Subject Of Previous
Articles
|
Article
|
Glossary of
Sizing Power and Distribution Transformers,
|
|
Resources
used to calculate basic ratings of power and distribution transformers
|
|
the selection
factors for the Power and Distribution Transformers
|
|
Applicable
calculations procedures for sizing of power and distribution transformers
|
|
1- Applicable
procedures for calculating power and distribution transformer ratios,
2- Applicable
procedures for calculating power transformer efficiency,
3- Applicable
procedures for calculating power transformer voltage regulation,
4- Special Cases
In Transformers Sizing Calculations: Secondary Unit Substations
|
|
Special Cases
In Transformers Sizing Calculations: Paralleled Transformers
|
|
Note: I’d like
from all of you to review our course “EP-3: Electrical Procurement – Transformers Course” to be more
familiar with the contents of our new articles about the Power and
Distribution Transformers sizing calculations.
|
|
Today, we
will explain other special cases for Power and Distribution Transformers
sizing calculations; K-Factor Transformers.
|
Special
Cases In Transformers Sizing Calculations
3-
K-Factor Transformers
|
Linear
Vs. Nonlinear Loads
Linear Loads:
A load that
does not affect the input waveform, which is a pure sinewave, composed of a
fundamental frequency (e.g. 60 hz) component with no multiple frequencies. Typical linear
loads are resistive heating and induction motors.
Nonlinear
Loads:
A load that
distorts the input sinewave such that the resultant waveform is composed of a
fundamental frequency (e.g. 60 hz) component and multiple frequency
components (e.g. 120 hz, 180 hz,..etc) called harmonics. Examples of these
loads used in offices are: computers, fax machines, copiers, printers, cash
registers, UPS systems, and solid-state ballasts. In industrial plants, nonlinear
loads are such
as variable speed drives, HID lighting, solid-state starters and solid-state
instruments.
See Fig.1
Fig.1:
voltage and current waveforms for nonlinear loads.
|
Harmonics
As defined by
ANSI / IEEE Std. 519, Harmonics are voltages or currents at frequencies that
are integer multiples of the fundamental (60 Hz) frequency: 120 Hz, 180 Hz,
240 Hz, 300 Hz, etc. which called odd harmonics (3rd, 5th, 7th ,...,
25th,...). See Table-1.
Table-1:
Harmonics
|
The
Effect of Nonlinear Loads on the Electrical Power Systems
Nonlinear
loads produce harmonic currents which flow from the load towards the power
source following the path of least impedances result in harmonic voltage
drops which are observed as harmonic voltage distortion. The voltage
distortions could become very severe when the power systems inductive and
capacitive impedances become equal, a condition of parallel resonance.
The Problems Caused By
Harmonic Currents Include:
|
K-Factor
K-4, K-9, K-13,
K-20, K-30, K-40, K-50
Fig.2:
UL Label for K-factor Transformers
|
Diversity
of Harmonics
Each non-linear load
generates harmonics independently with the magnitude and phase angle of each
harmonic depending on the design of the circuit and the instantaneous
loading. When several loads are connected in parallel, for example, a number
of personal computers on an office floor, the overall sum of each harmonic
will be less than the sum of the individual magnitudes. See Fig.3.
Fig.3: Diversity
of Harmonics
In other words, the
K-factor of the overall load is less than that which would be expected from measurement
of all the individual items. Similarly, when there are linear loads present,
the overall K-factor is reduced because the harmonic load is a smaller
proportion of the total load.
|
K-Factor
or Factor K?
There are two approaches
in selecting a transformer feeding non-linear loads as follows:
The figures produced by
each method are numerically different; ‘factor K’ is a total rating factor
while ‘K-factor’ is a multiplier (although a de-rating factor can be derived
from it). The fact that both methods use K as a designation can lead to
confusion when talking to suppliers.
Disadvantage
of using De-rated Transformers (factor K) instead of K-Factor Transformer
The use of
de-rated standard transformers instead of K-Factor Transformers carries some
disadvantage as under:
|
Sizing Methods
of Transformers for Non-Linear Loads
We have three methods for
Sizing Transformers for Non-Linear Loads as follows:
Method#1: ANSI / IEEE C57.110 has
a procedure for de-rating standard distribution transformers for non-linear
loading but We will explain this method later since it is more
complicated.
Method#2: Underwriters’
Laboratories method where the appropriate K-Factor for a transformer with non-linear
loads can be calculated as follows:
K
= Σ
(Ih)2
(h)2
Where:
Ih = RMS Current at
Harmonic h
h = Harmonic Order, i.e.
3rd, 5th, 7th, etc.
Fig.4:
K-factor calculations by UL
Method#3: Estimating
K-Factor from Tables
1- List the kVA value for
each load category to be supplied. Next, assign a K-factor designation that
corresponds to the relative level of harmonics drawn by each type of load.
Refer to Table-2.
2- Multiply the kVA of
each load or load category times the Index of Load K-rating (ILK)
that corresponds to the assigned K-factor rating. This result is an indexed
kVA-ILK value.
KVA x ILK
= kVA-ILK
2- Tabulate the total
connected load kVA for all load categories to be supplied.
4- Next, add-up the kVA-ILK
values for all loads or load categories to be supplied by the transformer.
5- Divide the grand total
kVA-ILK value by the total kVA load to be supplied.
This will give an average ILK for that combination of loads.
Total
kVA-ILK/ Total kVA = average ILK
6- From Table-2 find the
K-factor rating whose ILK is equal to or greater than the
calculated ILK.
Table-2:
Estimating K-Factor
Notes:
|
In the next article, we will explain K-Factor/Factor K Calculators used in sizing transformers with non-linear loads. So, please keep following.
Back To |
No comments:
Post a Comment