What is “Grounded Conductor”?
- A grounded conductor is the
conductor of an electrical system that is intentionally connected to earth
via a grounding electrode conductor and a grounding electrode at the service
of premises, at a transformer secondary, or at a generator or other source of
electric power. It is most commonly a neutral conductor of a single-phase,
3-wire system or 3-phase, 4-wire system but may be one of the phase legs—as
in the case of a corner-grounded delta system.
- A “grounded conductor” carries current during
“normal” operations of the power distribution system.
- (The “grounded conductor” is commonly referred to as the neutral
conductor.)
Grounded conductor in
different system types:
- In 3-wire, single-phase systems (see fig.1) the
midpoint of the transformer Winding, the point from which the system neutral
is derived, is grounded.
|
Fig (1): 3-wire, single-phase systems
|
- For grounded 3-phase, 4-wire wiring systems (see
fig.2) the neutral point of the wye-connected transformer(s) or
generator is usually the point connected to ground.
|
Fig (2): grounded 3-phase, 4-wire wiring systems
|
- In delta-connected transformer hookups (see
fig.3) grounding of the system can be effected by grounding one of the
three phase legs, by grounding a center-tap point on one of the transformer
windings (as in the 3-phase, 4-wire “red-leg” delta system), or by using a
special grounding transformer which establishes a neutral point of a
wye-connection which is grounded.
|
Fig (3): delta-connected transformer hookups
|
The need for a grounded conductor:
- It limits the voltage upon
the circuit that might otherwise occur through exposure to lightning or other
voltages higher than that for which the circuit is designed.
- It limits the maximum voltage
to ground under normal operating conditions.
- It provides automatic opening
procedure of the circuit if an accidental or fault ground occurs on one of
its ungrounded conductors.
|
Very Nice..
ReplyDelete