Subject of Previous Article |
Article
|
|
Glossary of Generators – Part One |
|
|
Glossary of Generators – Part Two |
|
First: Reasons for having on-site generators
Second: Applicable performance standards for generator sets
Third: Selection Factors Used For Generators Sizing Calculations
|
|
Today, we will continue explaining other Selection factors used for Generators Sizing Calculations.
Third: Selection Factors Used For Generators
Sizing Calculations
|
as we indicated before that preliminary factors for selecting a generator for certain
project, which will be as follows:
|
3- Location Considerations
|
One
of the first design decisions will be to determine whether the location of
the generator set will be inside a building or outside in a shelter or
housing. Making a good generator placement
decision can prevent problems and ensure operation of the unit(s) when they
are needed. For example, determining whether an
application would be best served by a single, large generator or a paralleled
solution with multiple, smaller generators can impact the location decision
significantly.
For
both indoor and outdoor locations, you must take care of the following
issues:
|
1- Outdoor Location Considerations
A- Sound Considerations:
B-
Weather protective housing
C-
Starting and accepting load
D-
Several auxiliary heating devices
E-
Fuel conditioning and heating
F-
Service access
G-
Security fences and sight barriers
H-
Property line distances
I-
Engine exhaust must be directed away from vents and building openings.
J-
Grounding – Electrodes or grounding rings may be required for
separately–derived system and/or equipment grounding.
K-
Lightning protection.
|
2- Indoor Location Considerations
Indoor Generator Installation
Indoor
locations generally require a dedicated room with fire resistive
construction.
Providing
the required airflow to an interior room may be difficult. Fire dampers in
ductwork to interior rooms are generally not permitted. Ideally the room will
have two exterior walls opposite each other so that intake air flows over the
generator set and is discharged out the opposite wall on the radiator end of
the unit.
A-
Dedicated generator room
B-
Fire rating of room construction
C-
Working space
D-
Type of cooling system
E-
Ventilation involves large volumes of air
F-
Engine exhaust
G-
Load Bank Connection
H-
Service access
|
3- Rooftop installations
Rooftop
installations, While common, require further planning and structural design
consideration. Vibration and fuel storage/delivery may be problematic with
rooftop installations. Table-1 lists the benefits and disadvantages
for Rooftop installations
Table-1: benefits and disadvantages for
Rooftop installations
|
4- Fuel Selection Considerations
|
The selection of natural gas, diesel, or LPG fuel will affect generator set availability and sizing. Often, generator sets running on gas or LP must be oversized due to de-rating. For example, The standard de-rating formula states that for every 1000 ft above sea-level, a gasoline, diesel, or liquid propane generator usually should be de-rated by 2–3% of its standard output. In case of generators using natural gas, the de-rating factor is typically closer to 5%.
you
must take care of the following issues:
1-
Diesel Fuel
2-
Biodiesel Fuel
3-
Natural Gas
4-
LPG (Liquefied Petroleum Gas)
5-
Gasoline
6-
Substitute Fuels
In
general, diesel engines may be run on substitute fuels
with acceptable lubricity during periods when the supply of No. 2–D
diesel fuel is temporarily limited. Use of substitute
fuels may affect warranty coverage, engine performance, and emissions. The
following substitute fuels are generally within prescribed limits:
|
5- Site Considerations
|
An
engine requires a certain quantity of air for combustion to achieve its rated
power. Altitude, temperature and humidity will all affect the air density.
The environment or site conditions also
impact an engine or generator rating, thus impacting the rating of the entire
generator.
These Conditions include:
An
engine requires a certain quantity of air for efficient combustion to achieve its rated power. Altitude,
temperature and humidity will all affect the air density. Therefore, a de-rating of the engine
must occur in high altitude and/or high temperature conditions in order for
the generator to
meet performance expectations.
1- Ambient Temperature
Table-2: Generator Class Vs.
Temperature Rise
For prime power:
The F class has a 105°C rise or total
temperature limit of 155°C (40°C ambient temperature + 10°C hot-spot margin +
105°C temperature rise) or less.
The H class allows for a 125°C rise or
total temperature limit of 175°C or less: 40°C + 10°C + 125°C
For standby power:
The F class has a 130°C temperature rise
limit or 180°C total temperature: 40°C + 10°C + 130°C
The H class has a 150°C temperature rise
or 200°C total temperature limit: 40°C + 10°C + 130°C
Notes:
2-
Altitude
The higher the altitude, the lower the
air density. The altitude/temperature
de-rating chart found in TMI can be used for proper de-rating information for
generators and each specific engine. Figure
.1 shows a sample engine TMI de-rate chart.
(TMI: Technical Marketing Information).
Fig.1: TMI Sample
Example:
A site with 200kW generator at 2,500ft and 122˚F, what is the de-rated rating of this generator?
Solution:
According to manufacturer’s data, this unit de-rates 2% per 1,000’ above 1,000’ above sea level (ASL) and 3% per 10˚ over 77˚F.
At our given site, conditions with these deration factors, we have 1,500’ of altitude and 45˚F to account for and properly de-rate.
1,500’ requires 3% of deration and 45˚F requires 13.5% deration for a total deration factor of 16.5%.
The de-rated power rating = 200 x (100-16.5)/100 = 167 KW
This means the 200kW unit you were expecting will only make 167kW at these site conditions. Typically, the only way to overcome this is to oversize the generator set accordingly.
3- Corrosive Atmospheres
4- Humidity
5-
Dust
|
In the next article, we will
continue explaining other Selection factors used for Generators Sizing Calculations.
So, please keep following.
Back To |





No comments:
Post a Comment