In the previous article " Receptacle Branch Circuit Design Calculations – Part Four ", I explained General-use Receptacle branch circuits.
Also, in previous article " Receptacle Branch Circuit Design Calculations – Part Three ", I stated that a Receptacle in dwelling units may serve one of the following loads:
- General-use Receptacle Loads,
- Small appliance Loads,
- Laundry Load,
- Fastened-in-place Appliance loads,
- Cloth dryer Load,
- Household cooking appliances load,
- Heating and air conditioning loads,
- Motor loads.
In the following paragraphs, I will explain Where and how to distribute each load outlets in a dwelling building as per NEC code.
You can review the following previous articles for more information:
2- Small Appliances Branch circuits
2.1 Applied NEC Rules for small appliances branch circuits:
There are many NEC rules that control the number, location and type of small appliances branch circuits including:
- 210.8 A(6) Ground-Fault Circuit-Interrupter Protection for Personnel in Kitchens,
- 210.11(C)(1) Required Branch Circuits in Dwelling Units for Small-Appliance Branch Circuits,
- 210.52(A)(4) Dwelling Unit Receptacle Outlets for Countertop Receptacles,
- 210.52(B) Dwelling Unit Receptacle Outlets for Small Appliances,
- 210.52(C) Dwelling Unit Receptacle Outlets for Countertops,
- 220.52 (A) Small-Appliance Circuit Load in Dwelling Unit.
2.2 Rules controlling small appliances Branch Circuits:
Rule#1: number of small appliance branch circuits
In each dwelling unit, two or more 20-ampere small-appliance branch
circuits shall be provided.
|
Rule#2: areas served by small appliances branch circuits
All Receptacle Outlets In the kitchen, pantry, breakfast room, dining
room, or similar area of a dwelling unit which serve Portable appliances used
at a kitchen counter, such as toasters, coffee makers, skillets, mixers, and
the like and after applying exceptions made by rules#6.
|
Rule#3: Receptacle Outlets served by small appliances branch
circuits (see fig.1)
The following receptacle outlets are permitted to be served by small
appliance branch circuits:
The small appliance branch circuits are not permitted to serve any
other outlets, such as might be connected to exhaust hoods or fans,
disposals, or dishwashers.
|
Rule#4: Receptacle outlet for refrigeration equipment
The receptacle outlet for refrigeration equipment located in a kitchen
or similar area shall be permitted to be supplied from one of the following
circuits:
|
Fig.1 |
Rule# 5: Distribution of small-appliance branch circuits
Small-appliance branch circuits must supply the required receptacles by
rule#3 in the following way:
|
Rule#6: floor Receptacles
Receptacle outlets in floors shall not be counted as part of the
required number of general-purpose receptacle outlets unless located within
450 mm (18 in.) of the wall. Otherwise, these Floor Receptacles will be
counted as part of the small appliance branch circuits.
|
Rule#7: kitchen and dining areas counters receptacles other than
that used for small appliances
Receptacle outlets installed to serve kitchen or dining area counters
(for small appliances) cannot also be used as general-use receptacles for an
adjacent wall space and in this case general-use receptacle branch circuits
must be added to serve such locations.
|
Rule#8:general-purpose Switched receptacles
Switched receptacles supplied from general-purpose 15-ampere branch
circuits are permitted to be located in kitchens, pantries, breakfast rooms,
and similar areas.
|
2.3 rules controlling distribution of receptacle outlets of countertop spaces
Countertops may be found In kitchens, pantries, breakfast rooms, dining rooms, and similar areas of dwelling units, these countertops have receptacle outlets which will be distributed in the countertop space as per the following rules:
Rule#9: spacing of Countertop receptacles
A receptacle outlet shall be installed at each wall countertop space
that is 300 mm (12 in.) or wider And spaced so that no point along the wall
line is more than 600 mm (24 in.) measured horizontally from adjacent
receptacle outlet in that space.
|
|
Rule#10: a sink, range, or counter-mounted cooking unit
installed in Countertop
Receptacle outlets shall not be required on a countertop wall directly
behind a range, counter-mounted cooking unit, or sink.
|
|
Rule#11: dividing a Countertop
If the space depth behind a sink, range, or counter-mounted cooking
unit is 12 in. or more or 18 in. or more (depending on the counter configuration),
the countertop is still one space, and in this case the wall length behind a
sink, range, or counter-mounted cooking unit must be included in measuring
the total wall counter space to calculate the number of required
Receptacle(s) for this countertop.
But if the space depth behind a sink, range, or counter-mounted cooking
unit is less than 300 mm (12 in.), countertop will be considered as two
separate standalone countertops and rules #1 will be applied for each
separate countertop.
|
Important!!!
Rule#11
will apply for island and peninsular countertop (see fig.4) with a short dimension of at
least 12 in. and a long dimension of at least 24 in. Noting that the measurement of a
peninsular- type countertop is from the edge connecting to the non-peninsular
counter.
Peninsular countertop definition: kitchen
is simply an island anchored to a wall or line of cabinets. It may be used as
a breakfast bar, seating area or just extra countertop and storage space.
|
Fig.4 |
Rule#12: Receptacle locations on or above Countertop
Receptacle outlets shall be located on or above, but not more than 500
mm (20 in.) above, the countertop.
|
Rule#13: Receptacle locations below Countertop
Receptacle outlets shall be permitted to be mounted not more than 300
mm (12 in.) below the countertop with the following conditions:
|
Important!!!
Multi-outlet
assemblies (see fig.5) shall be permitted to be to be used as the required countertop
receptacle outlet(s) and it will be installed as one of the following ways:
|
Fig.5 |
Rule#14: Guest Rooms and
Guest Suites in dwelling units and that are provided with permanent provisions
for cooking (see fig.6)
Guest rooms and guest suites that are provided
with permanent provisions for cooking shall have branch circuits installed in
the cooking area to meet the above rules#1 to #13.
|
2.4 Calculation of general-use receptacles load
A- For feeder and service calculation purposes:
As per NEC section 220.52(A), in each dwelling unit, the load shall be calculated at 1500 volt-amperes for each 2-wire small-appliance branch circuit. this load will be added for other loads to perform the feeder and service calculations.
B- For branch circuit requirements (conductor ampacity & size and over-current protection) calculation
This will be explained in coming articles, however you can review the calculation for maximum number of allowable receptacles on a branch circuit which was discussed before in previous article " Receptacle Branch Circuit Design Calculations – Part Three ".
2.5 How to specify the required Type of receptacles for small appliances branch circuits?
1- GFCI Type
As per NEC section 210.8 A (6), where the receptacles are installed to serve the countertop kitchen appliances around a kitchen sink must be GFCI Type. See fig.7.
Fig.7 |
Important!!!
I explained in rule#5 in previous article “Receptacle Branch Circuit
Design Calculations – Part Five“ that a general-use receptacle branch
circuits must be added to kitchens to serve Receptacles installed for
disposals, dishwashers, and trash compactors. These receptacles are not
required to be GFCI type. The same is for receptacle(s) installed behind a
refrigerator to supply that appliance, not the countertop, and will not be GFCI
type.
|
Important!!!
According to 406.5(E), receptacles installed to serve
countertops cannot be installed in the countertop in the face-up position
because liquid, dirt, and other foreign material can enter the receptacle.
|
2- Tamper-Resistant type
Tamper-Resistant receptacles are intended to increase safety for children. All non-locking type 125- volt, 15- and 20-ampere receptacles shall be listed tamper resistant receptacles. The Receptacles in the following locations shall not be required to be tamper-resistant:
- Receptacles located more than 1.7 m (51⁄2 ft) above the floor (these receptacles are not accessible and well out of reach of small children).
- Receptacles that are part of a luminaire or appliance.
- A single receptacle or a duplex receptacle located within dedicated space for appliance that, in normal use, is not easily moved from one place to another ( like dishwashers, refrigerators, washing machines, and the like )
In the next article, I will explain Receptacle branch circuits that serve other types of loads. Please, keep following.
No comments:
Post a Comment