Today, we will explain the following:
- Basic Elements of Electrical Drawings,
- Types of Electrical Drawings,
- Single-Line /One-Line Diagram - Part one.
|
8- Basic
Elements of Electrical Drawings
|
|
An electrical drawing is a type of
technical drawing that shows information about power, lighting, and
communication for an engineering or architectural project.
Any engineering
drawing consists of (6) basic elements (see above figure) as follows:
Field of the drawing: it is the main body or main area of the drawing, excluding the title block,
rev block, and other drawing elements.
For reviewing each drawing element in above
please click its name to open the link or review our course “ED-1: Electrical Drawings Course”
for more information.
|
|
9- Types
of Electrical Drawings
|
|
The electrical drawings can be categorized to many types according to
the following:
Note:
All types of electrical drawings are two dimensional drawings, the
three dimensional drawings (like the isometric drawings) are not common for
using as electrical drawings.
|
|
First: According To the Stage of Project
There are
many types of drawings that you will deal with during any project life as
follows:
For reviewing each Electrical drawing type
as per the stage of project in above please click its name to open the link
or review our course “ED-1: Electrical Drawings Course” for more information.
Also, in course “ED-1: Electrical Drawings Course”, You can
review the following articles about the electrical shop drawings:
|
|
Second:
According To the Drawing Purpose
There are many types of electrical drawings which range
from the very simple to the very complex. Each of these electrical drawings
has a specific purpose and distinguishing features that set it apart from the
others.
You should be able to recognize the relationship between these various types,
their distinguishing
features, and the purpose of each type of drawings.
Electrical drawings as per their purposes usually divide to main types as
follows:
|
|
1- Electrical Diagrams
Diagrams show the electrical path, device wiring, and sequence of
operation, device relationship, or connections and hookups of the electrical
installation.
Electrical
diagrams include the following sub-types:
Electrical
symbol is a small picture or image called a pictogram
used to represent
|
|
2- Electrical
Layouts (plans)
The electrical layout/plan determine where each electrical device and
piece of equipment is to be located related to the architectural features of
the area. It shows where and how the conductors/conduits are to run. It helps
locate the incoming service. Electrical plans are also used for estimating
installation and material costs. By examining a plan, you can take off, that
is, count, the number of switches, outlets, fixtures, feet of wire, etc.,
that may be required for a particular job.
Electrical
layouts include:
|
|
3- Electrical
Schedules
|
|
1- Electrical
Diagrams
|
|
1- Single-Line
/One-Line Diagram
|
|
A- Characteristics of Single-Line Diagram
The below Figure shows an example of a
single-line diagram.
Note:
|
|
B- Purposes of Single-Line Diagram
A single-line
diagram has multiple uses in the following
cases:
1- Power System Studies
2- Operations and Maintenance
3- Construction
|
C- Arrangement of Components on Single-line Diagrams
|
|
D- Interpreting Single-Line
Diagrams
The interpretation of single-line diagrams
is explained in this section under the following major subject headings:
|
|
D.1- Informational Elements
The following informational elements of a single-line
diagram are explained in this section:
|
|
D.1.1 Point of Connection to
the Utility Company
Information needed from the Utility Company:
|
|
D.1.2 Identification of buses,
substations, generators, motors
and other equipment
|
D.1.3 Ring Main Units data
Function:
The RMU is a
compact unit combining all MV functional units to enable connection, supply
and protection of one or two transformers on an open ring or radial network
by one of the following methods:
Overview of RMUs1- In an electrical power distribution system, a ring main unit (RMU) is a factory assembled, metal enclosed set of switchgear used at the load connection points of a ring-type distribution network. This type of switchgear is used for medium-voltage power distribution, from 7200 volts to about 36000 volts. 2- Ring main units can be characterized by their type of insulation, air, oil or gas. It includes in one unit two load break switches that can connect the load to either or both main conductors, and it includes a fusible switch or circuit breaker that feed a distribution transformer. The metal enclosed unit connects to the transformer either through a bus throat of standardized dimensions, or else through cables and is usually installed outdoors. Ring main cables enter and leave the cabinet from bottom. 3- The switch used to isolate the transformer can be a fusible switch, or may be a circuit breaker using vacuum or gas-insulated interrupters. In case a circuit breaker is the switching device, it is also equipped with protective relaying, either with a very basic self-powered type or a more advanced one with communication capabilities.
4- All of the switching devices are of
three-position design, having the possibility to close or open or earth the
feeder in question.
There are many combinations of RMUs as shown in below figure:
The
impotent data need for specifying the RMUs are:
|
In the next article, we will continue explaining
the Interpreting Single-Line Diagrams. So, please keep following.
The
previous and related articles are listed in the below table:
|
Subject
of Previous Article
|
Article
|
|
1- Overview for the articles/courses that give a preliminary explanation for the different Types of
Electrical drawings.
2-
Electrical Drawings Glossary.
|
|
|
3- Resources used to Read and Interpret Electrical Drawings.
|
|
|
4-
Electrical Symbols and Abbreviations
5-
Electrical Abbreviations
6- Device
Function Numbers
7-
Drafting Practices Using Graphical Symbols and abbreviations
|
|
|