This is the first Article in Course " GR-1: Inspect ground Grids, Rods, and Fence grounds ".
1- Introduction
Every Building, equipment, power plants, substations and/or facilities included in Electrical Utility System that use electricity require earth grounding, either directly or through a grounding system. (see fig.1)
| Fig (1) |
| Definition: The Earthing System: sometimes simply called ‘earthing’, is the total set of measures used to connect an electrically conductive part to earth. The earthing system is an essential part of power networks at both high- and low-voltage levels. |
| Functions of Earthing Systems A good earthing system is required for:
|
| Earting Main Divisions The earthing is broadly divided as:
|
| Rule of Electrical Inspector in Inspecting Earthing System As an electrical inspector, you must verify correct grounding system installation and operation by doing the following:
|
| The need for Testing Earthing Systems Test the ground system resistance to provide the only concrete proof that the preliminary design assumption is accurate and that the system is adequate and totally effective. Measurements of ground resistance or impedance and potential gradients on the surface of the earth that are due to ground currents are necessary for the following reasons:
|
| A totally effective Earthing system A grounding system to be totally effective, must satisfy the following conditions:
|
| How Earthing system works
|
In any discussion of grounding, the question always asked is how in low resistance ground should be? The answer is by determining the lowest possible ground resistance, the lower the ground resistance, the safer the grounding.
2.1 Determining Ground Resistance
Every Building, substation, equipment operation, and facility that uses electrical power requires a grounding system for safe and proper operation.
| Importance of Ground Resistance It is essential that the grounding system be of the proper resistance to maintain safety to personnel and equipment. And to verify this, you will perform the following:
|
| Definition: Ground Resistance: is the measure of resistance between a grounded system in its entirety or in part, and the soil. You do this by using the grid electrode at the center of the grounded system and the earth at a determined distance away from the system. Record all measurements in ohms (Ω). |
| Note: As an inspector, you must make ground resistance measurements during electrical inspections to verify safe operating limits of grounded systems and their components. The initial measurements will often be of a complete system. |
| Electrode Ground Resistance Components The resistance of a ground electrode has 3 basic components: 1- The resistance of the ground electrode itself and the connections to the electrode: The resistance of the ground electrode and it's connection is generally very low, ground rods are generally made of highly conductive/ low resistance material such as copper of copper clad. 2- The contact resistance of the surrounding earth to the electrode: The contact resistance of the earth to the electrode: The Bureau of Standards has shown this resistance to be almost negligible providing that the ground electrode is free from paint, grease etc. and that the ground electrode is in firm contact with the earth. 3- The resistance of the surrounding body of earth around the ground electrode: The ground electrode is surrounded by earth which is made up of concentric shells all having the same thickness. |
| Ground Resistance Values The ohmic values of ground resistance objectives vary from industry to industry as follows:
The goal in ground resistance values is to achieve the lowest ground resistance value possible that makes sense economically and physically. |
2.2 Soil Resistivity
As an electrical inspector, you should be familiar with soil resistance in order to make calculations for ground resistance layouts, when needed.
| Definition: Soil resistivity ρ (specific earth resistance): is the resistance, measured between two opposite faces, of a one-metre cube of earth. The earth resistivity is expressed in Ωm. |
| Factors Affecting Soil Resistivity ρ Soil resistivity depends on:
It stands to reason that soil resistivity will vary throughout the year in those areas where seasonal changes bring about a change in the moisture and temperature content of the soil. For a grounding system to be effective it should be designed to withstand the worst possible conditions. |
| Note: Where no information is available about the value of ρ it is usually assumed ρ = 100 Ωm. |
In the next Article, I will explain How to Calculate the Ground Resistance. Please keep following.
No comments:
Post a Comment