In the previous article “Classification and Types of UPS – Part One”, We explained the following points:
- Applicable Standards for UPS Systems
- What is a UPS?
- Why do we need a UPS?
- UPS Rating
- Classification of UPS
In addition, we stated that UPS is
classified according to:
- Voltage range,
- No. of phases,
- Mobility,
- Technological design,
- Physical Size/capacity,
- Form factor/ configurations,
- Topology,
- Distribution Architecture,
- Use of transformers.
We already explained the first four
classifications in the above-mentioned article.
Also, in the article “Classification and Types of UPS – Part Two”, We explained the following classifications:
- Physical Size/capacity,
- Form factor/ configurations.
In addition, we stated that according to the
Form factor/ configurations, the UPS Systems have
five famous configurations, which are:
1- “N” System
Configuration
2- “N+1” System
Configuration, which includes:
·
Isolated Redundant Configuration (N +1)
·
Parallel Redundant Configuration (1+1)
·
Parallel Redundant Configuration (N +1)
·
Parallel Redundant Configuration (N +2) and so on
3- Parallel Redundant with
Dual Bus Configuration (N+1 or 1+1)
4- Parallel Redundant with
STS Configuration
·
Parallel Redundant Configuration (1+1) + STS
·
Parallel Redundant Configuration (N+1) + STS
5- System plus System
2(N+1), 2N+2, [(N+1) + (N+1)], and 2N
Moreover, in article Part Two, we explained
the first configuration; “N” System
Configuration and today, we will continue explaining the other
configurations of UPS Systems.
|
2- “N+1” System
Configuration |
|
The “N+1” System Configuration has many
sub-Configurations included under it like: 1- Isolated Redundant Configuration
(N +1) Using two UPS systems may be with different Ratings and
different manufacturers; one on duty and the other is isolated or standby,
feeding load through single bus. 2- Parallel Redundant Configuration (1+1) Using
two UPS systems with same Rating from the same
manufacturer, both on duty and operating in parallel, feeding load through single bus. 3- Parallel Redundant Configuration
(N +1) Using
more than two UPS systems with same Rating from the
same manufacturer, all on duty and operating in parallel, feeding load through single bus. 4- Parallel Redundant Configuration
(N +2) and so on Using
Two or more than two UPS systems with same Rating
from the same manufacturer, all on duty and operating in parallel, feeding load through dual bus. |
|
2.1 Isolated
Redundant Configuration (N +1) It is sometimes called the Hot Standby Configuration;
this is a way to achieve a level of redundancy for
a previously non-redundant “N” System configuration without completely
replacing the existing UPS. Fig-1 Hot Standby Configuration The hot standby configuration is the
simplest form in providing a redundant configuration. In Hot standby
configuration, we utilize two UPS systems (Fig.1), the normal system power
flow to the critical load is through UPS #1 (Main or Primary UPS) and UPS#2 (Isolation
or Secondary UPS) acts as standby UPS. If UPS #1 should fail, or if the load current exceeds the UPS's full load rating, the static switch will transfer the critical load to the static bypass (which is the output of UPS #2) within 4-5 milliseconds. When the UPS #1 is rectified, the loads will be transferred back to UPS#1 automatically without any interruption to the loads. Under normal conditions, UPS #2 is idle but always on and ready to assume the critical load through the transfer of static switch (UPS #1). If UPS #2 should fail, its static switch will sense the loss of function and transfer the load to the system bypass source (see Fig.2). The system bypass can be supplied through either a voltage conditioning (regulating) transformer or a non-regulating shielded isolation transformer through Static Var Compensators SCVS. Fig-2 Isolated Redundant UPS Configuration The isolated redundant design concept does not require a paralleling bus, nor does it require that the modules have to be the same capacity, or even from the same manufacturer
Advantages:
Disadvantages:
|
|
2.2 Parallel
Redundant Configuration (1+1) Parallel
redundancy refers to the simultaneous operation of two UPS systems operating
in parallel. Figure 3–Parallel Redundant Configuration, illustrates two UPS
systems operating in parallel. Fig-3 Parallel Redundant Configuration (1+1)
In
this scheme both UPS systems are supplying approximately 50% of the combined
AC load. The failure of either UPS systems would result in the entire load
being assumed by the healthy UPS. The failure of both UPS systems would
result in the load being transferred to the alternate power source via the static
transfer switch.
|
|
2.3 Parallel
Redundant Configuration (N +1) Parallel
redundancy refers to the simultaneous operation of more than two UPS systems
with same rating from the same manufacturer
operating in parallel. Figure 4 – Parallel Redundant Configuration,
illustrates three UPS systems operating in parallel. Fig-4 Parallel Redundant Configuration (N+1) In
this scheme each of the UPS systems will share equally the combined AC load.
The failure of any one of the UPS system would result in the entire load
being assumed by the remaining healthy UPS. The failure of two UPS systems
would result in the load being transferred to the alternate power source via
the static transfer switch. This capability allows any one module to be removed from the bus and be repaired without
requiring the critical load to be connected to straight
utility. The UPS module manufacturer also provides the paralleling board for the system. The paralleling board may contain logic that communicates with the individual UPS modules, and the UPS modules will communicate with each other to create an output voltage that is completely synchronized. The parallel bus can have monitoring capability to display the load on the system and the system voltage and current characteristics at a system level. The parallel bus also needs to be able to display how many modules are on the parallel bus, and how many modules are needed in order to maintain redundancy in the system. There are logical maximums for the number of UPS modules that can be paralleled onto a common bus, and this limit is different for different UPS manufacturers. The system is N+1 redundant if the “spare” amount of power is at least equal to the capacity of one system module; the system would be N+2 redundant if the spare power is equal to two system modules; and so on
In
an N+1 system configuration there is an opportunity for the UPS capacity to
grow as the load grows. Capacity triggers need to be set up so that when the percentage of the capacity in place reaches a certain level, (acknowledging that delivery times for some UPS modules can be many weeks or even months), a new redundant module should be ordered. The larger the UPS capacity, the more difficult a task this can become. Large UPS modules weigh thousands of pounds and require special rigging equipment in order to set them into place. There would typically be a spot reserved in the UPS room for this module. This type of deployment needs to be well planned as placing a large UPS module into any room comes with some risk. System efficiency can be an important factor to consider in the design of redundant UPS systems. Lightly - loaded UPS modules are typically less efficient than a module that is loaded closer to its capacity. The below table shows the typical running load for a system using various UPS module sizes, all feeding a 240 kW load. As can be seen in the table, the module size chosen for a particular application can seriously affect the system efficiency. The efficiency of any particular UPS at low loads varies from manufacturer to manufacturer, and should be investigated during a design process.
Table: Parallel
Redundant Configuration (N +1) Advantages:
Disadvantages:
|
|
2.4 Parallel
Redundant Configuration (N +2) ) and so on Using
Two or more than two UPS systems with same Rating
from the same manufacturer, all on duty and operating in parallel, feeding load through dual bus. Same like (N+1) but the spare power is equal to two system
modules; and so on |
|
3- Parallel Redundant with Dual Bus
Configuration (N+1 or 1+1) |
|
The
dual bus configuration, Figure-5 utilizes two or more UPS systems operating
in parallel with two independent distribution systems. This is the most reliable
and most expensive design in the industry. Fig-5 Dual Bus Configuration
|
In the next Article, I will continue explaining other Configurations of
UPS System.
So, please keep
following.


.jpg)
.jpg)

No comments:
Post a Comment