In Article " Earthing Systems Design steps – Part One ", I indicated the following points:
Earthing Systems Design
Steps
|
In the above Article and Article " Earthing Systems Design steps – Part Two ", I explained the first step: Data Collection.
Also, in Article " Earthing Systems Design steps – Part Three ", I explained the second step: Data Analysis.
Today I will explain the third step of earthing system design which is Grounding Design Calculations as follows.
You can preview the following Articles for more info:
Third Step: Earthing System Design
Calculations
Under this title, I will differentiate between two types of
buildings as follows:
The design process of a substation grounding system requires many steps as established by the IEEE Standard 80, and it is more complicated than that of the general building (Non-substation buildings). However, the design process of a substation grounding system is not under the scope of this course. |
What we are going to design for grounding system in any
building?
Grounding system in any building can
be broken down into several subdivisions:
|
First: The Building
Exterior Grounds
Generally, the building exterior
grounds consists of:
|
1- The Building’s
Perimeter Grounds
The building’s perimeter grounds
consist of the following components:
Note:
In some cases, an electrical design
requires ground rods to be installed in addition to the perimeter ground
ring. The use of ground rods helps to minimize the effects of dry or frozen
soil on the overall impedance of the perimeter ground system. This is because
the ground rods can reach deeper into the earth where the soil moisture
content may be higher or the soil may not have frozen.
Design Recommendations For Building’s
Perimeter Grounds:
Fig. 1
Fig. 2
Fig. 3
Fig. 4
|
2- Fence Grounds
1- Where gates are installed, the fence
shall be grounded at each side of the gate or similar opening (see Fig. 5).
Fig. 5
2- If a conducting gate is used, a buried bonding jumper must be installed across the opening (see Fig. 5).
3- Where gates are installed, they shall
be bonded to the fence, grounding conductor or other bonding jumper (see Fig.
6).
Fig. 6
4- If the fence posts consist of a
conducting material, the grounding conductor must be connected to the fence
posts with a suitable connecting means (see Fig. 6).
5- If the fence contains sections of barbed wire, the barbed wire must also be bonded to the fence, grounding conductor or other bonding jumper (see Fig. 6). 6- If the fence posts consist of a nonconducting material, a bonding connection shall be made to the fence mesh strands and barbed wire strands at each grounding conductor point (see Fig. 6).
Fig. 7
|
3- Other Grounds
Other grounds that are located on the
outside of the building that should be considered are:
A- Handhole, Manhole And Pull Box
Covers
Fig. 8
B- Metal Poles
C- Lighting Fixture Standards
Lighting standards in parking lots
and other areas where the public may contact them should be grounded (see
Fig. 8). Keep in mind that the earth cannot serve as the sole equipment
grounding conductor. Light standards which are grounded by the use of a
separate ground rod must also be grounded with an equipment grounding
conductor to ensure that the overcurrent protective device will operate.
D- Rails
Rails or sidings into hazardous
locations such as grain storage facilities, ammunition dumps, etc., should
also be properly bonded and grounded (see Fig. 8). Designers and
installers must not forget that distant lightning strikes can travel through
the rails for many miles.
|
Installation Recommendation
For Building Exterior Grounds
Fig. 9
Fig. 10
|
In the next Article, I will continue explaining Other Building’s Earthing System Divisions. Please, keep following.
No comments:
Post a Comment
Leave a comment to help all for better understanding