Bonding:
It is the connection of two or more conductive objects to one another by means of a conductor such as a wire to provide continuity and conductivity.
the term "Bonding" shouldn't be confused with the term "Grounding" since the two terms has different definitions and applications although some consultants use them interchangeable especially in industrial projects.so, we need to define the term "Grounding" to understand its difference from the term "Bonding" as follows:
Grounding / Earthing:
It is the attachment of a bonded metallic system to earth, typically through ground rods or other suitable grounding electrodes for ensuring zero voltage.
Note: grounding is American standard term is equivalent to earthing which is a British standard term.
Comparison between bonding and grounding is given in the following table:
|
s/n
|
Bonding
|
Grounding
|
|
1
|
Connection between non-live conductive objects
|
Connection between live or non-live conductive objects to earth
|
|
2
|
Bonding is achieved by using bonding conductors, metallic raceways,
connectors, couplings, metallic-sheathed cable with fittings, and other
devices approved by the authority having jurisdiction as recognized for this
purpose
|
Grounding is achieved by using a rod or other suitable grounding
electrodes.
|
|
3
|
Bonding for grounded system provides the safety during fault current
for persons
|
Grounding provides the safety during fault current for equipments
without a need for bonding its enclosure
|
|
4
|
Bonding objects without grounding one of them gives no protection
from stray currents but it protect from static charges
|
Grounding is independent on bonding it gives equipment protection
disregard it is bonded to its enclosure or not.
|
Bonding Jumper: see fig.1
This is the connection between noncurrent-carrying metallic components of the electrical system that are provided to ensure continuity.
fig(1): Boning Jumper
Equipment Bonding Jumper: see fig.2
These are bonding connections made between two portions of the equipment grounding system.
fig (2): Equipment Bonding Jumper
Main Bonding Jumper: see fig.3
A main bonding jumper provides the Code-required connection between the grounded system conductor and the equipment ground bus at the service equipment for a building or structure.
fig (3): Main Bonding Jumper
System Bonding Jumper: see fig.4
The conductor, screw or strap that bonds the equipment bonding conductor (metal parts of a separately derived system) to one of the system conductors or terminal
fig (4): System Bonding Jumper
In the next topic, I will continue explaining other definitions from article 100.
No comments:
Post a Comment