In course " EE-1: Beginners' Electrical design course " which is a preparation for beginners in electrical design, I explained the Electrical design philosophy for all building types and indicated the different types of buildings according to usage which were:
- Industrial buildings
 - Commercial buildings
 - Residential buildings
 - Agricultural buildings
 - Educational buildings
 - Transportation buildings
 - Religious buildings
 - Parking and storage
 - Military buildings
 - Governmental buildings
 - Cultural buildings
 - Other buildings
 
In the current course" EE-3: Basic Electrical design course – Level II ", in Sixteen Articles, I explained the design of the Dwelling type buildings; I explained Where and how to distribute each type of load in a dwelling unit as per NEC code and how to calculate its Demand load for feeder and service sizing calculations, and finally I summarize the steps of calculating electrical load for any dwelling unit as per NEC standard & Optional Calculation methods in two Excel sheets/calculator.
These Sixteen Articles for the electrical design of dwelling buildings are as follows:
- Branch Circuit Design Calculations – Part One
 - Branch Circuit Design Calculations – Part Two
 - Branch Circuit Design Calculations – Part Three
 - Receptacle Branch Circuit Design Calculations – Part One
 - Receptacle Branch Circuit Design Calculations – Part Two
 - Receptacle Branch Circuit Design Calculations – Part Three
 - Receptacle Branch Circuit Design Calculations – Part Four
 - Receptacle Branch Circuit Design Calculations – Part Five
 - Receptacle Branch Circuit Design Calculations – Part Six
 - Receptacle Branch Circuit Design Calculations – Part Seven
 - Branch Circuit Design Calculations – Part Eight
 - Branch Circuit Design Calculations – Part Nine
 - Branch Circuit Design Calculations – Part Ten
 - Branch Circuit Design Calculations – Part Eleven
 - Electrical Load Calculator for Dwelling Units
 - Optional Electrical Load Calculator for Dwelling Units
 
Today, I will begin explaining the electrical design of Non-Dwelling Buildings as per NEC Code.
List of ordinary Non-Dwelling Buildings Loads:
Most of Non-Dwelling Buildings will have the following types of loads:
- Lighting loads,
 - Receptacles Loads,
 - Kitchen Loads,
 - Heating, Ventilation and air conditioning Loads (Non-Coincident Loads),
 - Motor Loads,
 - Other Loads.
 
Again, but for above Non-Dwelling Buildings Loads, I will explain the following points:
- Where and how to distribute each type of load in a dwelling unit as per NEC code?
 
- How to calculate its Demand load for feeder and service sizing calculations?
 
| 
   
Important!!! 
All design Calculations for Non-dwelling Buildings will be as per NEC standard calculation method but I will explain design calculations as per NEC Optional calculation method only for the following Non-Dwelling buildings as permitted by NEC, Part IV. Optional Feeder and Service Load Calculations: 
  | 
 
First: Lighting Loads
1- Lighting branch circuit ratings in non-dwelling units
Lighting branch circuit ratings in non-dwelling units may have one of the following ratings according to the type and application used as follows:
a) 15- and 20-Ampere Branch Circuits
It shall be permitted to supply lighting units or other utilization equipment, or a combination of both.
b) 30-Ampere Branch Circuits
It shall be permitted to supply fixed lighting units with heavy-duty lampholders.
c) 40- and 50-Ampere Branch Circuits
It shall be permitted to supply fixed lighting units with heavy-duty lampholders.
2- Lighting load Calculations
In the broad sense, lighting loads for Non-Dwelling buildings may be categorized as follows:
- General lighting.
 - Show-window lighting.
 - Track lighting.
 - Sign and outline lighting.
 - Other lighting.
 
2.1 General lighting
| 
   
Definition: 
General lighting outlets are those Outlets intended for
  general use for fixed-in-place luminaires (lighting fixtures). They are only
  used for lighting for the normal use of the occupants and Its
  intensity should be adequate for any type of work performed in the area. 
 | 
 
| 
   
Important!!! 
The following Lighting fixtures are not included in General
  Lighting category: 
  | 
 
2.1.a Calculation Method
Determining the general lighting load as per NEC will be based on the load per area method as follows:
Step#1: determine the general lighting load density (in VA/ft2) for the building occupancy under design.
| 
   
Rule#1: Applying
  Table 220.12 
The NEC code
  introduces minimum general lighting loads (in VA/ft2) for various types
  of buildings in Table 220.12. 
Within the same
  building, there are normally several different types of areas like storage,
  office, hallways, and cafeterias, these areas must be considered separately
  if their (VA/ft2) values are available in table 220.12. 
 | 
 
Step#2: calculate the floor area in (ft2)
| 
   
Rule#2: Applying
  Table 220.12 
The
  floor area for each floor shall be calculated from the outside dimensions of
  the building, or
  other area involved.  
The calculated floor area shall not include open porches,
  garages, or unused or unfinished spaces not
  adaptable for future use (like some attics, cellars, and crawl spaces). 
 | 
 
Step#3: calculate the general lighting load
The general lighting load is calculated by multiplying the floor area in (ft2) of a building by its unit load (in VA/ft2) derived from table 220.12.
General lighting load in (VA) = Area of Occupancy in (ft2) X general lighting load density in (VA/ft2)
Step#4: Apply lighting demand factor from table 220.42 for type of building under design.
| 
   
Important!!! 
The demand factors of table 220.42
  shall
  not apply to the calculated load of feeders or services supplying areas in
  hospitals, hotels, and motels where the entire lighting is likely to be
  used at one time, as in operating rooms, ballrooms, or dining rooms. 
 | 
 
| 
   
Important!!! 
For
  the purpose of determining the circuit requirements, If the General Lighting
  load is continuous (as in Most commercial structures), the calculated load is
  multiplied by 1.25 (the inverse of 80%).  
 | 
 
| 
   
Rule#3: Calculating
  Lighting Outlets load for
  heavy-duty Lampholders   
As per NEC section 210.21, If there is Lighting
  Outlets for heavy-duty Lampholders in the Non-Dwelling Building, It shall be
  calculated at a minimum of 600 volt-amperes. 
 | 
 
Example#1:
A 25,000 ft2 office building is being designed. What is the general lighting load and what load does the circuit need to supply?
Solution:
From Table 220.12, the unit load for an office building is 3.5 VA/ft2.
The general lighting load is determined by multiplying this value by the square footage of the building:
3.5 VA/ft2 x 25,000 ft2 = 87,500 VA
So, the general lighting load is 87,500 volt-amperes.
However, the load is continuous and can only be 80% of the load supplied by the circuit. This value must be multiplied by 1.25 to determine the circuit requirements:
87,500 VA x 1.25 = 109,375 VA
The circuit is designed to supply 109.375 KVA
Notes for table 220.12
| 
   
Important!!! 
Don’t
  apply the values of table 220.12 before reviewing the following notes: 
  | 
 
| 
   
Important!!! 
The
  general lighting load unit values specified in table 220.12 for guest rooms or guest
  suites of hotels and motels
  includes the following loads: 
 
So,
  no need to add the above outlets in load calculations per NEC method. 
 | 
 
| 
   
Important!!! 
The
  NEC method and table 220.12 are applied for any Additions to Existing
  Installations for non-dwelling installations. 
 | 
 
| 
   
Important!!! 
Energy
  saving–type calculations (which used to reduce the connected lighting load
  and actual power consumption) are not permitted to be used to determine the
  minimum calculated lighting load if they produce loads less than the load
  calculated according to 220.12. 
 | 
 
2.1.b Notes for NEC method for calculation of lighting branch circuit load
| 
   
Important!!! 
The
  NEC doesn’t introduce a procedure for calculating the actual full load for
  the individual lighting fixtures in a general lighting branch circuit. 
 | 
 
| 
   
Rule#4: NEC method for calculation of lighting
  branch circuit load  
If the required
  information for calculating the actual full load for every individual
  lighting fixture in the circuit is available, the following procedure will be
  applied: 
  | 
 
| 
   
Important!!! 
Actually,
  The NEC method for calculation of lighting load is not required if the actual
  full load for every individual lighting fixture in the circuit is determined. 
Methods
  for determining the actual full load for every individual lighting fixture in
  the circuit is explained in our course and I recommend reviewing these
  methods very well. 
 | 
 
| 
   
Rule#5: determining the actual load current of circuits
  supplying lighting units that have ballasts, transformers, autotransformers, or
  LED drivers 
As per NEC Section
  220.18 (b) states , circuits supplying lighting units that have ballasts,
  transformers, autotransformers, or LED drivers, the calculated load shall be
  based on the total ampere ratings of such units and not on the total watts of
  the lamps. 
This means that the
  losses in light fixture switchgear (ballast, internal wiring, etc.) must be
  taken into account when calculating the actual full load of light fixtures
  and the current rating of the ballast, not the tube wattage, will be used. 
 | 
 
Example#2:
A fluorescent lighting fixtures with 4 numbers 2 feet lamps, 18 watt/ lamp. Calculate the actual load for this lighting fixture.
Solution:
The actual total load of fixture = 4 lamps x 18 watt/lamp + losses
So, we can’t know the actual losses, we will use the same equation in another form
The actual total load of fixture = 4 ballast x watt/ballast = 4 x 20 w = 80 watt
2.2 Show-window lighting
The calculation of this type of lighting is explained in Article " Branch Circuit Design Calculations – Part Four ".
2.3 Track lighting
The calculation of this type of lighting is explained in Article " Branch Circuit Design Calculations – Part Four ".
2.4 Sign and outline lighting
The calculation of this type of lighting is explained in Article " Branch Circuit Design Calculations – Part Five ".
2.5 Other lighting
Other lighting includes but not limited to the following:
- Security lighting,
 - Parking area lighting,
 - Sidewalk lighting,
 - Roadway lighting,
 - Stadium lighting,
 - Tunnel Lighting.
 
2.5.a Rules applied for Calculation of Other lighting loads
Unfortunately, The NEC code don’t provide calculation rules for lighting types included under these additional lighting loads.
So, all additional lighting loads are calculated using the actual load designed by professional lighting programs and methods as explained in our course.
| 
   
Important!!! 
All
  Additional
  lighting loads should be computed separately from the general lighting load
  and then added to the general lighting load.  
 | 
 
| 
   
Don’t
  forget… 
These additional
  lighting loads are considered continuous loads where appropriate
  and must be multiplied by 1.25 for feeder and overcurrent protection
  calculations. 
 | 
 
| 
   
Rule#6: Calculating
  the total lighting load for
  buildings having more than one lighting category. 
lighting loads for Non-Dwelling buildings may be
  categorized as follows: 
 
If more than one of the above lighting categories is
  existing in the same building, Each lighting Category load is computed
  separately and then combined to other lighting categories load to determine
  the total lighting load. 
 | 
 
In the next article, I will explain design calculations for Receptacle Loads for Non-Dwelling Buildings. Please, keep following.


No comments:
Post a Comment