How to use this Spreadsheet? (see fig.1)
fig (1):Residential Load Calculation Spreadsheet
To print go to the top of the page, next to file, edit, is view from there go down to custom views, you will find “calc w/ pool” and “calc no pool”. Select the one you want to print and press the print button.
Residential Load Calculation spreadsheet manual:
1- Check the box in cell D6 next to the title of the sheet to use the “optional calculation ART 220.82” instead of the “standard calculation ART 220.42 THRU 220.55”
2- User Info. Worksheet: see fig.2
fig (2): User Info. Worksheet
Enter the required information in the User Info. worksheet As
follows:
|
| Company name Address City, state, Zip code Telephone &fax Serial number |
3- Residential Calculation worksheet: see fig.1
Step (1): Article 220.42 & 220.52 (see fig.3)
fig (3): step (1)
Input
|
NEC rule
|
note
|
Enter
square foot/square meter living area
by selecting from the drop down box
|
As
per NEC 220-3 (b) the floor area shall be computed from the outside
dimensions of the dwelling unit. For dwelling units, the computed floor area
shall not include open porches, garages, or unused or unfinished spaces not
adaptable for future use.
|
(a minimum square area permitted = 1000 square foot)
The
demand factors listed in table 220-42 (220.82(1) for optional method) shall
apply to that portion of the total branch-circuit load computed for general
illumination. They shall not be applied in determining the number of branch
circuits for general illumination.
|
Small Appliance
|
as
per NEC 220-11(c) (1) which need “two or more 20 ampere small appliance
branch circuits shall be provided for all receptacle outlets specified by
section 210-52 (b) for small appliance load”
|
(Minimum
of (2) circuits are required for small appliances)
|
Laundry circuit
|
as
per NEC 220-11(c) (2) which need “at least one additional 20 ampere branch
circuit shall be provided to supply laundry receptacle outlet(s) required by
section 210-52(f)”
|
(Minimum
of one circuit is required)
|
output
|
NEC rule
|
notes
|
General Lighting load
|
NEC
220-12 need Lighting load for dwelling unit(s) as follows:
a unit load not less than 3 VA shall
constitute the minimum lighting load for each square foot of floor area
|
|
Small Appliance
|
NEC
220-52(A) need that the load shall be
computed at 1500 VA for each 2-wire small appliance branch circuit required
by NEC 220-11(C) (1)
|
|
Laundry circuit
|
NEC
220-52(B) A load not less than 1500
volt-amperes shall be included for each 2-wire laundry branch circuit
installed as required by 210.11(C)(2)
|
|
General load sum for lighting, small appliances and laundry
loads
|
This
is the sum total of (1) general lighting (living area square footage times 3
watts) , (2) each small appliance circuit @1500 watts each and laundry
circuit @1500 watts
|
|
General demand load sum
|
General
load sum=
First 3000VA @ 100% demand +
Next 117,000 @35% demand +
Reminder @ 25% demand
|
Step 2: Article 220.50 & 220.51 (see fig.4)
fig (4): step (2)
A check box is shown for selection between making calculations
for (A/C Condenser and fixed space heating) or (Heat pumps with concurrent
supplementary heating)
|
|
First case: (A/C Condenser and fixed space heating)
|
|
Inputs
|
outputs
|
1- Select the A/C Condenser cooling tons from the drop down box #1 and you will get the electrical load in VA for A/C condenser. 2- Select the fixed space heating (AHU) KW from the drop down box #2 and you will get the electrical load in VA for both strip heater and blower loads. 3- Select the quantities for A/C Condenser and/or fixed space heating AHU. |
1- Heating load in VA (heating Load =(space heat x demand factor + 100% (fan blower) ) 2- Cooling load in VA (the blower fan from the AHU is included in this value) 3- Greater of Heating load @100% VS cooling load @ 100% |
second case: (Heat pumps with concurrent supplementary
heating)
|
|
Inputs
|
outputs
|
1- Select the Heat pump tonnage from the drop down box #1 and you will get the electrical load in VA for Heat pump. 2- Select concurrent supplementary heating KW from the drop down box #2 and you will get the electrical load in VA for both strip heater and blower loads. 3- Select the quantities Heat pumps with concurrent supplementary heating. |
1- Heating load in VA (heating Load =(space heat x demand factor + 100% (fan blower) + 100% heat pump ) 2- Horse power load in HP 3- Heating load @100% |
i will continue explaining this spreadsheet in the next topic. please keep following.
To down load Residential load calculations spreadsheet, please press on the link then choose save as.
With the advent of LED and florescent lights it seems like the lighting demand should be reduced by a factor of at least 3 more likely 10. I can reduce the square footage to get a demand but I wonder if the NEC reflects this.
ReplyDeleteTomG