Today, we will explain Rules Of Thumb for Generators Sizing Calculations for Existing and New Installations.
Fifth: Rules Of
  Thumb For Generators Sizing Calculations 
 | 
 
First:
  Rules Of Thumb For Existing
  Installations 
 | 
 
In article “Generators
  Sizing Calculations – Part Twelve”,  We explain how to
  calculate the peak load of an existing installation by one of the following
  methods: 
 
Then we can size the generator(s) of an
  existing installation based on the calculated/estimated peak load and based
  on the next steps explained in the following articles: 
Also, We can size the generator(s) of an
  existing installation for each of the above methods by using Rules Of Thumb as
  will be explained in below. 
 | 
 
1- Measurement Method 
Use
  a clamp-on Amp meter or power analyzer to measure facility load levels. Clamp
  each leg separately and take the measurement during peak usage levels. 
1.A-
  For 240V 1ø Applications:  
To
  determine peak usage in kW, add the highest Amp readings from the two legs
  then multiply by 120 and divide by 1,000. 
 
1.B-
  For 3ø Applications:  
Add
  the peak Amp readings from all three legs and divide by 3 to determine peak
  Amps. Multiply peak Amps by volts, multiply the result by 1.732 (square root
  of 3), then divide by 1000 to convert Amps to kW. 
  | 
 
2- Billing History Method 
Many
  commercial
  customers
  have a utility rate structure that has a peak demand charge. Using a year's
  worth of electric bills, find the Peak Demand. Then Verify motor and UPS load
  compatibility.  
Step#1:
  Peak
  Demand = largest peak demand from Billing History 
Step#2-
  Rules Of Thumb: Size the generator 25% larger than the largest peak
  demand 
 | 
 
3- Load Summation Method 
Step#1:
  Enter
  running kW for all motor loads (except the largest) expected to run during
  peak load levels into Table-3. Refer to Table-1 for typical motor load sizes and electrical requirements. 
 
Notes: 
For
  HP < 7.5; starting kW = HP x 3 
For
  HP > 7.5; starting kW = HP x 2 
Starting
  kW for loads with no listed HP; calculate HP based on running amps in Table-4
  below. 
 
Step#2:
  Enter
  kW for all non-motor loads expected to run during peak load levels into Table-5.
  Refer to Table-2 for typical residential loads and rules of thumb. 
 
Step#3:
  Add
  the running motor load kW, non-motor load kW, and the starting kW of the largest
  motor load. 
From
  Table-3, the Motor load running total - minus largest motor = X kW  
From
  Table-5, Non-motor load total = Y kW  
From
  Table-3, Starting load from largest cycling motor = Z kW  
Total
  electrical loads = X+Y+Z kW 
Step#4-
  Rules Of Thumb: Select generator:  
Commercial
  (add 20 to 25% to Total electrical loads kW)  
Residential
  (add 10 to 20% to Total electrical loads kW) 
Step#5-
  Rules Of Thumb: Select
  Generator Rating from Standard Sizes/Manufacturers Catalogs 
Step#6-
  Rules Of Thumb: Confirm that voltage dip is within acceptable limits by
  comparing motor LRA to generator surge capability (see Table-3). If
  not, select the next higher standard generator size. 
Step#7-
  Rules Of Thumb: Confirm UPS compatibility according to UPS type as in Table-7
  in below. 
 
Table-7: UPS compatibility according to UPS type 
If
  UPS compatibility not verified, select the next higher standard generator
  size. 
You
  can know the UPS type, if you know the supplier name from the below table: 
 
Note:
  Ferrups and Delta-Conversion UPS technologies not included in discussion 
 | 
 |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
4-
  NEC Load Calculation Methods 
No
  Rules Of Thumbs will be used just follow the NEC rules explained in article “Generators
  Sizing Calculations – Part Twelve”. 
 | 
 
5-
  Load Estimation Method  
Step#1- Rules of Thumbs: Calculate the square footage of the building. (For typical
  floors multiply the square footage of one floor by number of typical floors). 
Step#2- Rules of Thumbs: Calculate the estimated KW by multiply the total square
  footage of the building by the application factor indicated in below table. 
 
 
Step#3-
  Rules Of Thumb: Select
  Generator Rating from Standard Sizes/Manufacturers Catalogs. 
 | 
 |||||||||||||||||||||||||||||
Second:
  Rules Of Thumb For New Constructions 
 | 
 
We have two methods as Rules Of Thumb for generator sizing in New Constructions as follows: 
  | 
 
1- By Using Conservative
  Rules Of Thumb 
Here are some
  conservative rules of thumb for generator sizing include: 
 
The steps of
  generator sizing by this method will include the following steps: 
 
Example#1: 
Size the
  generator to supply the following loads: 
 
The system
  voltage is 480 V and PF is 0.77. 
Solution: 
Step#1:
  Calculate Running Amperes 
 
Step#2:
  Calculating Starting Amperes Using 1.25 Multiplier 
 
Step
  3: Selecting kVA of Generator 
  | 
 ||||||||||||||||||||||||||||||||||||||||||||||||||||||
2- By Using the Load Form
The load
  form is prepared by the generator manufactures to help and facilitate the
  process of generator sizing. A copy of the load form is in below image. 
The steps of
  generator sizing by using the load form will include
  the following steps: 
Step#1: Write down all resistive loads on column 12
  and 13, KW = KVA so entries are the same on the rows of resistive loads.
Note: Resistive
  loads consist of incandescent lights, water heaters, electric heaters,
  stoves, and electric furnaces. Power factor = 1, KW = KVA. Running and
  starting KW are the same. 
Step#2: List all
  motor loads with the worst case (largest load applied last) in order on the
  load form. 
Note: Motors
  are inductive loads with KVA always larger than KW. The power factor running
  usually is between 0.6 and 0.85. 
Step#3: List the
  following items for each motor load (If the motor is existing, use nameplate
  data. If this is a new installation, use Table-2):  
 
Special cases for step#3: 
A- Only locked rotor amps are
  known: 
To find starting KVA if only locked rotor amps are known;  
 
B- For submersible water pumps only: 
Submersible water pump motors have a higher
normal locked rotor code letter and running current than Onan tables shown
  for average motors. The running current is higher than NEC 430-148 when run
  at their service factor amps. Use the following two tables: 
Step#4: calculate the values of columns 10, 11, 12 & 13 as follows: 
 
Step#5: Look at the largest numbers in columns
  10, 11, 12 and 13. Generator output must be greater than these numbers.  
Note: 
These calculations do not take into account voltage drop on
  generator. Consult manufacturer at this point.  
Example#2: 
For the following Loads, calculate the
  suitable generator size. 
 
Assume resistance loads are balanced. 
Solution: 
Step#1: Write down all resistive loads on column 12
  and 13, KW = KVA so entries are the same on the rows of resistive loads.
Step#2: List all
  motor loads with the worst case (largest load applied last) in order on the
  load form,  
Step#3: List the
  following items for each motor load (use Table-2):  
 
Step#4: calculate the values of columns 10, 11, 12 & 13 
 
Step#5: Look at the largest numbers in columns
  10, 11, 12 and 13. Generator output must be greater than these numbers.  
 
In this case, a 20 KW generator would handle the continuous KVA
  and KW, and maximum KVA and KW.  
We can use for example, Onan generator 20ES which has the
  following ratings: 
  | 
 
In the next article, we will explain the special
cases for Generators Sizing Calculations. So, please keep following.
The previous and
related articles are listed in the below table:
Subject
  of Previous Article 
 | 
  
Article 
 | 
 
Glossary of Generators – Part One 
 | 
  |
Glossary of Generators – Part Two 
 | 
  |
First:
  Reasons for having on-site generators 
Second: Applicable performance standards for generator sets Third: Selection Factors Used For Generators Sizing Calculations 
  | 
  |
Third: Selection Factors Used For Generators Sizing
  Calculations 
3- Location Considerations, 4- Fuel Selection Considerations, 5- Site Considerations,  | 
  |
Third: Selection Factors Used For Generators Sizing
  Calculations 
6- Environmental Considerations, 7- System Voltage and Phase,  | 
  
 | 
 
Third: Selection Factors Used For Generators Sizing
  Calculations 
8- Acceptable percent of voltage & frequency dip, 9- Acceptable duration of the voltage & frequency dip,  | 
  |
Third: Selection Factors Used For Generators Sizing
  Calculations 
10- Percent And Type Of Loads To Be Connected – Part One  | 
  |
10- Percent And Type Of Loads To Be Connected – Part
  Two 
 | 
  
 | 
 
Third: Selection Factors Used For Generators Sizing Calculations 
11-
  Load
  step sequencing 
12-
  Future needs 
 | 
  |
Fourth: Applicable
  Procedures For Generators Sizing Calculations 
1.1- Generator Load Factor 
1.2- Load Demand Factor 
1.3- Load Diversity Factor 
 | 
  |
Fourth:
  Applicable Procedures For
  Generators Sizing Calculations 
Step#1:
  Determine the Required Generator(S) Set Rating, 
Step#2:
  Assign the System Voltage and Phase, 
Step#3: Segregate the Loads  
Step#4:
  Match
  the System to the Load Profile, Calculate the Required Number of Generator Sets and
  Paralleling Requirement, 
 | 
  |
Fourth: Applicable
  Procedures For Generators Sizing Calculations 
Step#5-Existing Installations: Calculate
  the peak load of the installation  
Step#5-New Constructions: Calculate Connected Loads to Generator 
Step#6- Existing Installations: Check for
  transients or harmonics by using power analyzers and de-rate the
  peak load value. 
Step#6-New Constructions: Calculate Effective Load to Generator, 
 | 
  |
Fourth:
  Applicable Procedures For
  Generators Sizing Calculations 
Step#7: Adjust the Generator Rating According To Transient Voltage Dip, 
Step#8:
  Adjust the Generator Rating According To Site Conditions, 
Step#9:
  Adjust the Generator Rating According To Fuel Type, 
Step#10:
  Adjust the Generator Rating According To Future Needs, 
Step#11:
  Adjust the Generator Rating According To Power Factor, 
Step#12: Calculate the Adjusted Generator Rating, 
Step#13:
  Select Generator Rating from
  Standard Sizes/Manufacturers Catalogs, 
Step#14:
  Assign Required Number Of
  Steps/Starting Sequence. 
 | 
  