Subject of Previous Article
|
Article
|
Glossary of Generators – Part One
|
|
Glossary of Generators – Part Two
|
|
First: Reasons for having on-site generators
Second: Applicable performance standards for generator sets
Third: Selection Factors Used For Generators Sizing Calculations
- Generator Power Ratings
- Application type
|
|
Third:
Selection Factors Used For Generators Sizing Calculations
3- Location
Considerations,
4-
Fuel Selection Considerations,
5-
Site Considerations,
|
|
Today, we will continue explaining other Selection factors used for Generators Sizing Calculations.
Third: Selection Factors Used For Generators
Sizing Calculations
|
Here
we will describe preliminary factors for selecting a generator for certain
project, which will be as follows:
Generator Power Ratings,
Application type,
Location Considerations,
Fuel Selection Considerations,
Site Considerations,
Environmental Considerations,
System Voltage and Phase,
Acceptable percent of voltage & frequency dip,
Acceptable duration of the voltage & frequency dip,
Percent and type of loads to be connected,
Load step sequencing,
Future needs.
|
6- Environmental
Considerations
|
The
Environmental Considerations that must be taken into
consideration when selecting a generator for an application are:
Noise Levels,
Engine Exhaust Emissions Regulations,
Fuel Storage Regulations.
|
1- Noise Levels
Effective noise treatment has to address all of these sources of noise. For the most part, the recommended noise treatment methods modify or redirect the path for the noise from the generator set source to people hearing it. Simply using a critical grade muffler may or may not do anything to reduce the noise level at a specific location. Because noise is directional, careful consideration needs to be given to the location, orientation, and distance of the generator set with respect to property lines or places where the noise may be objectionable.
In North America, state and local codes establish maximum noise levels for given areas.
Noise Zones
|
Peak
Daytime
Db(A)
|
Peak
Nighttime
Db(A)
|
Continuous
Daytime
Db(A)
|
Continuous
Nighttime
Db(A)
|
Urban—Residential
|
62
|
52
|
57
|
47
|
Suburban—Residential
|
57
|
47
|
52
|
42
|
Very Quiet Suburban
or Rural Residential
|
52
|
42
|
47
|
37
|
Urban—Nearby Industry
|
67
|
57
|
62
|
52
|
Heavy Industry
|
72
|
62
|
67
|
57
|
Table-1: Representative
Outside Noise Levels
|
2- Engine Exhaust Emissions Regulations
Generator sets, regardless of application, may be subject to engine exhaust emissions regulations on a local or national level or both. Compliance with emissions regulations usually requires special permits. Certain localities may have specific designations requiring gaseous–fueled engines and/or exhaust after–treatment strategies for diesels.
Criteria Pollutants
|
GRAMS /
BHP _ HR
|
HC (Total Unburned Hydrocarbons)
|
0.1–0.7
|
NOx (Oxides of Nitrogen as NO2)
|
6.0–13.0
|
CO (Carbon Monoxide)
|
0.5–2.0
|
PM (Particulate Matter)
|
0.25–0.5
|
SO2 (Sulfur Dioxide)
|
0.5–0.7
|
Table-2: Typical
Diesel Exhaust Emissions
|
3- Fuel Storage Regulations
In North America, environmental protection regulations generally exist at both federal and state levels. Different sets of regulations apply to underground vs. aboveground fuel storage tanks. These regulations cover design and construction standards, registration, tank testing, and leak detection. They also cover closure requirements, preparation of spill prevention plans, provisions for financial responsibility, and trust fund coverage.
Fire
Protection
In North America, fire protection regulations typically adopt or reference one or more of the National Fire Protection Association (NFPA) standards. These standards cover such requirements for indoor fuel storage capacity, fuel piping systems, the design and construction of fuel tanks, fuel tank locations, diking, and/or safe drainage provisions. Refer to NFPA Standard No. 37, Installation of Stationary Engines.
You
must consider the following:
Generators that are used for emergency and standby power should be protected from fire by location or by the use of fire–resistant construction in the generator room. In some locations, generator room construction for installations that are considered to be necessary for life safety must have a two–hour fire resistance rating. Some locations will also require feeder fire protection. Consider use of automatic fire doors or dampers for the generator room.
The authority having jurisdiction will usually classify the generator as a low heat appliance when use is only for brief, infrequent periods, even though exhaust gas temperature may exceed 1000°F (538°C). Where exhaust gas temperature may exceed 1000°F (538°C), some diesels and most gas engines may be classified as high heat appliances and may require exhaust systems rated for 1400°F (760°C) operation. Consult the engine manufacturer for information on exhaust temperatures.
However, the authority having jurisdiction may enforce much more stringent restrictions on the amount of fuel that can be stored inside a building. Also, exceptions may be made to allow use of larger amounts of fuel in a generator room, especially if the generator room has properly designed fire protection systems.
|
6- System
Voltage and Phase
|
some
factors needs to be considered when selecting a generator for an
application are:
Number of Phases,
Phase Configurations,
Number of Leads,
Voltage Ranges.
|
1- Number of Phases
Generators
are available in single- or three-phase as follows:
Single-Phase
Generators
For smaller
single-phase loads, these Generators usually do not go above 40 kW.
They are commonly used in residential environments and have a power factor of
1.0.
3-Phase Generators
Mainly for larger
industrial power generation, these Generators can provide both single
and 3-phase power for running industrial motors with higher horsepower,
branch power out for separate lines, and are in general more flexible.
They are typically used in commercial environments and have a power factor of
0.8.
Note:
The
three-phase selection permits single-phase loads to be connected.
|
2- Phase Configurations
Phases
are typically arranged in five configurations to meet the loads requirements
as follows, see figure.1:
Wye Configuration,
Delta Configuration,
Wye Broken Neutral,
Open Delta,
Zigzag Connection.
Fig.1: Phase Configurations
1- Wye Configuration
|
2- Delta Configuration
|
The
wye phase connection has a neutral point, often connected to ground.
The
wye configuration is used with three-phase loads or line to line loads.
In
a wye connection, the terminal voltage is 1.73 times the terminal to-
neutral voltage.
|
The
Delta does not have a neutral point.
Delta
connections are used with single phase and three-phase loads. for example; the
delta connection is sometimes used to obtain single phase 120-240 volts,
3-wire, along with three-phase, 3-wire on the same generator.
A
delta connection would have the same terminal-to neutral voltage as the wye
connection for its terminal voltage.
The
delta line current (I) would now be 1.73 times the wye line current (I).
Delta
connections are found in rural communities where three phase is not
available.
A
generator can lose up to half of its rating if a delta configuration is
hooked to a three-phase system.
|
3- Wye Broken Neutral
|
4- Open Delta
|
A
wye connection can be structured in the two ways; a fixed neutral
connection or a broken neutral connection. The broken neutral allows you to
reconfigure from a wye to delta and vice-versa. It also provides
differential protection by allowing the machine to monitor the currents
into and out of individual phases.
|
An
open delta is reconfigured from an original delta from three-phase to
single-phase use; this type of connection, however, will only provide
approximately 57% of the original three.
|
5- Zigzag Connection
|
The
zigzag connection is sometimes used to get an alternative voltage from a
generator.
For
example, the connection shown in Figure 18 can
provide 120-208V from a generator wound for 120-240V.
|
|
3- Number of Leads
Generators
have 4, 6, 10, or 12 line leads or outputs. These can be connected into a low
voltage wye configuration (coils parallel) or into a high voltage wye
configuration (coils in series). See figure.2
Fig.2: Number
of Leads
Generators with 12 leads can be connected in delta configuration.
Larger generators use more than one wire per line lead. This feature eases the problem of forming very heavy conductors inside a limited space for terminal connections. All leads are identified. If more than one wire is used per line lead, a line lead number identifies each of these wires.
Thus, on smaller generators, there would be only one wire marked T1. However, on larger generators, there will be two or more wires marked T1. These are to be connected together to form one lead.
|
4- Voltage Ranges
To determine the size of the generator
needed, we must assign the applicable voltage range. There
are three voltage ranges; Low, medium, and high.
Low voltage range
|
Medium voltage
range
|
High voltage
range
|
Low
voltage is the voltage on a local level or part of a site.
|
Medium
voltage is a low level distribution rating. This voltage is distributed to
power residential sites and other campuses.
|
High
voltage runs over regions and is the voltage at a utility or the national
grid.
|
600
V or less with 800 kVA for less than 250 V is typical.
|
601
V-5000 V with 5-10 MVA is the range for the medium rating.
|
5001
V-15,000 V used with MVA’s greater than 10 are considered High Voltage.
|
Figure.3
shows a voltage versus kVA
chart, indicating low, medium and high voltage selections.
Fig.3:
Voltage/KVA Chart
Common Voltages on
Generator Sets
Single-Phase
|
120
|
240
|
120/240
|
3-Phase
|
208
|
120/208
|
220
|
240
|
440
|
480
|
277/480
|
600
|
2400
|
3300
|
4160
|
6900
|
11500
|
13500
|
|
|
|
The most common voltages in North America are:
120/240V, 1 phase, 3W,
120/208V, 3 phase, 4W wye,
277/480, 3 phase, 4W wye,
120/240V 3 phase, 4W Delta.
120/240V, 1 phase, 3W
This is the standard voltage for single phase systems. 120
V is common for office equipment and small single-phase motors. Motors are limited to 10HP maximum. Either 120 volts or 240
volts can be used to supply loads. 120 volt loads must be balanced across the
generator L1 to N and L2 to N. Disadvantages are that single phase motors are
more unreliable than three phase motors, especially capacitor start motors.
The voltage drop is higher in single phase systems for a given load for the
same wire size used in 3 phase systems.
120/208V, 3 phase, 4W- wye
This is a good choice for a three phase system because you can
balance 120 volt loads around the wye to equally load the generator. 208V
single phase and 208V three phase loads can be used as well as 120V single
phase loads. Motors must be rated 200 volt operation; 240 volt resistance
heating equipment used on a 208V generator will only produce 75% of its rated
KW output.
277/480, 3 phase, 4W- wye
This voltage is usually used on large systems to reduce incoming
service size, wire size and distribution equipment size. Fluorescent and
other discharge lighting can be used at 277 volts. 480 volt single phase,
480V three phase for large air compressors, motors,
chillers, and air handlers, and 277 volt single
phase loads can be used on this system.
Also good for minimizing voltage drops on long runs.
Disadvantages are that a step down transformer is required to get 120/208 or
120/240 volt power for lights and outlets. Motors should be started directly
from the generator buss, not from a step down transformer to minimize
voltage drop.
120/240V, 3 phase, 4 W Delta
Should not use on generator as it overloads 1 phase if there are
large 120 volt loads. This is the
least desirable voltage to use if there is a large amount of 120 volt load.
The generator cannot be balanced and may overheat the windings. Advantages
are 240 volt motors and equipment are more common than 200 volts.
|
In the next article, we will
continue explaining other Selection factors used for Generators Sizing Calculations.
So, please keep following.
No comments:
Post a Comment