In the previous article "The National Electrical Code (NEC) and HVAC Systems – Part Two", We
indicated that Sizing Calculations for Air Conditioning
and Refrigeration Equipment as Per Article 440 will include
Sizing calculations for:
- Disconnecting Means,
- Branch-Circuit
Short-Circuit and Ground-Fault Protection Devices,
- Branch Circuit Conductors,
- Branch Circuit Overload Protection,
- Motor Controllers.
We explained the
first calculation; Disconnecting Means in
this previous article. Today, we will continue explaining other sizing
calculations for Branch-Circuit
Short-Circuit and Ground-Fault Protection Devices for Air Conditioning
and Refrigeration Equipment as Per Article 440.
The National
Electrical Code (NEC) And HVAC Systems – Part Three
|
MCA
and MOP
|
the
manufacturers are supplying nameplates on heir HVAC equipment which indicate
important information, some of this information are necessary in sizing
calculations of Branch-Circuit Short-Circuit and Ground-Fault Protection
Devices, Branch Circuit Conductors and Branch Circuit Overload Protection,
which are:
|
The Minimum Circuit Ampacity (MCA)
MCA
is the highest steady-state electrical current that the air conditioning
equipment should see when operating correctly. It is needed to
guarantee that the wiring will not overheat under all operating conditions
for the life of air conditioning equipment. The wire size takes into account
the normal current draw, ageing of components and anticipated faults.
MCA = 1.25 x [Motor Rated Current +
Heater Current] + 100% Other Loads (Amps)
The
MCA calculation is dependent on the types of loads in the air conditioner.
Different calculations are used for direct expansion and chilled water units
as follows:
For direct
expansion units:
MCA = 1.25 x [Motor Rated Current + Heater
Current] + 100% Other Loads (Amps)
For chilled
water units:
MCA = 1.25 x Sum of all loads Rated Current
Notes:
Example#1:
(2 nos.) 40 Ton Compressors RLA = 52 Amps each (4 nos.) Condenser Fans RLA = 1.5 Amps each
Calculate MCA?
Solution:
MCA = (52 x 1.25) + 52 + 1.5 + 1.5 + 1.5 + 1.5 = 123 Amps
|
The below table gives a very good summary of
both MOP & MCA:
Example#2:
Calculate the MCA &
MOP?
In this example, the
correction factor for the humidifier is zero. The heater and humidifier do not
run at the same time, so only one is used in the calculations. The heater
rating is used because it is higher than the humidifier rating.
|
Second:
Sizing calculation for Branch-Circuit Short-Circuit and Ground-Fault
Protection Devices
|
Short-circuit and ground-fault protection cannot exceed the
nameplate ratings. If the equipment does not have a nameplate specifying the
size and type of protection device, depending on the load type, you can use
the below calculation rules.
When making the sizing calculation for protection against over-current due to Short-Circuit and Ground-Fault for air conditioning or refrigeration system equipment, different cases apply, depending on the type of load as follows:
|
Case# 1: The load type is a single hermetic motor only as per
440.22(A)
The short-circuit and ground-fault protection device for
motor-compressor must be capable of carrying the starting current of the
motor.
So, you initially size the short circuit and ground fault OCPD
AR as follows:
The short circuit and ground fault OCPD AR ≤ 175%
of the motor-compressor rated-load current or
branch-circuit selection current, which‐ ever is greater.
But, if you reached the 175% threshold but the OCPD
can’t carry the starting current of the motor compressor, you can use the
next size larger OCPD. However, this OCPD can’t exceed 225% of the motor
compressor current rating. In this case, The rule become as follows:
175% of the motor-compressor
rated-load current or branch-circuit selection current, which‐ ever is
greater ≤ the short circuit and ground fault OCPD AR ≤ 225%
of the motor-compressor rated-load current or
branch-circuit selection current, which‐ ever is greater.
How to check
that the OCPD
(over-current protective device) AR with will not trip while motor compressor
starting?
Note:
Example#3:
Size the over-current protection device for a 24A
motor-compressor on a 240V circuit?
Solution:
24A x 1.75 = 42A, next size down protection = 40A.
If a 40A protection device is not capable of carrying the
starting current, you can size the protection device up to 225 percent of the
equipment load current rating (24A x 2.25 = 54A, next size down 50A).
|
Case# 2: The load type is a Combination loads as per 440.22(B).
In this case, the combined load may be:
Note:
In this case, Size the equipment short-circuit and ground-fault
protection with the "largest load" method according to the
following cases:
Note
for the largest load method:
|
Case# A: Where a hermetic
refrigerant motor-compressor is the largest load
In this case:
the rating of the branch-circuit short-circuit and
ground-fault protective device = 175% of the
largest motor-compressor rated-load current or branch-circuit selection
current, which‐ ever is greater + the sum of the rated-load current or
branch-circuit selection current, whichever is greater, of the other motor
compressor(s) + the ratings of the other loads.
But if the OCPD can’t carry
the starting current of the motor compressor, you can use the Maximum Over-Current
Protection (MOP) calculation:
the Maximum Over-Current Protection (MOP) = 225%
of the largest motor-compressor
rated-load current or branch-circuit selection current, which‐ ever is
greater + the sum of the rated-load current or branch-circuit selection
current, whichever is greater, of the other motor compressor(s) +
the ratings of the other loads.
Example#4:
Size the over-current protection device for a 20.2 A
motor-compressor with condenser fan motor 3.2A and evaporative fan motor 3.2
A on a 208V circuit?
Solution:
The rating of the
branch-circuit short-circuit and ground-fault protective device = 20.2 x 175% +3.2+3.2
= 41.75 A
Next size down protection = 40A.
If
a 40A protection device is not capable of carrying the starting current, you the Maximum Over-Current
Protection (MOP) calculation:
The Maximum Over-Current Protection (MOP) = (20.2A x 225% + 3.2+3.2) = 51.85A,
Next size down protection = 50A.
|
Case# B: Where a hermetic
refrigerant motor-compressor is not the largest
In this case:
the
rating of the branch-circuit short-circuit and ground-fault protective device
= the rated-load current or branch circuit selection
current, whichever is greater, rating(s) for the motor-compressor(s) + the
rated-load current For other motor loads not exceeding 800A + the rated-load
current for other loads
But if the OCPD can’t carry
the starting current of the motor compressor, you can use the Maximum Over-Current
Protection (MOP) calculation:
the Maximum Over-Current Protection (MOP) = 225%
of the largest Load rated current or
branch-circuit selection current , whichever is greater
+ the sum of the rated-load current or branch-circuit selection current,
whichever is greater, of the motor compressor(s) +
the ratings of the other loads.
Important notes for MOP value:
|
General
notes for sizing calculation for Branch-Circuit
Short-Circuit and Ground-Fault Protection
Devices
|
Summary
Of Sizing Steps For Branch-Circuit
Short-Circuit and Ground-Fault Protection Devices For Single Hermetic Motor Only
|
|
www.Electrical-Knowhow.com
|
|
Step#1
|
Size the short circuit and
ground fault OCPD AR ≤ 175% of the motor-compressor rated-load current or branch-circuit
selection current, which‐ ever is greater.
|
Step#2
|
Compare the time current curves for both the
motor and the circuit breaker:
If there is intersection, go to step#3,
If not, the OCPD
AR is adequate (end of sizing calculations).
|
Step#3
|
Size the short circuit and
ground fault OCPD AR ≤ 225% of the motor-compressor rated-load current or branch-circuit selection
current, which‐ ever is greater.
|
Notes:
|
Summary
Of Sizing Steps For Branch-Circuit
Short-Circuit and Ground-Fault Protection Devices For Combination Loads
|
|
www.Electrical-Knowhow.com
|
|
Case# A: Where a hermetic
refrigerant motor-compressor is the largest load
|
|
Step#1
|
OPCD AR = 175% of the largest motor-compressor rated-load current or branch-circuit selection current, which‐ ever is greater + the sum of the rated-load current or branch-circuit selection current, whichever is greater, of the other motor compressor(s) + the ratings of the other loads. |
Step#2
|
Compare the time current curves for both the
motor and the circuit breaker:
If there is intersection, go to step#3,
If not, the OCPD AR is
adequate (end of sizing calculations).
|
Step#3
|
the Maximum Over-Current
Protection (MOP) = 225% of the largest
motor-compressor rated-load current or branch-circuit selection current,
which‐ ever is greater + the sum of the rated-load current or branch-circuit
selection current, whichever is greater, of the other motor
compressor(s) + the ratings of the other loads.
|
Case# B: Where a hermetic
refrigerant motor-compressor is not the largest
|
|
Step#1
|
OPCD AR = the rated-load current or branch circuit selection current,
whichever is greater, rating(s) for the motor-compressor(s) + the rated-load
current For other motor loads not exceeding 800A + the rated-load current for
other loads
|
Step#2
|
Compare the time current curves for both the
motor and the circuit breaker:
If there is intersection, go to step#3,
If not, the OCPD AR is
adequate (end of sizing calculations).
|
Step#3
|
the Maximum Over-Current Protection (MOP) = 225% of the largest Load rated current or branch-circuit selection current , whichever is greater + the sum of the rated-load current or branch-circuit selection current, whichever is greater, of the motor compressor(s) + the ratings of the other loads. |
Notes:
|
In
the next article, we will explain in details the sizing calculations for:
- Branch Circuit Conductors,
- Branch Circuit Overload Protection,
So,
please keep following.
The previous and related articles
are listed in below table:
Subject Of Previous
Article
|
Article
|
Summary of
heating and cooling systems,
Parts Consuming
Power in HVAC Systems,
Types of motors
used in HVAC Systems,
Types of pumps
used in HVAC/refrigeration,
Parts consuming
power as per used unit/system,
Motor Nameplate
for Air Conditioner Motor Applications.
|
|
The Common Types Of Motors Used In HVAC Industry
First:
the Common Types of Motors Used in HVAC Industry to drive Compressors
1-
Single-Phase Hermetic Motors:
1.1 Split Phase (SP),
1.2 Capacitor-Start, Induction-Run (CSIR), 1.3 Capacitor-Start, Capacitor-Run (CSCR), 1.4 Permanent Split Capacitor (PSC),
2-
Poly-Phase Hermetic Motors.
Second:
the Common Types of Motors Used in HVAC Industry to drive Fans
1- Shaded-Pole Motors
HVAC System Units And Ratings
Energy Conversions In Air Conditioning /
Refrigeration Systems
|
HVAC Equipment Power Rating Calculations – Part Two |
Difference between Service, Feeder and Branch circuit load calculation
First: The HVAC System Contribution in
Service/Feeder Load Calculations
First: NEC Standard Method
Second: NEC Optional Calculation Method
First: For Single Dwelling Units
Second: Multifamily Dwelling
Third: Two Family Dwelling (That are Supplied By a Single
Feeder)
Forth: Existing Dwelling Unit
|
|
NEC Code & the
Hermetic Refrigerant Motor-Compressors
Sizing Calculations for Air
Conditioning and Refrigeration Equipment as Per Article 440:
First: Sizing Calculations for Disconnecting Means:
Case# 1: The load type is a single hermetic motor
only as per 440.12(A),
Case# 2: The load type is a Combination loads as per
440.12(B).
|
HVAC Equipment Power Rating Calculations – Part Four
|
Back To |
No comments:
Post a Comment