Load Calculations for Feeder and Service Neutral


Load Calculations for Feeder and Service Neutral





Definitions:

Neutral Conductor: is The conductor connected to the neutral point of a system that is intended to carry current under normal conditions.

Neutral Point: is The common point on a wye-connection in a polyphase system or midpoint on a single-phase, 3-wire system, or midpoint of a single-phase portion of a 3-phase delta system, or a midpoint of a 3-wire, direct-current system.





Important!!!
The neutral conductor is a current-carrying conductor. Many believe that, because the neutral conductor is a grounded conductor, it is safe to work on it while it is energized. This is a very dangerous practice that has led to many serious electric shocks.




Four examples of a neutral point in a system (see below image)

An example of the first system is a three-phase, four-wire wye-connected transformer.

An example of the second system is a single-phase, three-wire system that supplies power to Most of one-family dwellings.

An example of the third system is an ungrounded delta system which is a type of three-phase delta system that is sometimes used in industrial facilities

An example of the fourth system is a direct current system used to supply power derived from batteries, power supplies, generators or other sources to the loads.









Important!!!
At the neutral point of the system, the vectorial sum of the nominal voltages from all other phases within the system that utilize the neutral, with respect to the neutral point, is zero potential.
In some type of delta system, not all phases utilize the neutral; as in below image where phase (B) does not utilize the neutral.








Important!!!
The neutral load must be calculated in accordance section 220.61 even if the feeder or service is calculated by the NEC standard method (Part III) or the NEC optional method (Part IV).





Rule#1: The feeder or service neutral load Basic Calculation

As per NEC section 220.61(A), The feeder or service neutral load shall be the maximum unbalance of the load determined by article 220. The maximum unbalanced load shall be the maximum net calculated load between the neutral conductor and any one ungrounded conductor.

  
Exception for Rule#1:
For 3-wire, 2-phase or 5-wire, 2-phase systems, the maximum unbalanced load shall be the maximum net calculated load between the neutral conductor and any one ungrounded conductor multiplied by 140 percent.





Important!!!
When calculating the neutral load, it is not necessary to include loads that do not contribute to the neutral current.




Example#1:

A non-dwelling occupancy has a calculated service load of 92 amperes on one phase and 88 amperes on the other phase. The loads have been balanced as evenly as possible. A water heater has a current draw of 19 amperes at 240 volts. The voltage at this panelboard will be single-phase, 120/240 volts. What is the neutral load?



Solution: 



Since the water heater is 240 volts, it will not contribute to the neutral current. Therefore, 19 amperes can be omitted from the neutral load calculation.

The neutral load = highest calculated load – water heater Load = 92 – 19 = 73 amperes

Although the feeder conductors must have an ampere rating of at least 92 amperes, the conductor feeding the neutral must have an ampacity of at least 73 amperes.






Rule#2: Permitted Reduction in Neutral Load - 1

As per NEC section 220.61(B)(1), When calculating the feeder or service neutral load, it is permissible to apply a demand factor of 70 percent to household electric ranges, wall-mounted ovens, counter-mounted cooking units and electric dryers, where the maximum unbalanced load has been determined in accordance with Table 220.55 for ranges and Table 220.54 for dryers.





Example#2:

What is the minimum neutral load on the service for 5,500-watt clothes dryer installed in a one-family dwelling?



Solution: 


When calculating feeder or service neutral loads for clothes dryers, start by finding the feeder or service load. 
As per Table 220.54, because there is only one dryer, the minimum service load (at 100 percent) is 5,500 volt-amperes 
Apply Rule#2 above; multiply the service load by 70 percent. 

So, the minimum neutral load on the service = 5,500 VA × 70% = 3,850 VA




Example#3:

A 10-unit apartment building will have a 12-kW range in each apartment. What load will these ranges add to a service neutral calculation?



Solution: 


Start by finding the feeder or service load. 
As per column C of Table 220.55 for 10 appliances, the maximum demand for 10 nos. 12-kW ranges is 25 kW. 
Apply Rule#2 above; multiply the service load by 70 percent. 

The neutral load = 25 KW × 70% = 17.5 kW






Rule#3: Permitted Reduction in Neutral Load - 2

As per NEC section 220.61(B)(2), Where the calculated neutral current is more than 200 amperes, another reduction is permitted. Where the feeder or service is supplied from a three-wire DC or single-phase AC system; a four-wire, three-phase, three-wire, two-phase system; or a five-wire, two-phase system, it is permissible to apply a demand factor of 70 percent to that portion of the unbalanced load in excess of 200 amperes [220.61(B)(2)]. This demand factor is also in addition to any demand factors that may have already been applied.






Example#4:



After calculating the service load for an office building by the NEC Standard calculation, the neutral load is 216,000 volt-amperes. What is the neutral load after applying the demand factor from 220.61(B)(2)? The electrical service will be supplied by a 208Y/120-volt, three-phase, four-wire system.



Solution: 


First, convert volt-amperes to amperes. Since this is a 208-volt, three-phase system, the total voltage = 208 V × 1.732 = 360.256 V = 360 V 

The neutral Load in Amps = 216,000 VA ÷ 360 V = 600 A
Apply Rule#3 above; multiply the amperes in excess of 200 amperes by 70 % 

The amperes in excess of 200 amperes = 600 A – 200 A = 400 A

The demand neutral Load in excess of 200 amperes = 400 A × 70% = 280 A

The total demand neutral load = 280 A + 200 A = 480 A






Rule#4: Prohibited Reduction in Neutral Load - 1

As per NEC section 220.61(C)(1), there shall be no reduction of the neutral or grounded conductor capacity applied to Any portion of a three-wire circuit consisting of two ungrounded (hot) conductors and the neutral conductor of a three-phase, four-wire, wye-connected system.




Important!!!
As per Rule#2 above, it is permissible to apply an additional demand factor of 70 percent to a feeder or service neutral supplying household electric ranges. But, As per Rula#4, applying the 70 percent demand factor is not permissible if the ranges are supplied by a single-phase panel that is fed from a three-phase, four-wire, wye-connected system.





Definition:
Nonlinear Load: A load where the wave shape of the steady-state current does not follow the wave shape of the applied voltage.

Electronic equipment, electronic/electric-discharge lighting, adjustable-speed drive systems, and similar equipment may be nonlinear loads.





Rule#5: Prohibited Reduction in Neutral Load - 2

As per NEC section 220.61(C)(2), there shall be no reduction of the neutral or grounded conductor capacity applied to That portion consisting of nonlinear loads supplied from a 4-wire, wye-connected, 3-phase system.






Important!!!
As per Rule#3 above, where the feeder or service-neutral load exceeds 200 amperes, it is permissible to apply an additional demand factor of 70 percent to that portion of the unbalanced load in excess of 200 amperes. But, As per Rula#5, applying the 70 percent demand factor to reduce the neutral or grounded conductor’s capacity is not permissible for that portion consisting of nonlinear loads supplied from three-phase, 4-wire, wye-connected systems .





Example#5:

After calculating the service load for an office building by the basic calculation, the neutral load is 216,000 volt-amperes. The major portion of the neutral load is fluorescent luminaires and information technology equipment. The electrical service will be supplied by a 208Y/120 volt, three-phase, 4-wire system. After demand factors, what is the neutral load in amperes?



Solution: 



First, convert volt-amperes to amperes. Since this is a 208-volt, three-phase system, the total voltage = 208 V × 1.732 = 360.256 V = 360 V

The neutral Load in Amps = 216,000 VA ÷ 360 V = 600 A

Apply Rule#5 above; since the major portion of the neutral load consists of nonlinear loads, applying the additional demand factor of 70 percent is not permissible.
This office building has a neutral demand load of 600 amperes 






Important!!!
If the neutral load calculated as per 220.61 is less than the calculated load of the ungrounded (hot) conductors, it might be possible to reduce the size of the feeder or service-neutral conductor to be smaller than the ungrounded conductors size, but this is not a must, The installed neutral conductor can be the same size as the ungrounded conductors.




Rule#6: Relation between Sizes of Neutral Conductor and Equipment-Grounding Conductor

Compare the minimum size required for the neutral calculated load with the minimum size equipment-grounding conductor from table 250.122 (in below image); then, select the larger of the two to be the size of the neutral conductor.






Example#6:

a 400-ampere panelboard (protected by a 400-ampere breaker) will be installed in an area within an industrial plant. The panelboard will be supplied by a 208Y/120 volt, three-phase, 4-wire system. The size of the ungrounded feeder conductors will be 500 kcmil copper. The calculated neutral load is 67 amperes. What is the minimum size conductor required for the neutral?



Solution: 


Based on the calculated neutral load only, the minimum size conductor from Table 310.16 is 4 AWG. (See image for table 310.16) 




The size equipment-grounding conductor specified in Table 250.122 for a 400-ampere overcurrent device is 3 AWG copper.
Therefore, the minimum size neutral conductor is 3 AWG copper. 






Rule#6: Relation between Sizes of Neutral Conductor and Grounded Electrode Conductor

The neutral conductor must not be smaller than the required grounded electrode specified in table 250.66 (in below image).







In the next article, I will explain the Overcurrent Protection Calculations. Please, keep following. 





No comments:

Post a Comment