In Article " Overcurrent Protection – Part One ", which was an Introduction to Overcurrent Protection, I provide the basic information needed for best understanding of the Overcurrent protection.
Also, In Article " Overcurrent Protection – Part Two ", I answered the following questions:
- How to size the overcurrent protection devices (OCPDs)?
- How to select the proper overcurrent protection for certain applications?
Today, I will answer the following questions:
- How to select the proper overcurrent protection devices (OCPDs) for certain application?
Selecting the proper overcurrent protection devices (OCPDs) for certain application
There are several types of overcurrent protection devices (OCPDs) that can be used to protect equipment and people from overcurrents such as fuses, circuit breakers and Thermal overload relays.
1- overcurrent protection devices (OCPDs) Ratings:
Breaker or Fuse Type
|
Conditions
|
Rating
|
Fuses
and Fixed-Trip Circuit Breakers**
|
The standard
ampere ratings for fuses and inverse time circuit breakers shall be
considered as follows:
15,
20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200,
225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500,
3000, 4000, 5000, and 6000 amperes.
Additional
standard ampere ratings for fuses shall be 1, 3, 6, 10, and 601.
|
|
Adjustable-Trip
Circuit Breakers**
|
Breakers have external
means for adjusting the current setting (long-time pickup setting), not
meeting the requirements of Restricted Access breakers in below.
|
= the maximum setting possible.
|
Restricted
Access Adjustable-Trip Circuit Breakers **(see fig.1)
|
Breakers
that have restricted access to the adjusting means. Restricted access shall
be defined as located behind one of the following:
|
= the adjusted current setting (long-time
pickup setting).
|
Notes:
* The
use of fuses and inverse time circuit breakers with nonstandard ampere
ratings shall be permitted.
** A combination of a current
transformer and overcurrent relay shall be considered equivalent to an
overcurrent trip unit.
- The set long-time pickup rating is the opposite to the
instantaneous trip rating.
|
Fig (1) |
Rule#1: overcurrent protection devices (OCPDs) Load
According to the National Electric Code,
all overcurrent devices may be loaded to a maximum of 80% of their continuous
ampere rating, unless they are specifically listed for 100%.
|
2- Selection of Circuit Breakers:
Multipole or Single-Pole Circuit breakers
Circuit breakers (as Overcurrent Device)
shall open all ungrounded conductors of the circuit both manually and
automatically. (see fig.2)
Exception: single-pole circuit breakers,
with identified handle ties, shall be permitted as the protection for each
ungrounded conductor as in the blow table.
|
Fig (2) |
Fig (3) |
Fig (4) |
Circuit breaker used as a switch
|
Circuit breaker Proper Voltage Rating
Circuit breakers must be properly applied
within their voltage rating and as per the following:
|
Circuit Breaker without an Instantaneous Trip
Where a circuit breaker is utilized without
an instantaneous trip, one of the following or approved equivalent means
shall be provided:
Zone-selective interlocking and
Differential relaying do not require any manual intervention.
|
3- Selection of Fuses:
Disconnecting Means for Fuses
|
Permissible Usages for Fuses
fuses shall be permitted to be used in certain
circuits as per the following Table:
|
|
4- Using Thermal Overload Relays:
Thermal Overload Relays
Thermal overload relays and other devices
not designed to open short circuits or ground faults shall not be used for
the protection of conductors against overcurrent due to short circuits or
ground faults.
But the use of such devices shall be
permitted to protect motor branch-circuit conductors from overload and shall
be protected for short circuits or ground faults by fuses or circuit breakers
or by a motor short-circuit protector.
|
4- Series Rated System
|
Fig (7) |
Parallel Use Of Fuses And
Circuit Breakers
Fuses and circuit breakers shall be
permitted to be connected in parallel where they are factory assembled in
parallel and listed as a unit. Individual fuses, circuit breakers, or
combinations thereof shall not otherwise be connected in parallel.
|
In the next Article, I will answer the following questions:
- Where to locate the overcurrent protection devices (OCPDs)?
No comments:
Post a Comment