Marconite forms a permanent
  solution when mixed with cement and is used when certain ground conditions
  make it difficult to obtain a reliable earth resistance or installation might
  require a low resistance. 
C- Bentonite Compound: 
Bentonite can be supplied in powder
  or granular form and is a moisture retaining clay which is used to reduce
  soil resistivity. It has two types: 
1- Granular: 
It’s easier to handle in granular
  form, the powder can cause dust in windy conditions and below away, granular
  is the preferred option for filling trenches where the conductor is covered
  with bentonite and the water poured over and mixed in the trench. 
2- Powder 
Powder is the preferred method for
  pouring into bore holes to ensure the mixture is a thin enough to reach the
  bottom of the bore hole, if diamond drilling is required for deep holes
  possibly 40 meters and deeper and the bentonite is to be pumped through the
  core into the hole, powder will be the preferred option. 
The above image clearly shows, GEM has a resistivity factor more than 20 times lower than
  bentonite clay. 
3- How to Specify GEM? 
 
Note: 
 
4- GEM Installation 
GEM is supplied in
  easy-to-handle bags for one-man installation. GEM can be installed dry or wet
  (recommended). GEM quickly absorbs moisture from the soil when used dry, to
  reach its maximum conductivity in days. To accelerate curing time, water can
  be added after GEM is installed, or it can be pre-mixed with water. 
A- Trench Installation 
 
B- Ground Rod Backfill Installation 
 
Notes:  
  | 
 
Enhanced Ground Rod 
 
 
 
 
  | 
 
In the next Article, I will continue explaining the Earthing Systems Components. Please, keep following.