Today, we will start explaining what the
Load Bank is and How to Size it correctly.
Introduction to Load Banks
|
What is a Load Bank?
Any device which generates electricity can be called as a power
source and it may require testing from time to another for the purposes of
product development, production line testing, product demonstration,
commissioning of a new installation or for periodic service, maintenance or
trouble shooting.
To test a power source, we need to use a load bank which can be
simply defined as follows:
A Load
Bank is an electrical device which acts as an electrical load to an
electrical power source for the purposes of testing, supporting or protecting
this power source.
A load
bank test ensures that your power source will run property when it’s needed
so that you can depend on its proper operation during an actual emergency
situation.
We can
control, measure and record the electrical load provided by a load bank for
determining performance characteristics of any power source like:
|
Why we don’t
use the actual facility loads to test the power source?
If the performance of the power source like a generator is not
known, it is better to evaluate the performance with a load bank than with
actual facility loads for the following reasons:
|
Wet Stacking Problem
What is wet stacking?
The term ‘Wet Stacking’ originates from the fact that fuel is still ‘wet’ in the exhaust system when in operation. Wet Stacking occurs in diesel gen-set engines operating under no or lightly loaded conditions (less than 30% of rated load) for extended periods. The low running load means the engine does not reach optimal operating temperature for peak performance leaving unburnt fuel and carbon deposits within the engine. Consequences of wet stacking: Wet stacking conditions cause unburnt fuel deposits to collect on the combustion chamber, injector nozzles, piston rings, turbocharger, and exhaust system. Some issues associated with wet stacking include:
National fire protection agency (NFPA) standards for wet stacking The NFPA 110 has guidelines to reduce the effects of wet stacking on backup power systems. The NFPA 110 8.4.2 guidelines in Level 1 and 2 applications require exercising the unit, at least monthly, for 30 minutes under either of two methods:
How to prevent wet stacking? The best way to mitigate the effects of wet stacking is to apply additional load to the gen-set, increasing operating temperatures to burn off accumulated unburnt fuel and carbon. The amount of minimum load varies per engine manufacturer, but the typical range is 30% to 50% of the kilowatt rating. It is proven diesel engines operate more efficiently in the 70% to 80% range of rated kW output. Load banks are the best practical means of applying load to gen-sets and preventing wet stacking. |
Load Bank Applications
Load Banks can be used for
several purposes, including:
1- Manufacturing Testing
a- Generator Testing
Manufacturers of standby
power generators commonly use load banks to test and tune newly assembled
units. A test engineer uses the load bank to apply a discrete, selectable
electrical load to the generator and measure the response stability and
endurance. During this process, the test engineer calibrates and adjusts the
generator performance to ensure it meets the intended product specifications
and tolerances.
b- Engine Testing
Manufacturers of small gas
engines also use load banks to test newly manufactured engines under various
mechanical loads. This is accomplished by connecting the engine to the load
bank via a device called a dynamometer. Again, engine performance is
monitored and, if necessary, adjustments are made to ensure the product
performs within intended specifications.
c- Demonstration
Load banks are often used
as tool for demonstrating to buyers and users of a new generator set that the
unit meets the performance specifications outlined in the purchase contract
“Customer witness testing”.
2- Field operation and
Testing
a- Periodic maintenance
Generators installed in the
field must be periodically tested and exercised to ensure that it will
operate as intended when a power outage actually occurs. Service groups use
load banks to apply a load that mimics the load of the facility the generator
is protecting. Any problems with the generator can then be identified and
rectified in a non-critical environment.
Load Banks can be used to
satisfy the requirements of the National Fire Protection Association (NFPA)
for emergency stand-by power systems. These requirements concern acceptance
testing and periodic on-site testing and maintenance of emergency and
stand-by power systems.
b- Elimination of ‘Wet
Stacking’
Load banks may be installed
in a diesel powered generator set to apply the additional load required to
ensure the engine fully consumes the fuel in the combustion process. If a
diesel engine is not operated under adequate load, unconsumed fuel will
collect in the engine’s exhaust stack and form an oily coating.
|
Applicable
standards for Using load banks with emergency power generating systems
It is important for consulting engineers and facility
managers to understand the specific code requirements for
installation, performance, and testing of emergency power systems.
There are many codes and standards have requirements
to use load banks with emergency power generating systems like NFPA, NEC, and
ISO standards. These codes are further described as follows:
The National Fire Protection Association (NFPA)
NFPA 37: Standards for the Installation and Use of Stationary
Combustion Engines and Turbines
This standard establishes criteria for minimizing the
hazards of fire during the installation and operation of stationary
combustion engines and gas turbines.
This standard provides minimum fire safety requirements for
the installation and operation of stationary combustion engines and gas
turbines.
NFPA 70B: Recommended Practice for Electrical Equipment Maintenance
This recommended practice applies to preventive maintenance
for electrical, electronic, and communication systems and equipment and is
not intended to duplicate or supersede instructions that manufacturers
normally provide. Systems and equipment covered are typical of those
installed in industrial plants, institutional and commercial buildings, and
large multifamily residential complexes.
Consumer appliances and equipment intended primarily for
use in the home are not included.
Also, the purpose of this recommended practice is to reduce
hazards to life and property that can result from failure or malfunction of
industrial-type electrical systems and equipment.
NFPA
99 - Healthcare Facilities Code
Healthcare
facilities must exercise Emergency and Standby Power Systems under load and
operating temperature conditions for at least 30 minutes at intervals of not
more than 30 days.
NFPA 101 – Life Safety Code
NFPA 101,
Article 7.9.2.4 requires that emergency generators be installed, tested, and
maintained in accordance with NFPA 110. Provisions dealing with maintenance
and testing of emergency generators can be found in NFPA99, Article 4.4,
which deals with issues such as:
NFPA
110 - Standard for Emergency Generator Systems
This
standard sets safety standards to protect commercial building occupants by
making sure generator-powered backup lighting will operate as expected.
Monthly testing is performed on generators whose failure could result in
injury or death. If a generator fails a monthly test, it should be tested
annually for two continuous hours using a load bank. Under the continuous
test, the generator should be operated at 25 percent of the nameplate
kilowatt rating for 30 minutes, at 50 percent of the kilowatt rating for 30
minutes and at 75 percent of the kilowatt rating for 60 minutes.
The
National Electrical Code (NEC)
NEC
Article 700 - Emergency Systems
Emergency
systems are required to receive an operating permit as determined by the
local code enforcement authority. This requirement is a lifeline for
occupants, ensuring that lighting and life safety loads take priority over
other building loads. Should the main electrical power supply fail, backup
emergency power for life safety systems must be available within 10 seconds.
NEC
Article 701 - Legally Required Standby Systems
It requires
standby power to be available to legally required systems within 60 seconds
of power loss. While NEC 700 is designed to ensure that people can exit a
building, NEC 701 responds to the needs of firefighters and other personnel
responding to an emergency.
NEC
Article 702 - Optional Standby Systems
Applies
to situations where standby generators are optional. In these cases, the
systems may be put in place to protect against economic loss or business
interruptions. For instance, data centers may elect to install backup power
because an outage could result in large revenue losses.
NEC
Article 708 - Critical Operations Power Systems
This
article was developed following the 9/11 World Trade Center, Hurricane
Katrina, and Hurricane Rita disasters in the United States. It requires a
commissioning plan for on-site backup generation, baseline testing, and
periodic witness testing, as well as a documented preventive maintenance
program, written test records, and a method for testing all critical power
systems for maximum anticipated load conditions.
ISO8528
(BS 7698) - Reciprocating internal combustion engine driven alternating
current generating sets
ISO
8528 (BS 7698) Part 6 is the standard for testing engine-driven generating
sets. It details general test requirements and defines functional and
acceptance load bank testing. Functional tests must always be performed, and
usually occur at the manufacturer’s test cell.
ISO
8528 (BS 7698) Part 6 defines three performance classes - G1, G2, and G3. An
additional class, G4, is reserved for performance criteria which are agreed
upon between the supplier and the buyer. Each performance class has different
criteria depending on the characteristics of the generator set:
Table-1 below
lists the performance class and their criteria and application examples.
Note:
The
performance class relevant for the application must be followed to be within
the standard and achieve maximum performance.
Table-1:
Generator’s Performance Class
Table-2 shows the
acceptance (dip) and rejection (overshoot) parameters identified by ISO
8528-5. Class G4 is reserved for limits that are unique and must be agreed
upon by the manufacturer and customer. ISO 8528-5 also sets limits on
recovery times for each class and identifies how recovery time is measured.
Table-2: ISO 8528-5
acceptance (dip) and rejection (overshoot) Limits
Note:
AMC: Agreed between Manufacturer and Customer
|
In the next
article, we will explain the different types of Load Banks. So, please keep
following.



Great job Eng. Ali as usual. Thanks for such an interesting topic and looking forward to the next article.
ReplyDeleteGod Bless You